ꢀ
5HDG\*XDUGꢀ5(1
6HꢁXULW\ꢀ6\VWHP
ꢀ
OFF
AWAY
STAY
AUX
8VHUꢀ*XLGHꢀ
K5964-1 9/01
6<67(0ꢁ29(59,(:ꢁ
Features
General Information
This system offers you three forms of protection: burglary, fire, and emergency, depending on the
configuration of your system. The system consists of a master keypad for controlling system operation,
various wireless sensors that provide perimeter and interior burglary protection, and optional smoke or
combustion detectors to provide early fire warning. In addition, optional wireless keypads may have been
installed to allow you to control the system away from the master keypad. The system may also be
controlled from a remote telephone and can be used as a speaker phone.
The system uses microcomputer technology to monitor all protection zones and system status, display
appropriate information on the keypad display, and initiate appropriate alarms. Your system may also have
been programmed to automatically send alarm or status messages over the phone lines to a central alarm
monitoring station, and may also be capable of two-way voice communication with the central station.
The user features of this security system are listed below. Ask your installer which features have been
programmed for your system.
• STAY and AWAY arming modes: By using these modes you can protect either the perimeter only, or
the entire premises.
• 3 panic key functions: Designated keys allow you to manually activate fire, personal emergency, or
silent alarms. Refer to the PANIC KEYS section for detailed information.
• Paging feature: Alerts you to certain system conditions by displaying code numbers that indicate the
type of condition that has occurred. In addition, pressing the AUX key can send a predefined message to
your pager, if programmed to do so (see AUX key function below). Refer to the PAGING FEATURE
section for detailed information.
• Real-time clock: Keypad displays current time. Refer to the CLOCK/CALENDAR section for
procedures for setting the time.
• Voice announcement of system status: The master keypad’s built-in speaker announces system status at
the press of a key. Refer to the CHECKING SYSTEM STATUS section for detailed information.
• Message center: The system allows recording and play back of brief messages. Refer to the
RECORDING/PLAYBACK MESSAGES section for procedures.
• Device activation: Designated keys allow you to turn lights and/or other devices on and off. In addition,
some devices (e.g., a light) may be programmed to activate automatically as a result of a system event
such as an alarm or trouble condition. Refer to the USING POWERLINE CARRIER DEVICE
COMMANDS section for detailed information.
• AUX key function: Designated key lets you activate a predefined series of keystrokes with a single press
of the AUX key plus user code, if programmed to do so (see Paging feature above). Refer to the AUX
FUNCTION section for detailed information.
• Scheduling feature: Allows you to schedule the automatic activation or deactivation of X-10 devices or
program events (e.g. alarm clock, reminder, and latch key).
– 3 –
6<67(0ꢁ29(59,(:ꢁ
Features
• Two-way voice: Allows the central station to listen, talk to or conduct two-way conversations with
individuals on the premises Refer to the TWO-WAY VOICE section for detailed information.
• Phone Control: Provides a remote interactive phone capability that permits access to the security system
from any off-site touch-tone telephone.
• Speaker Phone Operation: The system is capable of operating as a speaker phone allowing hands free
telephone conversation.
• Security Codes: The system is capable of supporting an Installer code, Master user code and six
additional User codes. Refer to the SECURITY CODES section for detailed information.
– 4 –
ꢁ
6<67(0ꢁ29(59,(:ꢁ
General Operation
Zones
Your system's sensing devices have been assigned to various "zones." For example, the sensing device on
your entry/exit door may have been assigned to zone 01, sensing devices on windows in the master bedroom
to zone 02, and so on. These numbers appear on the display when an alarm or trouble condition occurs.
ReadyGuard-REN is not intended for UL985 Household Fire applications unless a 24-hour
backup battery (P/N LYNXRCHKIT-HC) is installed.
8
/ꢀ
Fire Protection
The fire protection portion of your security system (if used) is always active and will sound an alarm if a
fire condition is detected. Refer to the FIRE ALARM SYSTEM section for important information concerning
fire protection, smoke detectors and planning emergency exit routes from the premises.
Burglary Protection
Your system provides two modes of burglary protection: STAY and AWAY. STAY mode protects the
perimeter only, allowing you to freely move within inside the premises. AWAY mode protects the entire
system. Both modes provide an entry delay time that allows you to reenter the premises without setting off
an alarm. For additional security, you can turn the entry delay off when arming the system by using the
NO DELAY key in combination with the desired arming key. The system also allows you to bypass selected
zones before arming the system, if desired. Refer to the BYPASSING PROTECTION ZONES section. The
system also provides a CHIME mode, for alerting users to the opening of protected doors and windows
while the system is disarmed.
You must turn on ("arm") the burglary protection portion of your system before it will sense burglary
alarms. To arm the system, enter your user code then press the desired arming key (AWAY or STAY).
Refer to the ARMING THE SYSTEM section for detailed procedures and information.
Security Codes
At the time of installation, you were assigned a personal 4-digit security or “master user” code. You must
enter the user code when arming and disarming the system, and when performing other system functions. As
an additional security feature, other users who do not need to know your code can be assigned up to 6
different security codes. Refer to the SECURITY CODES section for procedures on adding security codes to
the system.
Alarms
When an alarm occurs, the keypad and external sounders will sound for about 15-seconds, and the keypad
will display the zone(s) causing the alarm. After 15-seconds, the siren stops temporarily and voice
– 5 –
6<67(0ꢁ29(59,(:ꢁ
General Operation
announcements of the zones in alarm begins. When these zones have been announced, the siren sounds
again and the cycle repeats itself, until the system is disarmed (code + OFF) or until alarm bell timeout
occurs. If your system is connected to a central monitoring station, an alarm message will be sent. To stop
the alarm sounding, simply disarm the system. The zone(s) causing the alarm remain displayed indicating
memory of alarm. Refer to the DISARMING THE SYSTEM section for information about clearing the
memory of alarm display
Two-Way Voice Feature
The ReadyGuard-REN supports voice dialog between an operator at the central station and an individual at
the premises. This feature allows the central station to listen, talk to or conduct a two-way conversation with
an individual(s) at the premises and allows the operator to gather information about the nature and location
of the alarm that may be helpful in responding to fire, police or rescue departments. If the Two-way Voice
Feature has been programmed and an alarm condition is detected the system sends an alarm message to the
central station. After acknowledgement is received, a “listen in to follow” message is sent to the central
station. By responding to this message the central station operator can enter commands that allow him to
initiate a 5-minute voice session. The options allow the operator to enter the following modes:
• Talk: Allows the operator to speak to individuals at the premises through the system speaker.
• VOX (2-way voice): Allows the operator to hold a two-way (speak and listen) conversation with
individuals at the premises.
• Listen: Allows the operator to listen to any activity at the premises through the system microphone.
If a subsequent zone is violated during a voice session, the system will terminate the session and process the
alarm. During the voice session, the ARMED (red) and READY (green) LEDs will alternately blink in the
Talk and VOX Modes but not during Listen Mode.
– 6 –
48,&.ꢁ9,(:ꢁ2)ꢁ6<67(0ꢁ)81&7,216ꢁ
NOTE:
= Boxes represent the entering of your 4-digit user code.
SECURITY FUNCTIONS
Checking system status: ---------------------- STATUS
To arm in STAY mode: ---------------------
*
+ STAY
To restart exit delay: ------------------------- STAY (only if programmed and system armed in Stay mode)
*
To arm in AWAY mode: --------------------
To arm with NO DELAY: ------------------
+
AWAY
*
+
AWAY or STAY
+
NO DELAY
To arm if Quick Arm is active: ------------- AWAY or STAY (hold down for at least 2 seconds)
To disarm system and silence alarms: -----
To bypass a zone(s): --------------------------
+
+
OFF
BYPASS + 2-digit zone number(s)
To turn Chime mode on or off: ------------- FUNCTION
+
CHIME
*
Security code is not required if Quick Arm is active. Instead, press and hold down the STAY or AWAY key.
MESSAGE CENTER
To record a message: ------------------------- FUNCTION
To stop recording before end of 20 secs: - OFF
To play back a message: --------------------- FUNCTION
+
+
RECORD
PLAY
VOLUME ADJUSTMENT
To adjust message playback/announcement volume: - FUNCTION
+
VOLUME + [3] or [6]
OFF
VOLUME + [3] or [6]
To mute system announcements: ----------- FUNCTION
To restore/unmute announcements: ------- FUNCTION
+
+
VOLUME
+
SPEAKER PHONE OPERATION
To enter speaker phone mode: -------------- [#] + AUX
To exit speaker phone mode: --------------- OFF
To enable/disable (toggle) ringer: ---------- [#] + VOLUME
+
AUX
To return the keypad to telephone mode (after clearing an alarm or trouble or after disarming the system):
[#] + AUX
To flash (switch between two calls using call waiting): AUX *
*To return to first call wait at least two (2) seconds and enter AUX again.
– 7 –
48,&.ꢁ9,(:ꢁ2)ꢁ6<67(0ꢁ)81&7,216ꢁ
REMOTE PHONE CONTROL OPERATION
To remotely disarm:
[1]
[2]
[3]
--------------------------
+
+
+
To remotely arm in AWAY mode:
To remotely arm in STAY mode:
---------
----------
To remotely arm in AWAY or STAY mode with NO DELAY:
To remotely activate X-10 devices 1-6: [#] + [4] + device no.
[2] or [3] + [0]
+
---
To remotely activate X-10 devices 7 & 8:
[#] + [4] + device no.
+
To remotely deactivate X-10 devices 1-6: [#] + [7] + device no.
To remotely deactivate X-10 devices 7 & 8:
[#] + [7] + device no.
[6] + zone no.
[6] + [#]*
+
To remotely bypass a zone:
------------------
+
+
To remotely activate forced bypass:
-------
To remotely check system status:
[*]
----------
To hang up:
[9]
-------------------------------------
+
*If forced bypass was enabled by your installer.
OTHER FUNCTIONS
To set the time and date:
FUNCTION
FUNCTION
[63]
[64]
---------------------
+
+
+
+
To set scheduling:
-----------------------------
To activate X-10 devices 1-6:
FUNCTION
FUNCTION
LIGHTS ON
device number
---------------
+
+
+
To activate X-10 devices 7 & 8:
To deactivate X-10 devices 1-6:
+ FUNCTION
LIGHTS ON
device number
------------
------------
+
+
LIGHTS OFF
device number
+
To activate or deactivate X-10 dev. 7 & 8:
+ FUNCTION
**
LIGHTS OFF
device number
+
+
To add a user code:
To delete a user code
CODE
CODE
TEST
OFF
user no. (02-08)+ user code
--------------------------
+
+
+
**
: -
------------------------
-----------------------
user number 02-08)
(except Master Code)
+
(
To turn Test mode on:
To turn Test mode off:
+
+
To use the defined AUX function:
Press and hold AUX key 2 seconds (4 beeps)
Press and hold AUX key 2 seconds (4 beeps)
----------
+
To send message to pager:
-------------------
** Only the master code can be used to add or delete another user code.
– 8 –
6<67(0ꢁ29(59,(:ꢁ
About the Master Keypad
General
IMPORTANT: If the keypad beeps rapidly upon entering the premises, an alarm has occurred during your
absence and an intruder may still be on the premises. LEAVE IMMEDIATELY and CONTACT THE
POLICE from a nearby safe location.
