HP Hewlett Packard Heat Pump H4H3 User Manual

INSTALLATION INSTRUCTIONS  
3-Phase R-410A Split System Heat Pump  
Product Family: H4H3  
These instructions must be read and understood completely before attempting installation.  
Safety Labeling and Signal Words  
DANGER, WARNING, CAUTION, and  
NOTE  
Signal Words in Manuals  
The signal word WARNING is used throughout this  
The signal words DANGER, WARNING,  
manual in the following manner:  
CAUTION, and NOTE are used to identify levels of  
hazard seriousness. The signal word DANGER is  
only used on product labels to signify an immediate  
hazard. The signal words WARNING, CAUTION,  
and NOTE will be used on product labels and  
throughout this manual and other manuals that may  
apply to the product.  
WARNING  
!
The signal word CAUTION is used throughout this  
manual in the following manner:  
!
CAUTION  
DANGER - Immediate hazards which will result in  
severe personal injury or death.  
Signal Words on Product Labeling  
WARNING - Hazards or unsafe practices which  
could result in severe personal injury or death.  
Signal words are used in combination with colors  
and/or pictures on product labels.  
CAUTION - Hazards or unsafe practices which  
may result in minor personal injury or product or  
property damage.  
NOTE - Used to highlight suggestions which will  
result in enhanced installation, reliability, or  
operation.  
TABLE OF CONTENTS  
Inspect New Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 3  
Unit Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4  
Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . 5 - 8  
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 10  
Defrost System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
Start-up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . 12 - 13  
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
Comfort Alertt Diagnostics Codes . . . . . . . . . . 15 - 16  
R-410A Quick Reference Guide . . . . . . . . . . . . . . . . . 16  
!
WARNING  
DEATH, PERSONAL INJURY, AND/OR PROPERTY  
DAMAGE HAZARD  
Failure to carefully read and follow this warning  
could result in equipment malfunction, property  
damage, personal injury and/or death.  
Installation or repairs made by unqualified per‐  
sons could result in equipment malfunction, prop‐  
erty damage, personal injury and/or death.  
The information contained in this manual is in‐  
tended for use by a qualified service technician fa‐  
miliar with safety procedures and equipped with  
the proper tools and test instruments.  
Installation must conform with local building  
codes and with the National Electrical Code  
NFPA70 current edition or Canadian Electrical  
Code Part 1 CSA C.22.1.  
506 01 5102 00 March 2008  
 
INSTALLATION INSTRUCTIONS  
Figure 1  
3-phase R-410A Split System Heat Pump  
Clearances (various examples)  
Wall  
Wall  
6”  
24”  
Service  
24”  
Service  
18”  
6”  
18”  
18”  
18”  
Wall  
6”  
Wall  
6”  
24”  
Service  
18”  
18”  
24”  
Service  
6”  
4”  
wide fence  
4”  
6”  
Post  
Wall  
24”  
Service  
24”  
Service  
24”  
Service  
18”  
18”  
18”  
18”  
506 01 5102 00  
3
 
INSTALLATION INSTRUCTIONS  
3-phase R-410A Split System Heat Pump  
UNIT SUPPORT  
NOTE: Unit must be level | 2 degrees (a inch rise or fall  
per foot of run) or compressor may not function properly.  
Figure 2  
Tie Down Knockouts  
View From Top  
Product Family: H series  
A. GROUND LEVEL INSTALLATION  
a” dia. Tie Down Knockouts  
In Base Pan (2 places)  
The unit must be level and supported above grade by  
beams, platform, or a pad. Platform or pad can be of open or  
solid construction but should be of permanent materials  
such as concrete, bricks, blocks, steel, or pressure- treated  
timbers approved for ground contact. Soil conditions must  
be considered so that the platform or pad does not shift or  
settle and leave the unit partially supported. Minimum pad  
dimensions are shown in Figure 2.  
Base  
Pan  
Depth  
If beams or an open platform are used for support, it is  
recommended that the soil be treated or area be graveled  
to reduce the growth of grasses and weeds.  
C
To minimize vibration or noise transmission, it is  
recommended that supports not be in contact with the  
building structure. However, slabs on grade constructions  
with an extended pad are normally acceptable.  
B
!
CAUTION  
PROPERTY DAMAGE HAZARD  
A
Base Pan Width  
Failure to follow this caution may result in proper‐  
ty damage.  
Base Pan  
(Bumpout)  
Width x Depth  
(inches)  
Tie Down  
Knockouts  
Minimum  
Mounting Pad  
Dimensions  
Top surface of platform must be above estimated  
snowfall level to prevent snow blocking coil and to  
allow water melt to drain from unit.  
A
B
C
@
%
n
~
@
^
c
(
z
z
z
$
v
@
!
4
@
^
~
@
^
2
#
!
8
~
#
@
v
(
(
^
^
2
2
@
$
s
#
!
2
~
#
@
2
B. ROOF TOP INSTALLATION  
#
$
,
~
#
^
2
@
*
v
#
%
~
#
^
2
This type of installation is not recommended on wood  
frame structures where low noise levels are required.  
Supporting structure or platform for the unit must be level.  
If installation is on a flat roof, locate unit minimum 6 inches  
above roof level.  
Place the unit over one or more load bearing walls. If there  
are several units, mount them on platforms that are  
self-supporting and span several load bearing walls. These  
suggestions are to minimize noise and vibration  
transmission through the structure. If the structure is a home  
or apartment, avoid locating the unit over bedrooms or study.  
NOTE: When unit is to be installed on a bonded  
guaranteed roof, a release must be obtained from the  
building owner to free the installer from all liabilities.  
C. FASTENING UNIT DOWN  
If conditions or local codes require the unit be attached in  
place, remove the knockouts in the base pan and install  
tie down bolts through the holes (refer to Figure 2).  
Contact local distributor for hurricane hold-down details and the  
P.E. (Professional Engineer) certification, when required.  
!
CAUTION  
PROPERTY DAMAGE HAZARD  
Failure to follow this caution may result in property damage.  
Inadequate unit support may cause excessive vibra‐  
tion, noise, and/or stress on the refrigerant lines,  
leading to refrigerant line failure.  
4
506 01 5102 00  
 
