COOPER LIGHTING - SURE-LITES
DESCRIPTION
Type
The Sure-Lites watertight, corrosion resistant exit with tough polycarbonate
lens is designed for use where rain, moisture, dust or corrosives are
present. Economical long-life fluorescent lamps provide highly visible
signage and downlighting. The vibration resistant lamps make the UMX
perfect for heavy industrial applications (NEMA 4X Listed).
Catalog #
Project
Date
Comments
Prepared by
SPECIFICATION FEATURES
Electronic
Housing Construction Cont.
- Tough, high contrast
polycarbonate lens
Code Compliance
- Dual Voltage Input
120/277 VAC, 60 Hz
- Line-latching
- UL 924 Wet Location Listed
- Life Safety NFPA 101
- NEC/OSHA
- Rubber booted momentary
test switch and gasketed
charge indicator lamp
- Surface mount only
- Fully gasketed housing
- Wet Location Listed for
operation in ambient
temperatures above
- Solid-state Voltage
Limited Charger
- Most State and Local Codes
Warranty
- Exit: 1-year
- Solid-state Switching
- Brownout Circuit
- Low-Voltage Disconnect
- Overload/Short Circuit
Protection
- Battery: 5-year pro-rata
(Lead Calcium); 15-year
pro-rata (Nickel Cadmium)
- Sealed Test Switch/Power
Indicator Light
32 degrees F.
Lamp Data
- AC: Two F6T5 fluorescent lamps
- DC: Two 6V, 6W DC lamps
- Long-life, low energy
consumption
Battery
UMX
SERIES
Housing Construction
- NEMA 4X corrosion
resistant fiberglass
housing
- 6 Volt Sealed Lead Calcium
or Sealed Nickel Cadmium
- Maintenance-Free, Long-Life
- Full Recharge Time
24 hrs. (max.)
- Available with emergency
lighting heads mounted on
enclosure - consult Cooper
Lighting Representative
- Industrial grey color
- Vented enclosure
WET LOCATION EXITS
SELF-POWERED
EMERGENCY FLUORESCENT
LAMPS
Exit Lighting
11 3/4"
[298mm]
ENERGY DATA
Charge Mode (Fully Discharged Battery)
Sealed Lead Calcium Battery
Fluorescent Exits - 6W Lamps
Input Power:
120V= 41W
277V= 43W
Input Current (Max.):
120V= .51A
7 1/2" [191mm]
11 3/4" [298mm]
277V= .22A
Power Factor:
120V= >.66
277V= >.69
T.H.D.:
120V= <14%
277V= <14%
Standby Mode (Fully Charged Battery)
Sealed Lead Calcium Battery
Sample Number: UMX203
Input Power consumption is reduced by
approximately 18 Watts in the standby
operating mode.
Sealed Nickel Cadmium Battery
Fluorescent Exits - 6W Lamps
Input Power:
Series
Letter Color / Arrow
Direction
Options
=Dual Heads
DH
Accessories
Protective Housing
=Self-Powered Wet
Location with
Fluorescent
Lamps
UMX
=Red Letters / Right Arrow
Wire Guard
=
WG7
8
120V= 29W
Polycarbonate Vandal Shield
VS2
=Red Letters / No Arrow
=
7
277V= 29W
Polycarbonate Vandal Shield -
=
Weather Proof
VS2WP
=Red Letters / Left Arrow
=Red Letters / Double Arrow
=Green Letters / Right Arrow
=Green Letters / No Arrow
=Green Letters / Left Arrow
6
5
4
3
2
1
Input Current (Max.):
120V= .42A
Battery
=Self-Powered, Lead
Calcium
20
277V= .17A
Power Factor
=Lead Calcium Battery
w/Remote Capability
10
120V= >.57
=Green Letters / Double
Arrow
277V= >.62
=Self-Powered, Nickel
Cadmium
22
T.H.D.:
120V= <9%
277V= <38%
Specifications and Dimensions subject to change without notice.
ADX041112
10/02/2008 9:07:48 AM
Consult your representative for additional options and finishes.
UMX EXITS
WATTAGE RATINGS
UMX201 – UMX208 Lead Calcium=18W for 1 1/2 hrs.; 15W for 2 hrs.