The keypad allows you to control all system functions. In the speaker phone mode the keypad becomes a
full-function telephone keypad The keypad features telephone-style keys and a Liquid Crystal Display
(LCD), which shows the nature and location of all occurrences.
ARMED
READY
OFF
AWAY
STAY
AUX
1
2
3
RECORD
VOLUME
PLAY
4
5
6
LIGHTS ON
TEST
BYPASS
7
8
9
LIGHTS OFF
CODE
CHIME
0
#
*
STATUS
NO DELAY FUNCTION
01100-006-V0
The keypad also features a built-in sounder, which will sound during alarms and troubles. The keypad also
"beeps" during certain system functions, such as during entry/exit delay times, in Chime mode, and when
depressing any of the keys (to acknowledge the key press). In addition, a built-in speaker announces system
status.
– 9 –
6<67(0ꢁ29(59,(:ꢁ
Master Keypad Definitions
21
3
1
2
20
4
19
5
6
7
ARMED
READY
OFF
AWAY
STAY
AUX
1
2
3
RECORD
VOLUME
PLAY
18
4
5
6
LIGHTS ON
TEST
BYPASS
7
8
9
LIGHTS OFF
CODE
CHIME
8
9
17
0
#
*
STATUS
NO DELAFUNCTION
16
11
12
10
14
15
13
01100-007-V0
IMPORTANT!: When you use the keypad to enter codes and commands, press the keys within 2
seconds of one another. If 2 seconds elapse without a key depression, the entry is aborted and must
be repeated from its beginning.
NOTE: Different timeouts may occur when defining auxiliary functions and setting the real-time
clock.
– 10 –
6<67(0ꢀ29(59,(:ꢀ
Master Keypad Definitions
NOTE: The system functions described below are for reference only, and require additional key entries to activate.
1. DISPLAY WINDOW: Liquid Crystal Display
(LCD). Displays protection point identification and
system status, messages, and user instructions.
13. LIGHTS ON
/
LIGHTS OFF KEYS: Turns lights or
other devices on or off, if programmed by the installer.
14. AUX KEY: Can be programmed to either perform a
2. ARMED INDICATOR: (RED) Lit when the
system has been armed (STAY, AWAY, NO
DELAY). Blinks when armed and fault exists, or
once per second when AVM (VOX or Talk) or
speaker phone mode is active.
predefined function or to send a preset message to a
pager.
15. STAY KEY: Arms the perimeter burglary protection,
guarding protected doors, windows and other perimeter
protection points, and sounds an alarm if one is opened.
Interior protection is not armed, which allows
movement within your house without causing an alarm.
Entrance can be made through an entry delay zone
without causing an alarm if the system is disarmed
before the entry delay time expires.
3. READY INDICATOR: When lit, indicates system
is ready to be armed; blinking indicates system is
not ready (a zone is open). Blinks once per second
when AVM (VOX or Talk) or speaker phone mode
is active.
4. PLAY KEY: Announces a user’s message if one
was previously recorded. See RECORD function.
5. TEST KEY: Tests the system and alarm
sounder.
16. AWAY KEY: Completely arms both perimeter and
interior burglary protection for backup protection by
sensing an intruder's movements through protected
interior areas as well as guarding protected doors,
windows, etc. Entrance can be made through an entry
delay zone without causing an alarm if the system is
disarmed before the entry delay time expires.
6. BYPASS KEY: Removes individual protection
zones from being monitored by the system. Displays
currently bypassed zones.
7. CODE KEY: Allows entry of additional user
codes that can be given to other system users.
8. CHIME KEY: Turns the Chime mode on and
17. OFF KEY: Disarms the burglary portion of the
system, silences alarms and audible trouble indicators,
and clears alarm trouble display after the problem has
been corrected.
off. When on, any entry through a protected delay
or perimeter zone while the system is disarmed
will cause a tone and voice descriptor to sound at
the keypad.
18. MICROPHONE: Used to record personal messages
up to 20 seconds long, and for 2 way voice and speaker
phone.
19. SPEAKER: Source of audible internal warning and
confirmation sounds, status announcements, as well as
alarms (see "Summary of Audible Notifications").
9. INTERNAL SOUNDER: Source of alarm sounds
(see "Summary of Audible Notifications" section).
10. FUNCTION KEY: Allows alternate key
functions.
20. RECORD: Activates the recording function to record
personal messages.
21. VOLUME: Sets the volume of system announcements
11. NO DELAY KEY: Used with STAY or AWAY
and status beeps.
function to eliminate the entry delay. Alarm sounds
immediately if entry is opened.
–– KEYS 0-9: Used to enter your individual security
access code(s).
12. STATUS KEY: When pressed prior to arming,
the keypad will display all open zones, and will
announce system status.
– 11 –
6<67(0ꢁ29(59,(:ꢁ
About the Display and Indicators
LOW BAT AC
AWAY
INSTANT CHIME TEST
REC MESSAGE
ALARM FIRE BYPASS FAULT
STAY
(for other displays, see Trouble Messages)
Display Definitions
ALARM:
Appears when the system is armed and an intrusion has been detected (also appears
during a fire alarm or audible emergency alarm). Accompanied by the protection zone
that is in alarm.
AWAY:
INSTANT:
STAY:
All burglary zones, interior and perimeter, are armed.
Entry delay is turned off.
Perimeter burglary zones, such as protected windows and doors, are armed.
ReadyGuard-REN is not intended for UL985 Household Fire applications unless a 24-hour backup
battery (P/N LYNXRCHKIT-HC) is installed.
FIRE:
Appears when a fire alarm or fire fault is present. Accompanied by a display of the zone
that is in alarm.
LOW BAT:
AC:
Low battery condition in a wireless sensor (if zone number is displayed) or low system
battery (if no zone number is displayed). If 00 is displayed, a wireless keypad (5827) has
a low battery condition.
Appears when AC power is present. If not displayed, the system is operating on backup
battery power.
CHIME:
TEST:
Appears when the Chime feature is activated.
Appears when the system is in Test mode.
REC:
Appears when the system is in Recording mode.
MESSAGE:
BYPASS:
FAULT:
Appears when a message has been recorded and has not yet been played back.
Appears when one or more burglary protection zones have been bypassed.
Appears at any time a malfunction is discovered in the system; or any time an open is
detected in a fire zone; or when a fault in a day/night burglary zone is discovered during
a disarmed period. Accompanied by a display of the zone number in trouble.
Appears in place of the clock when the speaker phone mode is active.
Appears during a remote phone control session.
PH:
PC:
LED Meanings
ARMED LED: ON = System armed
(Red)
OFF = System disarmed
Blinking = System armed, but a fault exists
Blinking alternately with READY LED = AVM (VOX or Talk) or speaker phone mode
is active
READY LED: ON = System disarmed, ready to arm
(Green)
OFF = System armed
Blinking = System disarmed, not ready to arm (a fault exists)
Blinking alternately with ARMED LED = AVM (VOX or Talk) or speaker phone mode
is active.
– 12 –
6(&85,1*ꢀ7+(ꢀ35(0,6(6
Checking System Status
ꢁ
General Information
Before arming your system, all protected doors, windows, and other protection zones must be closed or
bypassed (see the BYPASSING PROTECTION section). Pressing the STATUS key will announce all zones
that are faulted, as well as any other abnormal system condition, making it easier for you to secure any open
zones.
READY LIGHT: The green READY indicator on the keypad will be lit if the system is ready to be
armed. If blinking, the system is not ready.
Press the STATUS Key
Press the STATUS key once to announce the general status of the system. Depending on the current state of
the system the following phrases may be heard:
disarmed, ready to arm [message] [check system]
disarmed, [not ready to arm], [message]
armed [away] [stay] [instant] [check system] [message]
NOTE: The phrases shown in brackets are variable, and are announced only if appropriate in the current
state of the system.
Press the STATUS key a second time† to announce specific system status. Depending on the current state
of the system the following phrases may be heard:
fire alarm [zone voice descriptors]
alarm [zone voice descriptors]
fire fault [zone voice descriptors]
fault [zone voice descriptors]
low battery [zone voice descriptor]
system low battery
check system
AC loss
zones bypassed
†
chime
(second depression must be made within 10 seconds of the first)
VOLUME LEVEL: The volume level of system announcements can be increased or decreased. Refer to the
MESSAGE RECORDING/PLAYBACK section for the procedure.
System Can Be Armed
The READY LED will be lit once all protection zones have been closed or bypassed. You may now arm the
system as usual.
– 13 –
6(&85,1*ꢀ7+(ꢀ35(0,6(6
Arming the System
ꢁ
Arming in Stay Mode
Use this mode when you are staying home, but expect someone to use the entrance door later. Close all
protected perimeter windows and doors before arming. The green READY indicator on the keypad should
be lit if the system is ready to be armed.
**
or press and hold
STAY
To arm in STAY mode:
+ STAY
Your User code**
** See Quick Arming paragraph.
The keypad beeps three times and displays the armed STAY message. The red ARMED indicator lights and
the system announces “armed STAY–exit now.”
When armed in STAY mode, the system will sound an alarm if a protected door or window is opened, but
you may otherwise move freely throughout the premises. Late arrivals can enter through the entrance door
without causing an alarm, but they must disarm the system within the entry delay period or an alarm will
occur.
Restarting Exit Delay While System Armed
Ask your installer if this feature is active for your system. If active, you can restart the exit delay at any time
after arming in STAY mode. This is useful if you wish to open the entry/exit door to let someone in after
arming the system, and avoids having to disarm the system and then re-arm it again.
key
To restart exit delay while system is armed in STAY mode: Press STAY
Arming In Away Mode
Use this mode when no one will be staying on the premises. Close all protected perimeter windows and
doors before arming. The green READY indicator on the keypad should be lit if the system is ready to be
armed.