INSTALLATION INSTRUCTIONS  
3-phase R-410A Split System Heat Pump  
REFRIGERATION SYSTEM  
A. COMPONENT MATCHES  
B. REFRIGERANT LINE SETS  
Check to see that the proper system components are in  
place, especially the indoor coil.  
The refrigerant line set must be properly sized to assure  
maximum efficiency and proper oil circulation.  
R-410A outdoor units can only be used with R-410A  
specific indoor coils. If there is a refrigerant mis-match,  
consult the indoor coil manufacturer to determine if a  
refrigerant conversion kit is available for the indoor coil.  
Refer to Product Specifications and Long Line  
Applications Guideline for line set sizing.  
NOTE: If the line set actual length is to exceed 80 feet, or  
if there is more than 20 feet vertical separation between  
outdoor and indoor units, refer to the Long Line  
Application Guideline document for additional  
instructions.  
This outdoor unit is designed for use only with indoor coils  
that utilize a TXV refrigerant metering device. If any other  
type of metering device is installed on the indoor coil,  
consult the indoor coil manufacturer to determine if a TXV  
conversion kit is available.  
NOTE: Line set actual length must not exceed 200 feet.  
NOTE: A crankcase heater must be used when the  
refrigerant line length exceeds 80 feet.  
When installing a TXV on an indoor coil, follow the  
instructions provided with the new TXV.  
If it is necessary to add refrigerant line in the field, use  
dehydrated or dry, sealed, deoxidized, copper  
refrigeration tubing. Do not use copper water pipe.  
A typical TXV installation is shown in Figure 3.  
Do not remove rubber plugs or caps from copper tubing  
until connections are ready to be made.  
!
CAUTION  
Be extra careful when bending refrigeration tubing.  
Tubing can “kink” easily, and if this occurs, the entire  
length of tubing must be replaced.  
PRODUCT DAMAGE HAZARD  
Failure to follow this caution may result in product  
damage.  
Indoor coil and outdoor unit must be listed as a  
certified combination (match) in the ARI Unitary  
Directory of Certified Products.  
!
WARNING  
PERSONAL INJURY HAZARD  
Indoor coil must have R-410A specific, TXV refrig‐  
erant metering device.  
Failure to follow this warning could result in per‐  
sonal injury and/or death.  
Figure 3  
Typical TXV Installation  
Relieve pressure and recover all refrigerant before  
servicing existing equipment, and before final unit  
disposal. Use all service ports and open all flow-  
control devices, including solenoid valves.  
INDOOR  
COIL  
EQUALIZER  
TUBE  
!
CAUTION  
UNIT OPERATION HAZARD  
SUCTION  
TUBE  
SENSING  
BULB  
Failure to follow this caution may result in improp‐  
er product operation.  
Do not leave system open to atmosphere any lon‐  
ger than absolutely required for installation. Inter‐  
nal system components - especially refrigerant  
oils - are extremely susceptible to moisture con‐  
tamination. Keep ends of tubing sealed during  
installation until the last possible moment.  
LIQUID  
TUBE  
TXV  
C. ROUTING AND SUSPENDING REFRIGERANT  
LINES  
SENSING BULB  
(EITHER SIDE)  
Run refrigerant lines as straight and direct as possible,  
avoiding unnecessary bends and turns. Always insulate  
the entire suction line. Both lines should be insulated  
when routed through an attic or when routed through an  
underground raceway.  
STRAP  
SUCTION  
TUBE  
When routing refrigerant lines through a foundation or  
wall, do not allow refrigerant lines to come in direct  
contact with the building structure. Make openings large  
enough so that lines can be wrapped with extra insulation.  
Fill all gaps with RTV caulk. This will prevent noise  
8 O'CLOCK  
4 O'CLOCK  
506 01 5102 00  
5
 