UMX101 – UMX108 Lead Calcium=27W for 1 1/2 hrs.; 24W for 2 hrs.
UMX221 – UMX228 Nickel Cadmium=15W for 1 1/2 hrs.; 12W for 2 hrs.
TECHNICAL DATA
Lamps
Solid-State Charger
Brownout Circuit
Sealed Lead Calcium Battery
Two F6T5 fluorescent lamps
provide long life and normal
mode illumination of the
lens. Two 6V, 6W DC lamps
illuminate the face panel in
the emergency mode.
Supplied with a 120/277 VAC,
voltage regulated solid-state
charger. Immediately upon
restoration of AC current after
a power failure, the charger
provides a high charge rate.
The charge circuit reacts to the
condition of the battery and
alters the rate of charge in
order to maintain peak battery
capacity and maximize battery
life. Solid-state construction
recharges the battery following
a power failure in accordance
with UL 924.
The brownout circuit on Sure-
Lites’ exits monitors the flow
of AC current to the exit and
activates the emergency
The fully sealed, long-life,
maintenance-free, lead calcium
battery is ideal for emergency
lighting applications. These
batteries typically provide 8 to
10 years of life and may be
operated in any position.
lighting system when a
predetermined reduction of
AC power occurs. This dip
in voltage will cause most
ballasted fixtures to extinguish
causing loss of normal lighting
even though a total power
failure has not occurred.
Housing Construction
Sealed Nickel
Cadmium Battery
The Sure-Lites UMX Series
incorporates a rugged
Sure-Lites’ sealed nickel
cadmium batteries are
enclosure of moisture and
corrosion resistant industrial
grey fiberglass with a durable
polycarbonate lens. Housing
is fully gasketed. A breather
vent permits ventilation of
internal pressure from gases
released by charging batteries.
UMX Series Exits are suitable
for surface mounting only. Wet
Location Listed for operation in
ambient temperatures above
32°F. Optional Thermal Heater
available to facilitate use
maintenance-free with a life
expectancy of 15 years. The
sealed rechargeable nickel
cadmium battery offers high
discharge rates and stable
performance over a wide range
of temperatures. The specially
designed resealable vent
automatically controls cell
pressure, assuring safety and
reliability. This battery is best
suited for harsh ambient
Solid-State Transfer
The UMX Exit incorporates
solid-state switching which
eliminates corroded and pitted
contacts or mechanical failures
associated with relays. The
switching circuit is designed to
detect a loss of AC voltage and
automatically energizes the
lamps. Upon restoration of
AC power, the emergency
lamps will switch off and the
charger will automatically
recharge the battery.
Overload and Short
Circuit Protection
The solid-state overload
monitoring device in the DC
circuit disconnects the lamp
load from the battery should
excessive wattage demands
be made and automatically
resets when the overload or
short circuit is removed. This
overload current protective
feature eliminates the need
for fuses or circuit breakers
for the DC load.
temperatures because the
electrolyte is not active in the
electrochemical process.
in unheated areas where
battery performance would
be diminished due to low
temperature operation.
Warranty
Test Switch/Power Indicator
Light
Line-Latched
All Sure-Lites’ products are
backed by a firm one-year
warranty against defets in
material and workmanship
(excluding lamps). Maintenance-
Conveniently located rubber
booted Test Switch allows for
manual verification of proper
operation of the transfer circuit
Sure Lites’ line-latched
electronic circuitry makes
installation easy and
economical. A labor efficient
AC activated load switch
prevents the lamps from turning
on during installation to a
non-energized AC circuit.
Line-latching eliminates the
need for a contractor’s return
to a job site to connect the
batteries when the building’s
main power is turned on.
and emergency lamps. A sealed free, long-life, sealed lead
light emitting diode (Power
Indicator Light) provides visual
assurance that the AC power
is on.
calcium batteries carry a
five-year, pro-rata warranty.
Maintenance-free, long-life,
sealed nickel cadmium batteries
carry a fifteen-year pro-rata
warranty.
Specifications and Dimensions subject to change without notice.
Sure-Lites • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801
ADX041112
10/02/2008 9:07:48 AM
|