**
or press and hold
AWAY
To arm in AWAY mode:
+ AWAY
Your User code **
** See Quick Arming paragraph.
The keypad beeps twice, or beeps continuously if exit warning has been programmed for your system, and
displays the armed AWAY message. The red ARMED indicator lights and the system announces “armed
AWAY–exit now.”
When armed in AWAY mode, the system will sound an alarm if a protected door or window is opened, or if
any movement is detected inside the premises. You may leave through the entrance door during the exit
delay period without causing an alarm. You may also re-enter through the entrance door, but you must
disarm the system within the entry delay period or an alarm will occur.
– 14 –
6(&85,1*ꢀ7+(ꢀ35(0,6(6
ꢁ
Arming the System
Arming the System With No Delay
Use NO DELAY with STAY mode when you are staying home and do not expect anyone to use the
entrance door.
Use NO DELAY with AWAY mode when the premises will be vacant for extended periods of time such as
vacations, etc.
When armed with NO DELAY, the system will sound an alarm if a protected door or window is opened,
including the entrance door. You may leave through the entrance door during the exit delay period without
causing an alarm, but an alarm will sound as soon as someone reenters.
or
+
To arm with NO DELAY:
+ AWAY
STAY
NO DELAY
Your user code**
** See Quick Arming paragraph.
Quick Arming
If Quick Arm was programmed by the installer, you do not need to enter the security code to arm the
system. Instead, simply press and hold down the desired arming key for at least 2 seconds. The security
code must always be used to disarm the system, however.
To arm if Quick Arm is active:
or
hold down for at least 2 seconds
AWAY
STAY
To arm with NO DELAY if Quick Arm is active:
or
then
hold down for at
NO DELAY
AWAY
STAY
least 2 seconds
IMPORTANT: The Babysitter Code and Installer Code cannot disarm the system unless it was used to arm
the system. In addition, if the system is armed by pressing and holding the Quick-Arm buttons, neither the
Babysitter Code nor Installer Code can disarm the system.
– 15 –
6(&85,1*ꢀ7+(ꢀ35(0,6(6
Entry/Exit Delays
ꢁ
Exit Delay
Exit delay begins immediately after arming the system, and gives you time to leave through the designated
exit door without setting off an alarm. A slow beeping will sound throughout the exit delay period, if
programmed.
Exit Alarms
Exit Alarm Active
To minimize false alarms sent to the alarm monitoring company, your system may have been programmed
for this feature. Ask your installer if Exit Alarm is active for your system.
Whenever you arm the system, the exit delay begins. If an entry/exit door or interior zone is faulted when
the exit delay ends (e.g., exit door left open), the system sounds an alarm and starts the entry delay timer. If
you disarm the system before the entry delay ends, the alarm sound stops and the message "CA" is
displayed on the keypad, along with a zone number indicating the faulted zone. No message is sent to the
alarm monitoring company. To clear the exit alarm condition, the open zone must be made re-secured; to
clear the display, enter your code plus OFF.
If you do not disarm the system before the entry delay ends, and an entry/exit door or interior zone is still
open, the alarm sound continues and an "exit alarm" message is sent to the alarm monitoring company. The
message "EA" is displayed on the keypad, along with a zone number indicating the faulted zone. To stop
the alarm, the system must be disarmed (your code plus OFF); to clear the display, enter your code plus
OFF a second time. An exit alarm also results if an entry/exit door or interior zone is faulted within two
minutes after the end of the exit delay.
Entry Delay
Entry Delays give you time to disarm the system when you re-enter through the designated entrance door.
You must disarm the system before the entry delay period ends, or an alarm will occur. The keypad beeps
during the entry delay period, reminding you to disarm the system. There are two entry delays (if
programmed). The first is for your primary entrance and the second can be used for a secondary entrance,
where a longer delay is required to walk to the keypad to disarm the system.
You can also arm the system with no entry delay at all by using the NO DELAY key when arming. This can
provide greater security while on the premises or while away for extended periods of time. See ARMING
THE SYSTEM section for procedure.
See your installer for delay times programmed for your system.
Exit Delay:
00-99 seconds
00-99 seconds
Entry Delay 1:
Entry Delay 2:
00-99 seconds
– 16 –
6(&85,1*ꢀ7+(ꢀ35(0,6(6
ꢁ
Disarming the System
Use the OFF key to disarm the system and to silence alarm and trouble sounds. See the SUMMARY OF
AUDIBLE NOTIFICATION section for information, which will help you to distinguish between fire and
burglary alarm sounds.
IMPORTANT: If you return and the main burglary sounder is on, DO NOT enter the premises, but call
the police from a nearby safe location. If you return after an alarm has occurred and the main sounder has
shut itself off, the keypad will beep rapidly upon entering. This indicates that an alarm has occurred during
your absence and an intruder may still be on the premises. LEAVE IMMEDIATELY and CONTACT
THE POLICE from a nearby safe location.
To disarm the system and silence burglary alarms:
+ OFF
Your user code
The READY indicator will light (if no alarms have occurred while armed) and the keypad will beep once to
confirm that the system is disarmed.
Memory of Alarm
If an alarm occurs, the keypad displays the zone number (s) that caused the alarm and the type of alarm
(e.g., “FIRE ALARM”). These messages remain displayed until cleared by a user.
To clear the display, note the zone number displayed and enter an OFF sequence (enter your security code
and press the OFF key).
If the READY indicator is blinking, go to the displayed zone and correct the fault (close windows, etc.). If
the fault cannot be corrected, notify your alarm company.
– 17 –
6(&85,1*ꢀ7+(ꢀ35(0,6(6
Bypassing Protection Zones
ꢁ
Bypassing Individual Zones
Use the BYPASS key when you want to arm your system with one or more zones intentionally unprotected.
Bypassed zones are unprotected and will not cause an alarm when violated while your system is armed. All
bypasses are removed when an OFF sequence (security code plus OFF) is performed. Bypasses are
also removed if the arming procedure that follows the bypass command is not successful.
The system will not allow fire zones to be bypassed.
The system must be disarmed first.
BYPASS
+
2-digit zone number(s)
To bypass a zone(s):
+
for zone(s) to be
Your user code
bypassed (e.g., 01, 02, 03, etc.)
Important! All single-digit numbers must be preceded by a zero (for example, enter 01 for zone 1).
The keypad will provide a confirmation beep and display the word “BYPASS” along with each bypassed
zone number. Wait for these zones to be displayed, to be sure that intended zones are bypassed.
Arm the system as usual when the keypad displays the READY LED on steady.
Forced Bypass
Your system may allow you to easily bypass all open (faulted) zones without having to enter zone numbers
individually. Ask your installer if this feature is active.
BYPASS + FUNCTION
To bypass a zone(s):
+
Your user code
In a few moments, all open zones will be displayed along with the word “BYPASS.” Wait for these zones to
be displayed before arming. Arming the system before zones are displayed eliminates all bypasses.
Arm the system as usual when the keypad displays the READY LED on steady.
Displaying Bypassed Zones
The system allows you to determine what zones have been previously bypassed. Bypassed zones can be
displayed only when the system is disarmed, and when the “BYPASS” message described above is
displayed.
BYPASS + WAIT
To display bypassed zone(s):
+
Your user code
In a few moments, all open zones will be sequentially displayed along with the word “BYPASS.”
– 18 –
6(&85,1*ꢀ7+(ꢀ35(0,6(6
ꢁ
Panic Keys / Chime Mode
Panic Keys
Your system may have been programmed to use special keys to manually activate panic functions. The
functions that might be programmed are listed below. See your installer for the function(s) that may have
been programmed for your system.
Active Panic Functions
Keys
1 and ✴ 95
3 and # 96
✴ and # 99
Zone
Function
Your installer should
note the functions that
are active in your
system.
To use a paired key panic function, simply press both keys of the assigned pair at the same time. If your
keypad has lettered keys for panic functions, press the designated key and hold down for at least 2 seconds
to activate the panic function. Panic keys can also be activated by wireless devices such as the Ademco
5827. Ask your installer about this feature.
Types of Panic Alarms
†
A silent emergency/silent alarm sends an alarm signal to the alarm monitoring company, but there will be
no audible alarms or visual displays.
†
An audible emergency/audible alarm sends an emergency message to the alarm monitoring company and
sounds a loud, steady alarm at your keypad and at any external sounders that may be connected
(“ALARM” plus a zone number are also displayed).
†
A personal emergency/aux alarm sends an emergency message to the alarm monitoring company and
sounds at keypads, but not at external sounders. (“ALARM” plus a zone number are also displayed).
†
A supervised fire alarm sends a fire alarm message to the alarm monitoring company and uniquely
activates keypad and any external sounders (“FIRE ALARM” plus a zone number are also displayed).
† If your system is connected to an alarm monitoring company
Chime Mode
Your system can be set to alert you to the opening of a door or window, while it is disarmed, by using
CHIME mode. When activated, three beeps will sound at the keypad whenever a protected perimeter door
is opened and the zone voice descriptor will be announced. Pressing the STATUS key will display the open
protection points.
Note that the Chime mode can be turned on only when the system is disarmed.
FUNCTION
CHIME
To turn Chime mode on or off:
+
The “CHIME” message displays while Chime mode is on, and disappears from the display when Chime
mode is off.
– 19 –
86(5ꢀ)81&7,216
Paging Feature
ꢁ
Automatic Paging
If the Paging feature has been programmed for your system, your pager will respond to certain conditions as
they occur in your system by displaying a message that indicates the type of condition that has occurred.
The message appears in a 7-digit format explained below. The system can also be programmed to send up
to 16 additional digits that will appear in front of the 7-digit message. These 16 digits may consist of a PIN
number or special digits needed by the pager, account number, pauses, or any other special characters you
may choose (for example, you may want to use a special character code to distinguish between security
system messages and usual pager messages). See your installer if these additional characters are desired.
Code Format
The Pager Code takes the following form: (AAAAAAAAAAAAAAAA) EEE-00NN
AAA… = Optional 16 digits, programmed by your installer.
EEE
= 3-digit number describing the event that has occurred, as follows:
911 = Alarm (00NN following indicates the zone that caused the alarm)
101 = Open, system disarmed (00NN following indicates user number)
102 = Close, system armed (00NN following indicates user number)
811 = Trouble (00NN following indicates the zone that caused the trouble)
00NN = First two digits are always 00, followed by 2-digit user or zone number, depending on
the type of event that occurred. If NN = 00, it can mean an AC loss has occurred, the
system battery is low, or a 5827 wireless keypad battery is low. The Master Keypad
will indicate the specific condition.
Examples:
Pager displays: 911–0004
This indicates your system is reporting an alarm (911) due to a fault on zone 4 (0004).
Pager displays: 101–0005
This indicates that your system is reporting an open/disarm (101) by user 5 (0005).