INSTALLATION INSTRUCTIONS  
3-phase R-410A Split System Heat Pump  
transmission between the tubing and the foundation or  
wall.  
pipes, or ductwork. Use insulated or suspension type  
hangers. Metal straps must be at least 1” wide to avoid  
cutting into the tube insulation. Keep the liquid and  
suction lines separate. Refer to Figure 4.  
Along floor or ceiling joists, suspend refrigerant lines so  
that they do not contact the building structure, water  
Figure 4  
Routing and Suspending Refrigerant Lines  
JOIST  
OUTDOOR WALL  
CAULK  
INDOOR WALL  
HANGER STRAP  
(AROUND SUCTION  
INSULATION  
TUBE ONLY)  
LIQUID TUBE  
SUCTION TUBE  
SUCTION TUBE  
INSULATION  
1” MIN  
LIQUID TUBE  
THROUGH THE WALL  
SUSPENSION  
Liquid Line Filter-Drier  
Figure 5  
!
CAUTION  
Installed at Indoor Coil  
UNIT OPERATION HAZARD  
Failure to follow this caution may result in improp‐  
er product operation.  
Do not bury more than 36” of line set underground.  
Refrigerant may migrate to cooler buried section  
during extended periods of unit shut-down, caus‐  
ing refrigerant slugging and possible compressor  
damage at start-up.  
If ANY section of the line set is buried under‐  
ground, provide a minimum 6” vertical rise at the  
service valve.  
D. OUTDOOR UNIT HIGHER THAN INDOOR UNIT  
Proper oil return to the compressor should be maintained  
with suction gas velocity. If velocities drop below 1500  
fpm (feet per minute), oil return will be decreased. To  
maintain suction gas velocity, do not upsize vertical  
suction risers.  
NOTE: If there is more than 20 feet vertical separation  
between outdoor and indoor units, refer to the Long Line  
Application Guidline document for additional instructions.  
E. LIQUID LINE FILTER-DRIER  
Outdoor units are shipped with an appropriate filter-drier  
for installation in the liquid line. Leave the plugs in the tube  
ends until the filter-drier is installed. The optimal location  
for the filter-drier is close to the indoor coil. Heat pump  
filter-driers are “bi-flow” type. Either end can be pointed  
towards indoor coil. Refer to Figure 5.  
Filter-Drier  
38-11-84  
6
506 01 5102 00  
 
INSTALLATION INSTRUCTIONS  
F. SERVICE VALVES  
3-phase R-410A Split System Heat Pump  
Clean line set tube ends with emery cloth or steel brush.  
Remove any grit or debris.  
Service valves are closed and plugged from the factory.  
Outdoor units are shipped with a refrigerant charge  
sealed in the unit. Leave the service valves closed until all  
other refrigerant system work is complete or the charge  
will be lost. Leave the plugs in place until line set tubing is  
ready to be inserted.  
Insert line set tube ends into service valve tube stubs.  
Apply heat absorbing paste or heat sink product between  
service valve and joint. Wrap service valves with a heat  
sinking material such as a wet cloth.  
Braze joints using a Sil-Fos or Phos-copper alloy.  
Heat pumps require a piston metering device in the liquid  
service valve for proper heating operation. Piston is  
shipped in the piston body of the liquid service valve,  
temporarily held in place with a plastic cap. Do not remove  
the plastic cap until line set tubing is ready to be installed.  
!
CAUTION  
PRODUCT DAMAGE HAZARD  
Refer to Figure 6 and follow these steps for piston  
installation:  
Failure to follow this caution may result in product  
damage.  
1. Remove plastic cap holding piston in piston body of  
liquid service valve.  
Braze with Sil-Fos or Phos-copper alloy on cop‐  
per-to-copper joints and wrap a wet cloth around  
rear of fitting to prevent damage to TXV.  
2. Check that piston size (stamped on side of piston)  
matches with number listed on unit rating plate.  
Return piston to piston body of liquid service valve  
(either direction).  
H. EVACUATING LINE SET AND INDOOR COIL  
The unit is shipped with a factory refrigerant charge. The  
liquid line and suction line service valves have been  
closed after final testing at the factory. Do not disturb  
these valves until the line set and indoor coil have been  
evacuated and leak checked, or the charge in the unit  
may be lost.  
3. Find plastic bag taped to unit containing copper  
adapter tube, brass nut, and plastic washer.  
4. Install plastic washer in the seat inside piston body.  
5. Fit brass nut onto adapter tube and install tube  
onto liquid service valve. Tighten nut finger tight,  
then wrench additional ½ turn only. Over tightening  
may damage the plastic washer.  
NOTE: Do not use any portion of the factory charge for  
purging or leak testing. The factory charge is for filling the  
system only after a complete evacuation and leak check  
has been performed.  
Service valve bodies are brass and suction tube stub is  
copper.  
Liquid Service Valve with Piston  
and Adapter Tube  
!
Figure 6  
CAUTION  
PRODUCT DAMAGE HAZARD  
BRASS NUT  
Failure to follow this caution may result in product  
damage.  
ADAPTER TUBE  
PLASTIC WASHER  
Never use the outdoor unit compressor as a vacu‐  
um pump. Doing so may damage the compressor.  
Line set and indoor coil should be evacuated using the  
recommended deep vacuum method of 500 microns. If  
deep vacuum equipment is not available, the alternate  
triple evacuation method may be used by following the  
specified procedure.  
PISTON  
PISTON BODY  
LIQUID SERVICE VALVE  
If vacuum must be interrupted during the evacuation  
procedure, always break vacuum with dry nitrogen.  
G. BRAZING CONNECTIONS  
Deep Vacuum Method  
The deep vacuum method requires a vacuum pump  
capable of pulling a vacuum to 500 microns and a vacuum  
gauge capable of accurately measuring this vacuum  
level. The deep vacuum method is the most positive way  
of assuring a system is free of air and water.  
!
WARNING  
FIRE HAZARD  
Failure to follow this warning could result in per‐  
sonal injury, death, and/or property damage.  
Watch the vacuum gauge as the system is pulling down.  
The response of the gauge is an indicator of the condition  
of the system (refer to Figure 7).  
Refrigerant and oil mixture could ignite and burn  
as it escapes and contacts brazing torch. Make  
sure the refrigerant charge is properly removed  
from both the high and low sides of the system be‐  
fore brazing any component or lines.  
With no leaks in the system, allow the vacuum pump to  
run for 30 minutes minimum at the deep vacuum level.  
506 01 5102 00  
7
 