Manual Paging
In addition, your system may have been programmed to send a unique pager message when the AUX key is
pressed (see AUX FUNCTION section for alternate function of this key). The actual message sent is 999-
9999 (the hyphen may not appear, depending on your pager service). This code can be used to alert the
person with the pager to whatever meaning you pre-arrange (e.g., “call home”). Ask your installer if this
has been done for your system.
To manually send the pager message, if programmed: AUX (hold until 4 beeps sound)
– 20 –
86(5ꢀ)81&7,216ꢀ
Using Powerline Carrier Device Commands
(Lights On/Lights Off Keys)
General Information
Powerline Carrier devices (e.g. X-10 brand devices) are programmable switches that can be used to
perform many different functions. Your system may be set up so that certain lights or other devices can be
turned on or off by using the device command from the keypad. Ask your installer if this has been done in
your system. If programmed for your system, some devices may activate automatically upon certain system
conditions. In this case, the following commands can be used to override the device activation. See your
installer for a full explanation of this feature.
To activate X-10 devices 1-6: FUNCTION
+
LIGHTS ON + dev. no. (2 beeps)
To deactivate X-10 devices 1-6: FUNCTION
+
LIGHTS OFF + dev. no. (2 beeps)
To activate X-10 devices 7 & 8**:
+ FUNCTION + LIGHTS ON + dev. no. (2 beeps)
Your user code
To deactivate X-10 devices 7 & 8**:
+ FUNCTION + LIGHTS OFF + dev. no. (2 beeps)
Your user code
** Devices 7 and 8 may be assigned to system devices, such as alarm bells, which should not be activated
using this command because they are activated automatically under certain system conditions. See your
installer and the table below.
Device Descriptions
See your installer for device numbers assigned for your system.
Device
Description
1
2
3
4
5
6
7
8
– 21 –
86(5ꢀ)81&7,216ꢀ
Message Recording/Playback/Volume Control
Recording a Message
Your system can record a brief message (up to 20 seconds) that can be played back later.
To record a message: FUNCTION
+
RECORD
The keypad beeps and displays “REC MESSAGE.” Begin speaking into the microphone.
NOTE: The Record function can only be performed from the master keypad. It cannot be performed from
any other wireless keypad (ex. 5827).
To stop recording before the end of 20 seconds: Press OFF
Otherwise, the recording automatically stops after 20 seconds. The keypad beeps twice, the REC display
turns off, but the MESSAGE display remains on.
Message Playback
The lighted word MESSAGE indicates that a new message is in memory. After playing the message, the
MESSAGE display turns off. See NOTE below if using a wireless keypad.
To play back a message: FUNCTION
+
PLAY
Adjusting the Volume
The volume level of message playback, system announcements, and status beeps can be changed. You can
also mute system announcements if desired. See NOTE below if using a wireless keypad.
To adjust message playback/system announcemnt volume:
†
FUNCTION
+
VOLUME + [3] or [6]
†
[3] = increases volume one level, [6] = decreases volume one level (when pressed the keys beep at the selected volume.)
Repeat the key sequence until the desired volume level is achieved.
To mute system announcements: FUNCTION OFF
+
VOLUME
+
When muted, no system announcements will be made. Recorded messages will be announced, though,
when PLAY is pressed.
To restore announcement sounding: FUNCTION
+
VOLUME + [3] or [6]
Volume level will be restored to the level that was selected prior to muting the sound.
NOTE: If a wireless keypad (5827) has been installed and is programmed for quick arming, it cannot be
used to activate message playback or adjust the volume. In this case, you must use the master
keypad to perform these functions.
– 22 –
86(5ꢀ)81&7,216ꢀ
AUX FUNCTION
General Information
The AUX key may have been programmed to either perform a predefined function or to send a preset
message to a pager (see PAGER FEATURE section for pager operation). Ask your installer which function
has been assigned for your system.
AUX Key:
PRE-DEFINED FUNCTION
PAGING FUNCTION
If programmed for the AUX function, you can use the AUX key to activate a string of up to 20 keystrokes
that have been stored in the system’s memory. Typical functions include:
• Seldom used but repeatable sequences
• Arming sequences that involve bypassing zones before arming
• Device activation sequences
Defining the AUX Function
The system must be disarmed before defining a function.
1. Enter
+ FUNCTION + AUX (hold down at least 2 seconds until 4 beeps sound).
Master user code
2. Press the desired command sequence, up to 20 keystrokes. Press the AUX key between each command
in the sequence.
3. Press the AUX key twice to end the definition.
For example, to bypass Zones 10 and 11 and arm AWAY with NO DELAY, enter the following string:
+ FUNCTION + AUX
[6] + [10] + [11] + AUX + AWAY + [0] + AUX + AUX
+
Master user code
Note that the AUX key is included in the 20 keystroke maximum.
Performing the AUX function
Press and hold down the AUX key (hold down at least 2 seconds until 4 beeps sound), then enter
The defined function will begin.
Your user code
– 23 –
86(5ꢀ)81&7,216ꢀ
Clock/Calendar
Your system can display the current time (see your installer). The date is not displayed, but has an internal
function. The system must be disarmed with no faults present.
To set the time and date:
+ FUNCTION + [63]
Master user code or
Installer Code
NOTES: 1. The keypad beeps twice for invalid data entries (e.g., an hour greater than 12), and the entry will not be
accepted. The keypad beeps once for valid entries.
2. Clock-Setting mode automatically ends if no keys are pressed for one minute.
3. Daylight savings time may have been programmed to automatically begin and end.
4. It is not possible to enter the real time clock programming mode from a wireless keypad (i.e. Ademco 5827)
5. It is not possible to enter the real time clock programming mode when either FC or CA is displayed on the
display.
Hour
(The current hour will be displayed with the AM/PM indication.)
Enter the 2-digit hour (i.e., 01-12).
Press [*] to accept the entry and continue to the AM/PM selection.
Press [#] to exit Clock-Setting mode (keypad beeps 4 times).
AM/PM
(The current AM/PM setting will display A or P.)
Enter 1 for PM or 0 for AM.
Press [*] to accept the entry and continue to the minute selection.
Press [#] to return to hour-setting prompt.
Minute
(The current minute will display.)
Enter the 2-digit minute (i.e., 00-59).
Press [*] to accept the entry and continue to the month selection.
Press [#] to return to AM/PM setting.
Month
(The current month will display.)
Enter the 2-digit month designation (i.e., 01-12).
Press [*] to accept the entry and continue to the day selection.
Press [#] to return to the minute setting.
Day
(The current day of the month will display.)
Enter the 2-digit day of the month (i.e., 01-31).
Press [*] to accept the entry and continue to the year setting.
Press [#] to return to the month setting.
Year
(The current year will display.)
Enter the last two digits of the year (i.e., 00-99).
Press [*] to accept the entry and exit Clock-Setting mode (keypad beeps 4 times).
Press [#] to return to the day setting.
– 24 –
86(5ꢀ)81&7,216ꢀ
Scheduling User Interface
To access the Scheduling User Interface enter:
+ FUNCTION + [64]
Master user code or
Installer Code
The following entries will be sequentially prompted to the user. Note that all inputs are checked for validity
upon entry and all invalid entries are rejected. Hitting a [*] will allow the entries to be accepted and
advance to the next field. Hitting a [#] will reject the entry and back up one field. Hitting the [#] in the
“Schedule Number” screen will exit the schedule programming.
NOTES: 1. During the schedule programming, if three minutes passes and no key was entered, the programming
will be terminated and no values will be saved. Furthermore, if a zone is troubled while in schedule
programming, the system will abort the programming mode and show the troubled zone, and any
uncompleted program event will not be saved.
2. It is not possible to enter the schedule programming mode from a wireless keypad (i.e. Ademco 5827)
3. It is not possible to enter the schedule programming mode when either FC or CA is displayed on the
display.
Because the keypad display does not show prompt titles, you must refer to these instructions while
programming the system. The prompts are indicated by a number/letter combination.
The prompts for option #64 are as follows:
Schedule number-------------for selecting a schedule number (1-8)
Event identifier---------------for selecting a schedule action (0-5)
n
d
b
i
Begin time (hrs, am/pm)----for selecting a schedule begin time (hour, am/pm)
entry (00-12)
:
:
A
Begin time (min)-------------for selecting a schedule begin time (minute)
entry (00-59)
b
Begin day--------------------- for selecting a schedule begin day (01-17)
b
d
End time (hrs, am/pm)------ for selecting a schedule end time (hour, am/pm)
entry (00-12)
:
A
E
End time (min)--------------- for selecting a schedule end time (minute)
entry (00-59)
E
:
End day------------------------for selecting a schedule end day (01-17)
Device number--------------- for selecting a X-10 device number (1-8)
E
d
d
n
– 25 –
86(5ꢀ)81&7,216ꢀ
Scheduling User Interface
NOTE: The keypad beeps twice for invalid data entries (e.g.: an hour greater than 12), and the entry will
not be accepted. The keypad beeps once for valid entries and four times when a schedule event is
programmed successfully.
[x] = the value that was last stored in the memory.
Enter the 1-digit schedule number to be programmed, then press
[*] to accept and advance to the next programming field: Event
Identifier.
Schedule number
[x] = schedule number 1 to 8
ꢀx n
[*] = continue
• Press the [#] key in this entry will exit the schedule
programming mode. The keypad will beep four times and
exit.
[#] = exit schedule programming
mode
• Schedule number 7 and 8 are always random events that are
meant to work only with X-10 devices.
NOTE: This feature should be implemented when the user is
trying to give the impression that a premises is “lived
in”. The events will occur at random times (0-59
minutes) within the defined hour.
0 = Empty - no event scheduled (or schedule temporarily
disabled. Keypad will beep four times and return to Schedule
Number with the schedule number advanced.
1 = X-10 Device - the user is required to enter data up to and
include the Device Number screen. Selection #1 is a time
driven event that requires a begin and end time.
2 = Latch Key Report - the user is required to enter data up to
and include the End Day screen. Selection #2 is a window
driven event that requires a begin/end time.
Event Identifier
[x] = event identifier 0 to 5
[*] = continue
ꢀꢀx id
[#] = return to previous prompt
3 = Automatic Stay Arming - the user is required to enter data
up to and include the Begin Day screen. Selection #3 is a time
driven event that requires a begin time to send a report.
4 = Reminder Announcements - the user is required to enter
data up to and include the Begin Day screen. This is a reminder
announcement.
5 = Alarm Clock - the user is required to enter the field values
up to and include the Begin Day screen. This is a an alarm
clock.
NOTE: See figure 1 for an explanation of each entry of the
event identifier.