INSTALLATION INSTRUCTIONS  
3-phase R-410A Split System Heat Pump  
Deep Vacuum Gauge Response  
and System Conditions  
Figure 8  
Triple Evacuation Sequence  
EVACUATE  
Figure 7  
5000  
4500  
4000  
3500  
3000  
2500  
2000  
1500  
1000  
500  
BREAK VACUUM WITH DRY NITROGEN  
LEAK IN  
SYSTEM  
WAIT  
EVACUATE  
BREAK VACUUM WITH DRY NITROGEN  
WAIT  
VACUUM TIGHT  
TOO WET  
TIGHT  
DRY SYSTEM  
0
1
2
3
MINUTES  
4
5
6
7
EVACUATE  
CHECK FOR TIGHT, DRY SYSTEM  
(IF IT HOLDS DEEP VACUUM)  
Triple Evacuation Method  
The triple evacuation method should only be used when  
system does not contain any water in liquid form and  
vacuum pump is only capable of pulling down to 28 inches  
of mercury. Refer to Figure 8 and proceed is as follows:  
CHARGE SYSTEM  
I. OPENING SERVICE VALVES  
1. Pull system down to 28 inches of mercury and  
allow pump to continue operating for an additional  
15 minutes.  
Outdoor units are shipped with a refrigerant charge  
sealed in the unit. Opening the service valves releases  
this charge into the system.  
2. Close manifold valves or valve at vacuum pump  
and shut off vacuum pump.  
NOTE: Open the Suction service valve first. If the Liquid  
service valve is opened first, oil from the compressor may  
be drawn into the indoor coil TXV, restricting refrigerant  
flow and affecting operation of the system.  
3. Connect a nitrogen cylinder and regulator to  
system and fill with nitrogen until system pressure  
is 2 psig.  
Remove Suction service valve cap and insert a hex  
wrench into the valve stem. Hold the valve body steady  
with an end-wrench and back out the stem by turning the  
hex wrench counterclockwise. Turn the stem until it just  
contacts the rolled lip of the valve body.  
4. Close nitrogen valve and allow system to stand for  
1 hour. During this time, dry nitrogen will diffuse  
throughout the system absorbing moisture.  
5. Repeat this procedure as indicated in Figure 8.  
6. After the final evacuate sequence, confirm there  
are no leaks in the system. If a leak is found, repeat  
the entire process after repair is made.  
After the refrigerant charge has bled into the system,  
open the Liquid service valve.  
NOTE: These are not back-seating valves. It is not  
necessary to force the stem tightly against the rolled lip.  
The service valve cap is a primary seal for the valve and  
must be properly tightened to prevent leaks. Make sure  
cap is clean and apply refrigerant oil to threads and  
sealing surface on inside of cap.  
Tighten cap finger tight and then tighten additional 6 of a  
turn (1 wrench flat) to properly seat the sealing surfaces.  
J. GAUGE PORTS  
Check for leaks at the schrader ports and tighten valve  
cores if necessary. Install plastic caps finger tight.  
8
506 01 5102 00  
 