• The begin hour is a two-digit entry. To enter the hour 3,
Begin Time (hour)
[xx] = begin hour 00 to 12
[*] = continue
press “0” followed by “3”.
xx : ꢁb
• The begin hour “00” indicates this schedule does not have a
begin time.
[#] = return to previous prompt
• Press “0” to select AM or “1” to select PM.
NOTE: When programming schedule number 7 and 8, do not
program turn on/off to occur within the same 1-hour
period. This will prevent this random feature from
causing a reversal of the on/off times.
Begin Time (am/pm)
[0] = begin time, am (A)
[1] = begin time, pm (P)
[*] = continue
[#] = return to previous prompt
– 26 –
86(5ꢀ)81&7,216ꢀ
Scheduling User Interface
Begin Time (minute)
[xx] = begin minute 0 to 59
[*] = continue
ꢀb : xx
[#] = return to previous prompt
• If the value programmed in the Event Identifier is “3”, “4”,
or “5”, and the current entry is completed, the system will
save all field data up to this field. The system will beep four
times and go back to the first field (Schedule Number) with
the schedule number advanced.
Begin Day
[xx] = begin day 01 to 17
[*] = continue
xx : bd
[#] = return to previous prompt
• If the value programmed in the Event Identifier is “1” or
“2”, and the current entry is completed, the system will
advanced to the next programming field - End Time (hour).
NOTE: See figure 2 for the definition of begin day entries.
• The end hour is a two-digit entry. To enter the hour 3, press
End Time (hour)
“0” followed by “3”.
[xx] = begin hour 00 to 12
[*] = continue
xx : ꢁꢂ
• The end hour “00” indicates this schedule does not have a
end time.
[#] = return to previous prompt
• Press “0” to select AM or “1” to select PM.
End Time (am/pm)
[0] = end time, am (A)
[1] = end time, pm (P)
[*] = continue
[#] = return to previous prompt
End Time (minute)
[xx] = end minute 0 to 59
[*] = continue
ꢀꢀꢂ : xx
xx : ꢂd
ꢀx : dn
[#] = return to previous prompt
NOTE: See figure 2 for the definition of end day entries.
End Day
[xx] = end day 01 to 17
[*] = continue
• If the event identifier is set to “2” upon completion of this
field, the current schedule data will be saved and the system
will go back to the next schedule number.
[#] = return to previous prompt
[*] will accept and save the entire schedule event. The system
will beep four times and go back to the beginning of the
programming field (Schedule Number) with the schedule
number advanced. If the current schedule number is 8, the
system will wrap around and set the schedule number to 1.
NOTE: For X-10 devices.
Device Number
[xx] = device number 1 to 8
[*] = continue
[#] = return to previous prompt
– 27 –
86(5ꢀ)81&7,216ꢀ
Scheduling User Interface
Event Identifier Entries
Entry
Event
Comment
0
Empty
No event scheduled (or schedule is temporarily disabled)
1
2
X-10 Device
Turn an X-10 device, either on or off at begin/end times. (will
have a start and end time to program) (time driven)
SH10A siren cannot be used.
NOTE:
Latch Key Report
Send a special pager report (7110000) indicating system not
yet disarmed. (will have a start/end time to send the report)
(window driven), (reports only to pager)
Option *49 must be programmed to be 6 or higher.
Make sure unit is armed prior to start of window time.
In addition a secondary phone number must be
programmed in Option *42.
NOTE:
3
Automatic Stay Arming
Will arm the system automatically, and bypass any open
zones, at a given time. It will send a report to the pager and
central station, indicating system has been auto armed stay,
plus all bypass reports. (will have only a start time to send the
report) (time driven)
(1) Prior executing auto stay arming, force bypass
will be executed - if option *23 was enabled.
(2) If pager report is required, Option *49 must be
programmed to be 6 or higher.
NOTES:
4
5
Reminder Announcements
Alarm Clock
Will beep three times and then announce custom words 72,
73 and 74. This will be repeated every minute until a key is
†
depressed, or a button type zone does an arm or disarm.
Make sure installer programmed custom words 72-74
at the time of installation.
NOTE:
Will start a trouble tone (beep) on the speaker, which will
†
continue until a key is depressed.
†
The beeping sounds will be terminated when any key is pressed during a remote phone control session.
Figure 1.
– 28 –
86(5ꢀ)81&7,216ꢀ
Scheduling User Interface
Day of Week Entries
Entry
Day
00
Invalid day entry
01
02
03
04
05
06
07
08
Do event on next time match on the next Monday (will remove itself after executing)
Do event on next time match on the next Tuesday (will remove itself after executing)
Do event on next time match on the next Wednesday (will remove itself after executing)
Do event on next time match on the next Thursday (will remove itself after executing)
Do event on next time match on the next Friday (will remove itself after executing)
Do event on next time match on the next Saturday (will remove itself after executing)
Do event on next time match on the next Sunday (will remove itself after executing)
Do event on next time match every day (will run continuously, remains in schedule after
executing)
09
10
11
12
13
14
15
16
17
Do event on next time match every weekday (will run continuously, remains in schedule
after executing)
Do event on next time match every day of the weekend (will run continuously, remains in
schedule after executing)
Do event on next time match on the next Monday (will run continuously, remains in
schedule after executing)
Do event on next time match on the next Tuesday (will run continuously, remains in
schedule after executing)
Do event on next time match on the next Wednesday (will run continuously, remains in
schedule after executing)
Do event on next time match on the next Thursday (will run continuously, remains in
schedule after executing)
Do event on next time match on the next Friday (will run continuously, remains in
schedule after executing)
Do event on next time match on the next Saturday (will run continuously, remains in
schedule after executing)
Do event on next time match on the next Sunday (will run continuously, remains in
schedule after executing)
Figure 2.
– 29 –
86(5ꢀ)81&7,216ꢀ
Remote Phone Control Feature
The ReadyGuard-REN is equipped with a remote interactive phone capability that permits access to the
security system from any off-site touch-tone telephone using all user codes. If this feature has been
programmed, the system will provide the appropriate voice messages and any system beeping sounds
indicating the status of the security system over the phone line. (Refer to Summary of Audible Notification
for further information.) The following functions can be performed from any remote touch-tone telephone:
•
•
•
•
•
Disarm the system.
NOTE
Arm the system in STAY or AWAY mode.
Activate or deactivate X-10 devices.
Bypass zones.
(1) All voice announcements on the phone line will
also be announced on the local speaker, unless
the system has been placed in the mute mode.
(2) Entry/Exit beeps will be terminated if you enter
the remote phone access mode.
Check system status.
The remote access session will be aborted if:
•
•
•
A report must be sent.
Any local or wireless key entry (e.g. 5827), except [*], is made.
User Code is not entered within eight (8) seconds of call pickup (during the “system…..system
announcement).
•
No keys are depressed for a period of 15 seconds and while no announcement has been made by the
system. Any remote key entry will, however extend this timeout back to 15 seconds.
It will not be possible to begin a remote access session if:
•
•
•
•
•
•
•
A report must be sent
The system is in any Test mode.
During real time clock setting.
During scheduling setup.
Panel is in shutdown mode (programmed by your installer).
Panel is in Macro learning mode.
Remote phone control feature has not been enabled by your installer.
NOTE: If a remote phone session is not granted by the system, for any of the reasons identified above, a modem tone
will be generated before the end of the session.
Using Remote Phone Control Feature
Dial the controls’s phone number. If no answering machine is present, the control will pick up between 1
and 14 rings, depending on the number programmed by your installer and will periodically announce
“SYSTEM”. During a remote phone control session “PC” will be displayed on the control.
Enter:
(within eight seconds)
Your user code
The system status will be announced. Enter phone control commands as described on the next page:
If an answering machine is on the premises, you need to dial the premises and hang up on the first ring.
Wait at least five (5) seconds (but no more than 22 seconds) and dial the premises phone number again. The
control will pick up and periodically announce “SYSTEM”.
– 30 –
86(5ꢀ)81&7,216ꢀ
Remote Phone Control Feature
Enter:
(within eight seconds)
Your user code
The system status will be announced.
Remote Phone Control Commands
To remotely disarm system:
+ [1]
Your user code
To remotely arm in AWAY mode:
To remotely arm in STAY mode:
+ [2]
Your user code
+ [3]
Your user code
To remotely arm in AWAY or STAY mode with no delay:
+ [2] or [3] + [0]
Your user code
To remotely activate X-10 devices 1-6: [#] + [4] + device no.
To remotely activate X-10 devices 7 & 8:
+ [#] + [4] + device no.
Your user code
To remotely deactivate X-10 devices 1-6: [#] + [7] + device no.
To remotely deactivate X-10 devices 7 & 8:
+ [#] + [7] + device no.
Your user code
To remotely Bypass zones:
+ [6] + zone no.
Your user code
To remotely activate Forced Bypass:
+ [6] + [#]
Your user code
To remotely check system status: [*]
To end remote phone session: Hang Up or
+ [9]
Your user code
NOTES: (1) Check with your installer to see if the Forced Bypass mode has been enabled.
(2) When bypassing zones, make sure a confirmation beep sounds for each zone that has been bypassed.
– 31 –
86(5ꢀ)81&7,216ꢀ
Speaker Phone Feature
If this feature has been programmed the ReadyGuard-REN is capable of operating as a speaker phone.
During speaker phone operation the system will provide the following functions:
•
•
•
All function/event processing will continue to operate, but there will be no announcements.
The ARMED (red) and READY (green) LEDs will alternately blink.
“PH” will be displayed.
NOTE: The system will enter the Speaker phone mode if an alarm or trouble is stored in the system memory. Although “PH” may
not appear, the LEDs will alternately blink indicating you are currently in the Speaker Phone mode.
Do not use the speaker phone as the only telephone in your home since in some special cases the
speaker phone is not functional.
!
The system will not enter speaker phone mode if:
•
•
•
•
•
•
The feature has not been programmed.
A report is being sent.
An audible alarm is present.
An announcement is being made or a recorded message is being played back.
A message is being recorded.
AC power is not present
The speaker phone will be aborted if:
•
•
•
A report must be sent.
An audible alarm or trouble has ocurred.
AC power is lost.
Using the Speaker Phone Feature
When the ReadyGuard-REN is operating in the speaker phone mode the system keypad functions as a
telephone keypad and the only security keypad functions that will remain enabled are the panic keys and the
speaker volume control. (refer to Volume Adjustment section) You may adjust the volume before entering
speaker phone mode or after dialing the desired number. In the speaker phone mode, if a zone is violated
and has triggered an entry/exit delay, the system will automatically change the keypad from telephone to
security mode. This allows the user to disarm the system or take other appropriate actions in the security
mode without interrupting the telephone session. To regain telephone keypad control (i.e.: to enter an
account number or menu selection) you will need to reactivate the telephone keypad as described below.