INSTALLATION INSTRUCTIONS  
3-phase R-410A Split System Heat Pump  
ELECTRICAL WIRING  
Phase Monitor Relay Board  
!
WARNING  
The Phase Monitor Board detects the sequence of the  
three phase electrical system, and a relay breaks the Y  
(call for cooling) control signal if the phasing is incorrect.  
Additionally, the board will detect the loss of voltage on  
any of the three phase inputs and break the Y signal in the  
same way.  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in per‐  
sonal injury or death.  
Before installing, modifying or servicing system,  
turn OFF the main (remote) electrical disconnect  
device. There may be more than one disconnect  
device.  
An LED on the board displays the following status:  
Normal function, relay contact  
closed.  
Red LED ON -  
Red LED Blinking - Abnormal function, relay contact  
open.  
Refer to unit rating plate for the required supply voltage.  
Depending on the model, required supply voltage will be:  
Red LED OFF -  
No 24 VAC control power present at  
board.  
208/230 V, 3-phase, 60 Hz.  
or  
NOTE: Units with Comfort Alertt Diagnostics device  
have phase monitor feature built in.  
460 V, 3-phase, 60 Hz.  
Outdoor units are approved for use with copper  
conductors only. Do not use aluminum wire.  
Figure 10  
Phase Monitor Relay Board  
Refer to unit rating plate for minimum circuit ampacity and  
circuit protection requirements.  
Grounding  
Permanently ground unit in accordance with the National  
Electrical Code and local codes or ordinances. Use a  
copper conductor of the correct size from the grounding  
lug in control box to a grounded connection in the service  
panel or a properly driven and electrically grounded  
ground rod.  
Supply Voltage Wiring Connections  
Make all outdoor electrical supply (Line Voltage)  
connections with raintight conduit and fittings. Most  
codes require a disconnect switch outdoors within sight of  
the unit. Consult local codes for special requirements.  
Route electrical supply (Line Voltage) wiring through  
knockout hole in bottom of Control Box.  
Thermostat Wiring Connections  
Connect two power wires to Contactor and one power  
wire to Blue lead wire (use wire nut). Connect ground wire  
to Ground Lug. Refer to Wiring Diagram on unit and  
Figure 9.  
Route thermostat wiring through rubber grommet in  
bottom of Control Box. Low voltage lead wires are  
provided in the control box for connection to thermostat  
wires (use wire nuts). Refer to Wiring Diagram on unit and  
Figure 11 for low voltage wiring examples.  
208/230 V and 460 V  
Electrical Supply  
(Line Voltage) Connections  
Figure 9  
NOTE: Use No. 18 AWG (American Wire Gage)  
color-coded, insulated (35 °C minimum) wire. If  
thermostat is located more than 100 feet (30.5 m) from  
unit as measured along the control voltage wires, use No.  
16 AWG color-coded wires to avoid excessive voltage  
drop.  
DISCONNECT  
PER NEC AND/OR  
LOCAL CODES  
CONTACTOR  
11  
L1  
FIELD POWER  
WIRING  
L3  
13  
L2  
BLUE LEAD WIRE  
FIELD GROUND  
WIRING  
GROUND  
LUG  
506 01 5102 00  
9
 
INSTALLATION INSTRUCTIONS  
Figure 11  
3-phase R-410A Split System Heat Pump  
Typical Thermostat (Control Circuit) Connections  
NOTE: WHEN USING OUTDOOR THERMOSTATS, W MUST BE ENERGIZED WHEN REQUESTING SUPPLEMENTAL HEAT.  
2
SYSTEMS WITH ONE OUTDOOR THERMOSTAT  
SYSTEMS WITH TWO OUTDOOR THERMOSTATS  
OUTDOOR  
SPLICE  
CONNECTION  
INDOOR  
SPLICE  
CONNECTION  
THERMOSTAT  
SUBBASE  
DEFROST  
BOARD  
THERMOSTAT  
SUBBASE  
INDOOR  
SPLICE  
CONNECTION  
OUTDOOR  
SPLICE  
CONNECTION  
DEFROST  
BOARD  
W
3
W
3
ODT  
SHR  
C
C
C
C
C
C
W
2
W E  
2
W
2
W
2
W
2
W
2
ODT  
L
G
Y
L
G
Y
G
G
SHR  
Y
Y
ODT  
E
R
E
O
R
EHR  
E
O
R
O
R
O
R
R
REMOVE WIRES FROM CRIMP NUT IN INDOOR FAN COIL WHEN INSTALLING OUTDOOR THERMOSTATS.  
SYSTEMS WITHOUT OUTDOOR THERMOSTATS  
INDOOR  
SPLICE  
OUTDOOR  
SPLICE  
CONNECTION  
THERMOSTAT  
SUBBASE  
DEFROST  
BOARD  
CONNECTION  
LEGEND  
C
C
24ꢀ-V FACTORY WIRING  
C
24ꢀ-V FIELD WIRING  
W2  
W2  
W2  
FIELD SPLICE CONNECTION  
OUTDOOR THERMOSTAT  
EMERGENCY HEAT RELAY  
SUPPLEMENTAL HEAT RELAY  
L
G
G
Y
EHR  
SHR  
Y
E
O
R
O
R
R
10  
506 01 5102 00  
 
INSTALLATION INSTRUCTIONS  
3-phase R-410A Split System Heat Pump  
DEFROST SYSTEM  
A. DEFROST THERMOSTAT  
7. Unit will remain in defrost for remainder of  
defrost-cycle time or until defrost thermostat  
reopens at approximately 65 °F coil temperature of  
liquid line.  
The defrost thermostat is factory installed on a short tube  
stub extending from the coil end plate. Refer to Figure 12  
and confirm that the thermostat is securely fastened in  
place on the tube stub.  
8. Turn off power to outdoor unit and reconnect  
fan-motor lead to OF2 on control board (refer to  
Figure 13).  
Figure 12  
Defrost Thermostat  
Figure 13  
Defrost Control Board  
FEEDER TUBE  
TUBE STUB  
H9C1  
®
O1  
C
US  
OF1  
K1  
COIL  
OF2  
DEFROST  
THERMOSTAT  
C19  
C9  
C1  
1
U1  
B. DEFROST CONTROL BOARD  
C17  
The defrost board is a time/temperature control which  
includes a field-selectable time period between defrost  
cycles of 30, 60, or 90 minutes (quick-connects located  
at board edge, factory set at 90 minutes).  
1
Defrost mode is identical to cooling mode except that  
outdoor-fan motor stops and second-stage heat is  
turned on to continue warming conditioned space.  
R20  
Initially, the defrost cycle timer starts when the contactor  
is energized and a 24 VAC signal is present on the T1  
terminal. Then the defrost cycle begins when the defrost  
thermostat is closed and the cycle timer times out (30, 60,  
90 or minutes).  
P3  
1
1
J2  
DFT  
Y
P2  
W1  
30 60 90  
T1 C C O  
J1  
P1  
1
1
SPEEDUP  
To initiate a forced defrost cycle, the defrost thermostat  
must be closed. This can be accomplished as follows:  
O
R
1. Turn off power to outdoor unit.  
W
2
2. Disconnect outdoor fan-motor lead from OF2 on  
control board (refer to Figure 13). Tape lead to  
prevent grounding.  
Y
C
3. Restart unit in heating mode, allowing frost to  
accumulate on outdoor coil.  
4. After a few minutes in heating mode, liquid line  
temperature should drop below closing point of  
defrost thermostat (approximately 32 °F).  
5. Short between speed-up terminals with a  
flat-bladed screwdriver (refer to Figure 13). This  
reduces the timing sequence to 7, 14, or 21  
seconds (30, 60, or 90 minute defrost selection,  
respectively).  
6. When you hear reversing valve change position,  
remove screwdriver immediately; otherwise,  
control will terminate normal 10-minute defrost  
cycle in approximately 2 seconds.  
NOTE: Length of defrost cycle is dependent upon length  
of time it takes to remove screwdriver from test pins after  
reversing valve has shifted.  
506 01 5102 00  
11  
 
INSTALLATION INSTRUCTIONS  
3-phase R-410A Split System Heat Pump  
START-UP PROCEDURE  
1. Set indoor thermostat selector switch to OFF.  
2. Turn ON all electrical disconnect devices.  
5. Set indoor thermostat selector switch to COOL or  
HEAT. Operate unit for minimum 15 minutes, then  
check the system refrigerant charge.  
3. If unit has a crankcase heater, energize the heater  
and wait 24 hours before proceeding.  
Check For Proper Phasing  
Observe the LED on the Phase Monitor Relay Board. If  
the LED is blinking, turn off power to the unit and swap any  
two of the supply voltage wires. Turn power back on and  
repeat the start-up procedure.  
4. Set indoor thermostat at desired temperature. Be  
sure setpoint is below indoor ambient temperature  
to call for cooling, or above indoor ambient to call  
for heating.  
REFRIGERANT CHARGE  
A. COOLING MODE  
4. Refer to unit rating plate for required subcooling  
temperature.  
Outdoor units are shipped with a refrigerant charge to  
match a specific indoor coil and 15 feet of refrigerant line.  
If shorter or longer refrigerant lines or a different indoor  
coil are used, the charge will have to be adjusted.  
5. Refer to Figure 14. Find the required liquid line  
temperature where the rating plate subcooling  
temperature intersects measured liquid service  
valve pressure.  
For different line lengths, add or remove charge based on  
0.6 ounces charge per foot of difference. For example, a  
25 foot line set is 10 feet longer than the specified 15 feet.  
Add 0.6 ounces charge for each of the extra 10 feet:  
6. If the measured liquid line temperature is higher  
than the chart number, add refrigerant to lower the  
measured temperature.  
NOTE: When adding refrigerant, charge in liquid  
form, using a flow restricting device, into the  
suction port.  
If the measured liquid line temperature is lower  
than the chart number, reclaim refrigerant to raise  
the measured temperature.  
10 x 0.6 = 6.0 ounces additional charge  
This outdoor unit is designed for use only with indoor coils  
that utilize a TXV refrigerant metering device. With an  
indoor TXV, use the subcooling method to make final  
charge adjustments:  
Tolerance is | 3 °F.  
NOTE: Only use subcooling charging method when  
S outdoor ambient temperature is between 70_F and 100_F  
S indoor temperature is between 70_ and 80_F  
S line set is less that 80 feet.  
B. HEATING MODE  
To check system operation during heating cycle, refer to  
the Tech Label on outdoor unit. This chart indicates  
whether a correct relationship exists between system  
operating pressure and air temperature entering indoor  
and outdoor units. If pressure and temperature do not  
match on chart, system refrigerant charge may not be  
correct. Do not use chart to adjust refrigerant charge.  
1. Operate unit a minimum of 15 minutes before  
checking charge.  
NOTE: If outdoor unit has a 2-speed fan motor,  
motor will operate in low speed when outdoor  
ambient temperature is below 82 °F. Pull one of the  
yellow low voltage wires off the fan control and the  
unit will default to high speed fan for servicing.  
Reconnect wire after servicing.  
NOTE: When charging is necessary during heating  
season, charge must be weighed in accordance with unit  
rating plate 0.6 ounces per foot of a inch liquid line  
above or below 15 feet respectively.  
2. Measure liquid service valve pressure by attaching  
an accurate gauge to service port.  
3. Measure liquid line temperature by attaching an  
accurate thermistor type sensor or electronic  
thermometer to liquid line near outdoor coil.  
12  
506 01 5102 00  
 