ReadyGuard-REN Speaker Phone Functions
NOTE
To place a call using the Speaker Phone: [#] + AUX and dial the desired phone number
To answer a call using the Speaker Phone: [#] + AUX
If you are using pulse
(rotary) dialing, make
sure that ReadyGuard-
To flash (switch between two calls using call waiting): AUX
To hang up: OFF
REN
has
finished
dialing the last digit you
dialed, (listen to pulses)
before dialing the next
To activate/deactivate (toggle) ringer: [#] + VOLUME + AUX
To return the keypad to telephone mode after disarming the system: [#] + AUX
NOTES: (1) The speaker phone ringer can only be enabled/disabled when the speaker phone mode is not active. The system will
ring once to confirm the ringer is enabled. Entering [#] + VOLUME + AUX a second time will disable the ringer. No
ring will confirm that the ringer is disabled.
(2) The speaker phone ringer will not ring when an alarm, trouble or entry/exit delay are sounding.
(3) The ReadyGuard-REN speaker phone does not provide a “hold” feature
– 32 –
(If Installed)
),5(ꢁ$/$50ꢁ6<67(0ꢁ
General Information
ReadyGuard-REN is not intended for UL985 Household Fire applications unless a 24-hour
backup battery (P/N LYNXRCHKIT-HC) is installed.
8
/ꢀ
General
Your fire alarm system (if installed) is active 24 hours a day, providing continuous protection. In the event
of an emergency, the installed smoke and heat detectors will automatically activate your security system,
triggering a loud, intermittent sound from the keypad. An intermittent sound will also be produced by
optional exterior sounders, and interlaced with the voice descriptor, sounding every 15 seconds. A “FIRE”
message will appear at your keypad and remain on until you silence and clear the alarm display.
In Case of Fire
1. Should you become aware of a fire emergency
before
your detectors sense the problem, go to your
nearest keypad and press the single panic key (or panic key pair) assigned as FIRE emergency (if
programmed by the installer) and hold down for at least 2 seconds. The alarm will sound.
2. Evacuate all occupants from the premises.
3. If flames and/or smoke are present, leave the premises and notify your local Fire Department
immediately.
4. If no flames or smoke are apparent, investigate the cause of the alarm. The zone number of the zone(s)
in an alarm condition will appear at the keypad.
Silencing a Fire Alarm
OFF
key.
1. Silence the alarm by entering
+
Your user code
To clear the alarm display, enter
OFF
+
key again.
Your user code
2. If the keypad indicates a trouble condition after the second OFF sequence, check that smoke detectors
are not responding to smoke- or heat-producing objects in their vicinity. Should this be the case,
eliminate the source of heat or smoke.
3. If this does not remedy the problem, there may still be smoke in the detector. Clear it by fanning the
detector for about 30 seconds.
OFF
key.
4. When the problem has been corrected, clear the display by entering
+
Your user code
– 33 –
),5(ꢁ$/$50ꢁ6<67(0ꢁꢁ
National Fire Protection Association’s
Smoke Detector Recommendations
ReadyGuard-REN is not intended for UL985 Household Fire applications unless a 24-hour
backup battery (P/N LYNXRCHKIT-HC) is installed.
8
/ꢀ
With regard to the number and placement of smoke and heat detectors, we subscribe to the
recommendations contained in the National Fire Protection Association's (NFPA) Standard #74 noted
below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and
areas of the household. The equipment should be installed as follows: A smoke detector installed outside of
each separate sleeping area, in the immediate vicinity of the bedrooms and on each additional story of the
family living unit, including basements and excluding crawl spaces and unfinished attics.
In addition, the NFPA recommends that you install heat or smoke detectors in the living room, dining room,
bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached
garages.
KITCHEN
DINING
KITCHEN
BEDROOM
BEDROOM
BEDROOM
BEDROOM
TV ROOM
DINING
LIVING ROOM
BEDROOM
LIVING ROOM
BEDROOM
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
BEDROOM
BEDROOM
BEDROOM
KTCHN
LIVING
ROOM
GARAGE
CLOSED
DOOR
.
TO
BEDROOM
BASEMENT
01000-002-V0
– 34 –
),5(ꢁ$/$50ꢁ6<67(0ꢁꢁ
Emergency Evacuation
ReadyGuard-REN is not intended for UL985 Household Fire applications unless a 24-hour
backup battery (P/N LYNXRCHKIT-HC) is installed.
8
/ꢀ
Establish and regularly practice a plan of escape in the event of fire. The following steps are recommended
by the National Fire Protection Association:
1. Position your detector or your interior and/or exterior sounders so
that they can be heard by all occupants.
2. Determine two means of escape from each room. One path of
escape should lead to the door that permits normal exit from the
OOM
CLOSET
BEDR
building. The other should be an alternative escape, such as a
window, should your path to that door be unpassable. Station an
escape ladder at such windows if there is a long drop to the
ground.
H
OOM
BEDR
OOM
BEDR
T
BA
2nd FLOOR
3. Sketch a floor plan of the building. Show windows, doors, stairs
and rooftops that can be used to escape. Indicate escape routes for
each room. Keep these routes free from obstruction and post
copies of the escape routes in every room.
OOM
BEDR
KITCHEN
BACK DOOR
H
OOM
BEDR
T
BA
4. Assure that all bedroom doors are shut while you are asleep. This
will prevent deadly smoke from entering while you escape.
1st FLOOR
5. Try the door. If the door is hot, check your alternate escape route.
If the door is cool, open it cautiously. Be prepared to slam the
door if smoke or heat rushes in.
6. When smoke is present, crawl on the ground. Do not walk
upright, since smoke rises and may overcome you. Clearer air is
near the floor.
BACK
7. Escape quickly; don't panic.
8. Establish a place outdoors, away from your house, where
everyone can meet and then take steps to contact the authorities
and account for those missing. Choose someone to assure that
nobody returns to the house — many die going back.
FRONT
01000-023-V0
– 35 –
6<67(0ꢁ)81&7,216ꢁ
Security Codes
General Information
For additional security you (the Master User Code) can assign secondary user codes to individual users
enabling them to perform specific system functions. These secondary users are identified by "user numbers"
when their codes are assigned. You can assign up to 6 user codes (2-digit user numbers 03-08). Note that
the master user is the only one who can assign codes to secondary users, and is designated user no. 02; user
no. 01 is the Installer’s code.
All codes can be used interchangeably when performing system functions (a system armed with one user's
code can be disarmed by another user's code), with the exception of the Babysitter Code described below.
Babysitter Code (User 07): This code can be used to arm the system, but cannot disarm the system unless
the system was armed with this code. This code is typically assigned to someone (such as a babysitter) who
needs to arm/disarm the system only at certain times. The Babysitter Code is assigned to User 07.
Duress Code (User 08): This feature is intended for use when you are forced to disarm or arm the system
under threat. When used, the system will act normally, but can silently notify the alarm monitoring company
of your situation, if that service has been provided. Duress Code is assigned to User 08.
The Duress Code is useful only when the system is connected to an alarm monitoring company.
To Add/Delete a User or Change a User's Code
Changing the Master User Code
Follow the procedure for changing a user's code, but enter User No. 02 and enter the new code twice.
IMPORTANT: Temporary users of the system (e.g., babysitters, cleaning staff) should not be shown how to use any
system function they do not need to know, such as bypassing protection zones for example.
Sequential key depressions for all steps in a procedure must be made within 2 seconds of one another, or
else the entire entry is aborted and must be repeated from its beginning.
Add a user code:
+ CODE Key + user number (03-08) + user’s code
Master user code
Delete a user code:
+ CODE Key + user number (03-08)
Master user code
Wait (about 3 seconds) until the keypad beeps once before pressing any other key. The code is
automatically deleted.
– 36 –
6<67(0ꢁ)81&7,216ꢁ
Testing the System (to be conducted weekly)
Entering Test Mode
The TEST key puts your system into the Test mode, which allows each protection point to be checked for
proper operation. The keypad sounds a single beep every 45 seconds as a reminder that the system is in the
Test mode.
NOTE: An alarm message will not be sent to your alarm monitoring company during the following tests.
Disarm the system and close all protected windows, doors, etc. The “READY” indicator should be lit.
Enter:
+ TEST key
Your user code
WATCH. All LCD segments will light for 3 seconds.
LISTEN. The external sounder should sound for 2 seconds and then turn off. If the sounder does not sound,
notify your service company.
FAULT ZONES. Open each protected door and window in turn and listen for three beeps from the keypad,
followed by the zone’s Voice Descriptor, if it is programmed. Identification of each faulted protection point
should appear on the display. The display will clear when the door or window is closed.
Walk in front of any interior motion detectors (if used) and listen for three beeps and/or voice descriptors, if
programmed. The identification of the detector should appear on the display when it is activated, and its
voice descriptor will be announced (if programmed). The display will clear when no motion is detected.
Note that if wireless motion detectors are used, there is a 3-minute delay between activations. This is to
conserve battery life.
To test all smoke detectors, follow the manufacturer's instructions. The identification of each detector
should appear on the display when each is activated.
If a problem is experienced with any protection point (no confirming sounds, no display), notify your
service company.
When all protection points have been checked and are intact (closed), there should be no zone identification
numbers displayed on the keypad.
Exit Test Mode
When testing is completed, exit the TEST mode by entering:
+ OFF key.
Your user code
NOTES: (1) If the Test mode is inadvertently left active, it automatically turns off after 4 hours.
(2) Macros cannot be run from the Test mode.
– 37 –
6<67(0ꢁ)81&7,216ꢁ
Trouble Messages
Typical Trouble Condition Displays
To silence the beeping sound for fault conditions, press any key.
FAULT
Indicates that a problem exists with the zone(s) displayed, accompanied by rapid beeping.
First, determine if the zone(s) displayed are intact and make them so if they are not. If the
zone uses a wireless detector, check that changes in the room (moving furniture, televisions,
etc.) are not blocking wireless signals from the detector. If the problem has been corrected,
the zone descriptor(s) and FAULT should disappear from the display. If not, key an OFF
sequence (security code plus OFF) to clear the display. A fault condition can also indicate a
wiring problem. If the “FAULT” display persists, notify your service company. Note that the
system will not allow arming if a fault condition exists. To arm the system with a fault
condition present, you must first bypass the zone(s) having the fault condition.
FC
CC
Indicates that a failure has occurred in the telephone communication portion of your system
or a problem with the phone line existed when dialing was attempted.
Indicates that the control is on-line with the central station's remote computer. The control
will not operate while on-line. Wait a few minutes. The display should disappear.
†
†
dI
If this remains displayed for more than 1 minute, the system is disabled.
CA
EA
90
Indicates a cancelled alarm. See Entry/Exit Delay section
Indicates an exit alarm. See Entry/Exit Delay section.
Indicates that the system has detected an RF jam condition or excessive interference. If the
condition persists, notify your service company.
LOW BAT
Accompanied by a once-per 45 seconds beeping at the keypad, indicates a low system
(no zone no.) battery condition exists. Refer to the Changing the ReadyGuard-REN System Battery section.
†
LOW BAT
Accompanied by a once-per-45 seconds beeping at the keypad, indicates a low battery
(with zone no.) condition exists in the wireless transmitter displayed.
†
LOW BAT
Accompanied by a once-per-45 seconds beeping at the keypad, indicates a low battery
(with zone 00) condition exists in a wireless keypad.
†
† Notify your service company.
Routine Care
•
•
•
Treat the components of your security system as you would any other electrical equipment. Do not slam
sensor-protected doors or windows.
Keep dust from accumulating on the keypad and all protective sensors, particularly on motion sensors
and smoke detectors.
The keypad and sensors should be cleaned carefully with a dry soft cloth. Do not spray water or any
other fluid on the units.
– 38 –
6<67(0ꢁ)81&7,216ꢁ
Maintaining your system
The components of your security system are designed to be as maintenance-free as possible. To make sure
that your system is in working condition, do the following:
1. Test your system weekly.
2. Test your system after any alarm occurs (see the TESTING THE SYSTEM section).
Low Battery Conditions in Wireless Sensors
Each wireless sensor in your system has a 9-volt or 3-volt battery. The system detects low battery conditions
in wireless sensors, including smoke detectors, personal emergency transmitter, and the portable wireless
keypad, and displays a “LOW BAT” message on the master keypad, which also beeps. A low battery in a
wireless keypad is detected as soon as one of its keys is pressed, and the master keypad (e.g. Ademco 5827)
will display “00”. In addition, a wireless smoke detector with a low battery also emits a "chirp" sound
approximately once every 20–30 seconds, identifying itself as the smoke detector with the weak battery.
NOTE: A low battery message means that battery replacement in the indicated sensor(s) is due within 30
days. In the meantime, a sensor with a low battery is still operational.
To silence Low Battery Warning Tones at the Keypad: Press the OFF key.
The low battery message display will remain on as a reminder. When you replace the weak battery with a
fresh one, the sensor will send a "good battery" signal to the control when the sensor is activated
(opening/closing of door, window, etc.).
To clear the “LOW BAT” message enter:
+ OFF key.
Your user code
When replacing batteries, use only those recommended by your installer.
Alkaline batteries provide a minimum of 1 year of operation, and in most units and applications, provide 2–4 years of service. 3-volt
lithium batteries may provide from 4-7 years of operation. Actual battery life will depend on the environment in which the sensor is
used, the number of signals that the transmitter in the sensor has had to send, and the specific type of sensor. Factors such as
humidity, high or low temperatures, and large swings in temperature may all lead to the reduction of actual battery life in an
installation.
Changing the ReadyGuard-REN System Battery
In the event of an AC power loss, the ReadyGuard-REN is powered by a rechargeable, nickel-metal hydride
battery pack. The battery pack should be replaced when a “LOW BAT” message with no zone number is
displayed.
NOTE: The battery pack (P/N LYNXRCHKIT-SC or LYNXRCHKIT-HC) should be changed every
four years and must be replaced by a qualified service technician.
Following battery pack replacement, rechargeable batteries may take up to 48 hours to charge. The “LOW
BAT” message may be displayed after one minute, however it should clear within 4 hours or by entering
Test Mode.
– 39 –
6XPPDU\ꢁ2Iꢁ$XGLEOHꢁ1RWLIL$DWLRQꢁ
*UPPER CASE indicates announcements after pressing STATUS once. Lower case indicates announcements after pressing STATUS twice.
SOUND
CAUSE
FIRE ALARM
DISPLAY
FIRE ALARM is displayed; zone number in
alarm displayed.
ANNOUNCEMENT*
fire alarm + zone voice descriptor
(Voice descriptor is interlaced
with the siren and sounds every
45 seconds)
INTERRUPTED
Speaker and external
piezo and bell
CONTINUOUS
Speaker and external
piezo and bell
BURGLARY/AUDIBLE
EMERGENCY ALARM
ALARM is displayed; zone number in
alarm displayed.
alarm + zone voice descriptor
(Voice descriptor is interlaced
with the siren and sounds every
45 seconds)
ONE SHORT BEEP
(not repeated)
Speaker and external
piezo
a. SYSTEM DISARM
b. SYSTEM ARMING
ATTEMPT WITH AN OPEN
ZONE.
a. Green LED on steady
b. The number of the open protection zone
is displayed after pressing STATUS.
a. DISARMED–READY TO ARM
b. DISARMED–NOT READY TO
ARM
c. BYPASS VERIFY
c. Numbers of the bypassed protection
zones are displayed (One beep is heard
for each zone displayed).
c. zones bypassed
ONE SHORT BEEP
(once every 45 secs)
Speaker and external
piezo
a. SYSTEM IS IN TEST MODE a. Opened zone identifications will appear.
a. No announcement
b. low battery + zone voice
descriptor
c. system low battery
d. check system
b. LOW BATTERY AT A
TRANSMITTER
b. LOW BAT displayed with zone number
of transmitter.
c. SYSTEM LOW BATTERY
d. FAIL TO COMMUNICATE
ARM AWAY OR MAXIMUM
c. LOW BAT displayed with no zone no.
d. FC displayed with no zone no.
AWAY or AWAY + INSTANT is displayed.
Red ARMED indicator is lit.
TWO SHORT BEEPS
Speaker and ext. piezo
THREE SHORT
BEEPS
ARMED AWAY [INSTANT] –
EXIT NOW
a. ARM STAY OR INSTANT
a. STAY or STAY + INSTANT is displayed.
Red ARMED indicator is lit.
a. ARMED STAY [INSTANT] –
EXIT NOW
Speaker and external
piezo
b. ZONE OPENED WHILE
SYSTEM IS IN CHIME
MODE.
b. CHIME displayed, number of open
protection zone will be displayed if the
Status key is pressed.
b. zone voice descriptor
RAPID BEEPING
Speaker and external
piezo
a. TROUBLE
a. FAULT displayed. Number of troubled
protection zone is displayed.
b. FIRE ALARM or ALARM is displayed;
zone number in alarm is displayed.
a. Exceeding the delay time without
disarming causes alarm.
a. fault + zone voice descriptor
b. MEMORY OF ALARM
a. ENTRY DELAY WARNING
b. EXIT DELAY WARNING
b. fire alarm or alarm + zone
voice descriptor
SLOW BEEPING
Speaker and external
piezo
a. DISARM SYSTEM NOW
b. AWAY or AWAY + INSTANT is
displayed
b. ARMED [AWAY] [INSTANT] –
EXIT NOW
Additional Announcements:
Pressing STATUS key once will announce the following primary messages, depending on the system’s status at the time:
Disarmed–Ready to Arm [check system]
Disarmed [not ready to arm]
Armed [away] [stay] [instant] [check system] [exit now]
Pressing the STATUS key twice will announce the following secondary messages, depending on the system’s status at the time:
Fire Alarm + zone voice descriptor
Alarm + zone voice descriptor
Fire Fault + zone voice descriptor
Fault + zone voice descriptor
Low Battery + zone voice descriptor
Chime
Zones Bypassed
System Low Battery
AC Loss
NOTE: If there are no secondary messages, the primary status messages will be announced.
LED Meanings
ARMED LED: ON = System armed
READY LED: ON = System disarmed, ready to arm
(Red)
OFF = System disarmed
(Green)
Blinking = System disarmed, not ready to arm
(a fault exists) or once per second when AVM
(VOX or Talk) or speaker phone mode is
active.
Blinking = System armed, but a fault exists or
once per second when AVM (VOX or Talk) or
speaker phone mode is active.
NOTE: When the system is armed, the READY LED turns off.
– 40 –
UL NOTICE: This is a "Grade A" residential system.
FCC ID: CFS8DLLYNX
RADIO FREQUENCY EMISSIONS
Federal Communications Commission (FCC) Part 15
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) this device must accept any interference received, including interference that may cause
undesired operation.
Industry Canada
This Class B digital apparatus complies with Canadian ICES-003.
Cet Appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
TELEPHONE/MODEM INTERFACE
Federal Communications Commission (FCC) Part 68
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains the FCC
registration number and Ringer Equivalence Number (REN). You must provide this information to the telephone company when
requested.
This equipment uses the following USOC jack: RJ31X
This equipment may not be used on telephone-company-provided coin service. Connection to party lines is subject to state
tariffs. This equipment is hearing-aid compatible.
Industry Canada
NOTICE: The Industry Canada Label identifies certified equipment. This certification means that the equipment meets
telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment
Technical Requirements document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local
telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer
should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations
made by the user to this equipment, or equipment malfunctions, may give the telecommunications company to request the user to
disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and
internal metallic water pipe system, if present, are connected together, This precaution may be particularly important in rural
areas.
Caution: Users should not attempt to make such connections themselves but should contact appropriate electric inspection
authority, or electrician, as appropriate.
Ringer Equivalence Number Notice:
The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of
terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of
devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.
IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMS
In the event of telephone operational problems, disconnect the control by removing the plug from the RJ31X (CA38A in Canada)
telephone wall jack. We recommend that your certified installer demonstrate disconnecting the phones on installation of the system.
Do not disconnect the phone connection inside the control/communicator. Doing so will result in the loss of your phone lines. If the
regular phone works correctly after the control/communicator has been disconnected from the phone lines, the control/communicator
has a problem and should be returned for repair. If upon disconnection of the control/communicator, there is still a problem on the
line, notify the telephone company that they have a problem and request prompt repair service. The user may not under any
circumstances (in or out of warranty) attempt any service or repairs to the system. It must be returned to the factory or an authorized
service agency for all repairs.
– 41 –
OWNER'S INSURANCE PREMIUM CREDIT REQUEST
This form should be completed and forwarded to your homeowner's insurance carrier for possible premium credit.
A. GENERAL INFORMATION:
Insured's Name and Address:
Insurance Company:
Policy No.:
First Alert Professional's ReadyGuard-REN _________________________
Other
Type of Alarm:
Installed by:
Burglary
Fire
Both
Serviced by:
Name
Name
Address
Address
B. NOTIFIES (Insert B = Burglary, F = Fire)
Local Sounding Device
Police Dept.