INSTALLATION INSTRUCTIONS  
Figure 14  
3-phase R-410A Split System Heat Pump  
R-410A Required Liquid Line Temperature (°F) - Cooling Mode  
Rating Plate (required)  
Subcooling Temperature (°F)  
Rating Plate (required)  
Subcooling Temperature (°F)  
Measured Liquid  
Pressure (psig)  
Measured Liquid  
Pressure (psig)  
6
8
10  
74  
76  
78  
80  
82  
84  
86  
88  
90  
92  
94  
96  
12  
72  
74  
76  
78  
80  
82  
84  
86  
88  
90  
92  
94  
14  
70  
72  
74  
76  
78  
80  
82  
84  
86  
88  
90  
92  
16  
68  
70  
72  
74  
76  
78  
80  
82  
84  
86  
88  
90  
6
8
10  
12  
104 102 100 98  
14  
96  
16  
94  
96  
251  
259  
266  
274  
283  
291  
299  
308  
317  
326  
335  
345  
78  
80  
82  
84  
86  
88  
90  
92  
94  
96  
98  
76  
78  
80  
82  
84  
86  
88  
90  
92  
94  
96  
364  
374  
384  
395  
406  
416  
427  
439  
450  
462  
474  
106 104 102 100 98  
108 106 104 102 100 98  
110 108 106 104 102 100  
112 110 108 106 104 102  
114 112 110 108 106 104  
116 114 112 110 108 106  
118 116 114 112 110 108  
120 118 116 114 112 110  
122 120 118 116 114 112  
124 122 120 118 116 114  
100 98  
SEQUENCE OF OPERATION  
A. COOLING MODE  
B. HEATING MODE  
On a call for cooling, the thermostat makes circuits R-O,  
R-Y, and R-G. Circuit R-O energizes reversing valve,  
switching it to cooling position. Circuit R-Y energizes  
contactor, starting outdoor fan motor and compressor.  
Circuit R-G energizes indoor unit blower relay, starting  
indoor blower motor.  
On a call for heating, the thermostat makes circuits R-Y  
and R-G (circuit R-O is NOT made, and the reversing  
valve stays in the de-energized, heating position). Circuit  
R-Y energizes contactor, starting outdoor fan motor and  
compressor. Circuit R-G energizes indoor blower relay,  
starting blower motor. If the room temperature continues  
to fall, circuit R-W2 is made through the second-stage  
room thermostat bulb. Circuit R-W2 energizes a  
sequencer, bringing on the first bank supplemental  
electric heat and providing electrical potential to the  
second heater sequencer (if used). If outdoor  
temperature falls below the setting of the outdoor  
thermostat (field-installed option), contacts close to  
complete the circuit and bring on the second bank of  
supplemental electric heat.  
When thermostat is satisfied, its contacts open,  
de-energizing contactor and blower relay. Compressor  
and motors stop.  
NOTE: If indoor unit is equipped with a time-delay relay  
circuit, the blower runs an additional length of time to  
increase system efficiency. (Applies to both cooling and  
heating modes.)  
NOTE: Low ambient cooling feature allows unit to  
operate safely in cooling mode down to 0_ F outdoor  
ambient.  
When the thermostat is satisfied, its contacts open,  
de-energizing contactor, blower relay, and sequencer.  
Compressor, motors, and heaters stop.  
506 01 5102 00  
13  
 
INSTALLATION INSTRUCTIONS  
3-phase R-410A Split System Heat Pump  
TROUBLESHOOTING  
Some models are factory equipped with the Comfort  
Alertt Diagnostics device in the control box (refer to  
Figure 15). Comfort Alert provides around-the-clock  
monitoring for common electrical problems, compressor  
defects, and broad system faults. If trouble is detected, an  
alert code is displayed with a flashing LED indicator.  
Comfort Alertt Diagnostics  
Figure 15  
(some models)  
NOTE: Comfort Alert is required for unit operation.  
Comfort Alert provides active safety protection and  
compressor may be shut down. Alert codes are listed in  
Figures 16 and 17.  
POWER LED  
Y2  
Second Stage  
Compressor Signal  
Y
Comfort Alert is factory wired and requires no  
modification. Low voltage lead wires are provided in the  
control box for connection to thermostat wires (use wire  
nuts).  
First Stage  
Compressor Signal  
DATA  
PORT  
L
24 VAC for Thermostat  
Indicator  
R
24 Volt Power  
The Comfort Alert device operates by monitoring the  
compressor power leads and the thermostat demand  
signal (Y terminal). It draws constant 24 VAC power at the  
R and C terminals.  
C
P
24 Volt Common  
24 Volt Compressor  
Protection Function  
DC Compressor  
Solenoid  
DC  
SOL  
ALERT LED  
TRIP LED  
Compressor Wires  
Pass Through Holes (3)  
MAINTENANCE  
Condensate Drain  
2. Keep the coil free of grass clippings, leaves,  
weeds, and other debris.  
During the cooling season, check monthly for free flow of  
drainage and clean if necessary.  
NOTE: Coil may occasionally require cleaning with  
a liquid solution. The coil must be cold when  
cleaning. Use an alkaline based cleaner only.  
Cleaning a hot coil or using an acid based cleaner  
will remove the paint from the fins and may clog the  
coil.  
Cleanliness  
These tips will help keep the air conditioner looking better  
and working more efficiently:  
1. Free flow of air is essential. Keep fences, shrubs,  
trash cans, and other obstructions at least 18  
inches from all coil inlets.  
3. Never use a weather cover over the outdoor unit  
unless it is a ventilated type or made of breathable  
fabric that will allow moisture to evaporate rapidly.  
A cover that holds moisture in the unit will cause  
more rust build-up and damage than normal  
exposure to weather.  
14  
506 01 5102 00  
 