Fire Dept.
Central Station
Name:_______________________________________________________________________
Address:
Phone:
C. POWERED BY: A.C. With Rechargeable Power Supply
D. TESTING:
Quarterly Monthly
Weekly
Other
continued on other side
– 42 –
OWNER'S INSURANCE PREMIUM CREDIT REQUEST (cont.)
E. SMOKE DETECTOR LOCATIONS
Furnace Room
Kitchen
Bedrooms
Attic
Hall
Basement
Living Room
Dining Room
F. BURGLARY DETECTING DEVICE LOCATIONS:
Front Door
Basement Door
Rear Door
All Exterior Doors
1st Floor Windows
All Windows
Interior Locations
All Accessible Openings, Including Skylights, Air Conditioners and Vents
G. ADDITIONAL PERTINENT INFORMATION:
Signature:
Date:
– 43 –
,1'(;
A
E
AC...................................................................12
Adjusting the Volume.....................................22
Alarm..........................................................5, 12
Alarm Monitoring Company...........................19
Armed Indicator..............................................11
Audible Emergency/Audible Alarm................19
AUX Function ........................................3, 7, 23
AWAY............................................................12
Away Mode ......................................5, 7, 14, 15
EA.............................................................16, 38
Emergency Evacuation ...................................35
End Day ..........................................................27
End Time ........................................................27
Entry Delay.................................................5, 16
Event Entries...................................................28
Event Identifier ...............................................26
Exit Alarms.....................................................16
Exit Delay.......................................................16
B
F
Babysitter Code ..............................................36
Battery ............................................................38
Begin Day.......................................................27
Begin Time ...............................................26, 27
Burglary Protection...........................................5
BYPASS.........................................................11
Bypass a Zone...................................................7
Bypassing Protection Zones............................18
FAULT .....................................................12, 37
FC ...................................................................38
FCC.................................................................41
Features.........................................................3, 4
FIRE................................................................10
Fire Alarm.......................................................33
Fire Protection ..................................................5
Forced Bypass...................................................18
C
H
CA.............................................................16, 38
CC...................................................................38
Central Monitoring Station...............................6
CHIME ...........................................................12
Chime Mode .......................................5, 7, 8, 19
Clock/Calendar ...............................................24
Hardwire .........................................................26
I
INSTANT .......................................................12
Internal Sounder..............................................11
L
Low Bat ..............................................12, 38, 39
D
Day Of Week Entries......................................29
Daylight Savings Time ...................................24
Device Activation.............................................3
Device Descriptions........................................21
Device Number...............................................27
dI ...................................................................38
Disarm ........................................................7, 17
Display Definitions.........................................12
Displaying Bypassed Zones............................18
Duress Code....................................................36
– 44 –
M
S
Manual Paging................................................20
Master Code....................................................36
Master Keypad........................................3, 8, 10
Master User ................................................5, 36
Master User Code...........................................36
Memory of Alarm...........................................17
Message ..........................................................12
Message Center.............................................3, 7
Message Playback...........................................22
Schedule Number............................................26
Scheduling ......................................................26
Security Codes........................................4, 5, 36
Security Functions ............................................7
Servicing Information .....................................47
Silence Alarm ............................................17 32
Silencing Low Battery Warning Tones...........39
Silent Emergency/Silent Alarm.......................19
Smoke Detectors...............................................5
Speaker ...........................................................11
Speaker Phone Feature....................................32
Status ........................................................11, 40
STAY..............................................................12
Stay Mode..........................................5, 7, 14 15
Stop Recording .................................................7
Supervised Fire Alarm....................................19
System Battery................................................39
Microphone
.....................................................11
N
No Delay.....................................................7, 15
P
Pager.....................................................7, 20, 23
Pager Feature..................................................23
Paging Feature ............................................3, 20
Panic Key....................................................3, 19
Personal Emergency/Aux. Emergency............19
Phone Control...................................................4
Play Back a Message ........................................7
Powerline Carrier Device Commands.............21
T
TEST...............................................................12
Test Mode...................................................7, 37
Time And Date............................................7, 24
Trouble Messages ...........................................38
Two-Way Voice............................................3, 6
Q
U
Quick Arm........................................................7
Quick Arming ...........................................14, 15
User Code ...................................................5, 36
Using Powerline Carrier Device Commands ....3
R
V
Ready Indicator..........................................12 17
Ready LED ................................................13 18
Real-Time Clock...............................................3
REC ................................................................12
Rechargeable, Nickel-Metal Hydride Battery
Pack ...........................................................39
Voice Announcement........................................3
Voice Dialog.....................................................6
...........................................................11
Volume Adjustment..........................................7
Volume Level .................................................13
Volume
Record
...................................................7, 12 22
W
Remote Phone Control Feature.......................30
Restart Exit Delay.......................................7, 14
RF Jam Condition...........................................38
Wireless Keypads .............................................3
Wireless Sensors.............................................39
Z
Zone Number..................................................26
Zones ................................................................5
– 45 –
WARNING!
THE LIMITATIONS OF THIS ALARM SYSTEM
While this system is an advanced design security system, it does not offer guaranteed protection against burglary or fire or other
emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of
reasons. For example:
•
Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or
disconnect an alarm warning device.
•
Intrusion detectors (e.g. passive infrared detectors), smoke detectors, and many other sensing devices will not work without
power. Battery operated devices will not work without batteries, with dead batteries, or if the batteries are not put in properly.
Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly.
•
Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the
signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path.
•
•
A user may not be able to reach a panic or emergency button quickly enough.
While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not activate or
provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by the Federal
Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System may not work are
as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not sense fires that start
where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level of a residence or building. A second floor detector, for example, may not
sense a first floor or basement fire. Moreover, smoke detectors have sensing limitations. No smoke detector can sense every kind
of fire every time. In general, detectors may not always warn about fires caused by carelessness and safety hazards like smoking
in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children
playing with matches, or arson. Depending upon the nature of the fire and/or the locations of the smoke detectors, the detector,
even if it operates as anticipated, may not provide sufficient warning to allow all occupants to escape in time to prevent injury or
death.
•
•
Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation
manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection, and
intrusion can only be detected in unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes
place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows. Mechanical tampering, masking,
painting or spraying of any material on the mirrors, windows or any part of the optical system can reduce their detection ability.
Passive Infrared Detectors sense changes in temperature; however, as the ambient temperature of protected area approaches the
temperature range of 90° to 105°F, the detection performance can decrease.
Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other
side of closed or partly open doors. If warning devices sound on a different level of the residence from the bedrooms, then they
are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not hear the warning if the alarm
is muffled from a stereo, radio, air conditioner or other appliance, or by passing traffic. Finally, alarm warning devices, however
loud, may not warn hearing-impaired people or waken deep sleepers.
•
•
•
Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or
temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.
Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect themselves
from the emergency situation. In the case of a monitored alarm system, authorities may not respond appropriately.
This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to last as
long as 10 years, the electronic components could fail at any time.
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This
alarm system should be tested weekly to make sure all sensors and transmitters are working properly.
Installing an alarm system may make one eligible for lower insurance rates, but an alarm system is not a substitute for insurance.
Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to insure their
lives and property.
We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones to
learn about these developments.
– 46 –
SERVICING INFORMATION
Your local First Alert Professional dealer is the person best qualified to service your
alarm system. Arranging some kind of regular service program with him is advisable.
Your local First Alert Professional dealer is:
Name:
Address:
Phone:
– 47 –
ONE YEAR LIMITED WARRANTY
Pittway Corporation, and its divisions, subsidiaries and affiliates ("Seller"), 165 Eileen Way, Syosset, New
York 11791, warrants its security equipment (the "product") to be free from defects in materials and
workmanship for one year from date of original purchase, under normal use and service. Seller's obligation is
limited to repairing or replacing, at its option, free of charge for parts, labor, or transportation, any product
proven to be defective in materials or workmanship under normal use and service. Seller shall have no
obligation under this warranty or otherwise if the product is altered or improperly repaired or serviced by
anyone other than the Seller. In case of defect, contact the security professional who installed and maintains
your security equipment or the Seller for product repair.
This one year Limited Warranty is in lieu of all other express warranties, obligations or liabilities. THERE
ARE NO EXPRESS WARRANTIES, WHICH EXTEND BEYOND THE FACE HEREOF. ANY IMPLIED
WARRANTIES, OBLIGATIONS OR LIABILITIES MADE BY SELLER IN CONNECTION WITH THIS
PRODUCT, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY, OR FITNESS FOR A
PARTICULAR PURPOSE OR OTHERWISE, ARE LIMITED IN DURATION TO A PERIOD OF ONE
YEAR FROM THE DATE OF ORIGINAL PURCHASE. ANY ACTION FOR BREACH OF ANY
WARRANTY, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF
MERCHANTABILITY, MUST BE BROUGHT WITHIN 12 MONTHS FROM DATE OF ORIGINAL
PURCHASE. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL
OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR
IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER, EVEN IF THE LOSS OR
DAMAGE IS CAUSED BY THE SELLER'S OWN NEGLIGENCE OR FAULT. Some states do not allow
limitation on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential
damages, so the above limitation or exclusion may not apply to you.
Seller does not represent that the product may not be compromised or circumvented; that the product will
prevent any personal injury or property loss by burglary, robbery, fire or otherwise; or that the product will in
all cases provide adequate warning or protection. Buyer understands that a properly installed and maintained
alarm may only reduce the risk of a burglary, robbery, fire or other events occurring without providing an
alarm, but it is not insurance or a guarantee that such will not occur or that there will be no personal injury or
property loss as a result. CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY
PERSONAL INJURY, PROPERTY DAMAGE OR OTHER LOSS BASED ON A CLAIM THE PRODUCT
FAILED TO GIVE WARNING. HOWEVER, IF SELLER IS HELD LIABLE, WHETHER DIRECTLY OR
INDIRECTLY, FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED WARRANTY OR
OTHERWISE, REGARDLESS OF CAUSE OR ORIGIN, SELLER'S MAXIMUM LIABILITY SHALL
NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT, WHICH SHALL BE THE
COMPLETE AND EXCLUSIVE REMEDY AGAINST SELLER. This warranty gives you specific legal
rights, and you may also have other rights which vary from state to state. No increase or alteration, written or
verbal, to this warranty is authorized.
175 Eileen Way, Syosset, New York 11791
Copyright © 2001 PITTWAY CORPORATION
i.ꢀꢁꢂꢃꢄꢅ!lꢆ
K5964-1 9/01
|