INSTALLATION INSTRUCTIONS  
Figure 16  
3-phase R-410A Split System Heat Pump  
Comfort Alertt Diagnostics (some models)  
Status LED Status LED Description  
Green “POWER” Module has power  
Status LED Troubleshooting Information  
Supply voltage is present at module terminals  
Red “TRIP” LED Thermostat demand signal 1. Compressor protector is open  
On Solid  
Y1 is present, but the  
compressor is not running  
2. Outdoor unit power disconnect is open  
3. Compressor circuit breaker or fuse(s) is open  
4. Broken wire or connector is not making contact  
5. Compressor power wires not routed through Comfort Alert  
6. Compressor contactor has failed open  
Red “TRIP”  
LED Flashing  
The anti-short cycle timer (3 minutes), in module is preventing compressor restart.  
Module locks out compressor when compressor damaging ALERT codes appear. Lockout ALERT codes are  
noted in the Status LED Description; during a compressor lockout, 24VAC power must be removed from module  
to manually reset.  
Yellow “ALERT” A short circuit or over  
LED On Solid current condition exists on  
PROT terminal  
1. Compressor contact coil shorted  
2. Electrical load too high for PROT circuit (maximum) 1 amp  
3. 24 VAC wired directly to PROT terminal  
1. High head pressure  
Yellow “ALERT” System Pressure Trip  
Flash Code 2  
Discharge or suction  
2. Condenser coil poor air circulation (dirty, blocked, damaged)  
3. Condenser fan is not running  
pressure out of limits or  
compressor overloaded (if  
no high pressure switch in  
system) LOCKOUT  
4. If low pressure switch present in system, check Flash Code 3  
information  
Yellow “ALERT” Short Cycling  
Flash Code 3 Compressor is running only  
briefly LOCKOUT  
1. If low pressure switch is open:  
a. Low refrigerant charge  
b. Evaporator bower is not running  
c. Evaporator coil is frozen  
d. Faulty metering device  
e. Condenser coil is dirty  
f. Liquid line restriction  
2. If high pressure switch present go to Flash Code 2 information  
3. Intermittent thermostat demand signal  
4. System or control board defective  
Yellow “ALERT” Locked Rotor  
Flash Code 4 LOCKOUT  
1. Low line voltage to compressor  
2. Excessive liquid refrigerant in compressor  
3. Compressor bearings are seized  
Yellow “ALERT” Open Circuit  
Flash Code 5  
1. Outdoor unit power disconnect is open  
2. Compressor circuit breaker or fuse(s) is open  
3. Compressor contactor has failed open  
4. High pressure switch is open and requires manual reset  
5. Broken supply wires or connector is not making contact  
6. Unusually long compressor protector reset time due to ex‐  
treme ambient temperature  
7. Compressor windings are damaged  
Yellow “ALERT” Missing Phase  
Flash Code 6  
1. Compressor fuse is open on one phase  
2. Broken wire or connector on one phase  
3. Compressor motor winding is damaged  
4. Utility supply has dropped one phase  
LOCKOUT  
Yellow “ALERT” Reverse Phase  
Flash Code 7 LOCKOUT  
1. Compressor running backward do to supply phase reversal  
Yellow “ALERT” Welded Contactor  
Flash Code 8 Compressor always runs  
1. Compressor contactor has failed closed  
2. Thermostat demand signal not connected to module  
1. Control circuit transformer is overloaded  
2. Low line voltage to compressor  
Yellow “ALERT” Low Voltage  
Flash Code 9 Control circuit < 18VAC  
S Flash Code number corresponds to a number of LED flashes, followed by a pause and then repeated.  
S TRIP and ALERT LEDs flashing at same time means control circuit voltage is too low for operation.  
S Reset ALERT Flash code by removing 24VAC power from module.  
S Last ALERT Flash code is displayed for 1 minute after module is powered on.  
S ALERT codes can be reset manually or automatically. ALERT codes that result in a lockout or compressor  
lockout can only be reset manually.  
- For manual reset, cycle power to Comfort Alert off and on.  
- For automatic reset, Comfort Alert will continue to monitor compressor and system; if condition returns to  
normal, the ALERT code is automatically turned off.  
506 01 5102 00  
15  
 
INSTALLATION INSTRUCTIONS  
3-phase R-410A Split System Heat Pump  
Figure 17  
Miswired Module Indication  
Comfort Alertt Diagnostics (some models)  
Troubleshooting Information  
Green LED is not on, module Determine if both R and C module terminals are connected. Verify voltage is  
does not power up present at module's R and C terminals.  
Green LED intermittent, mod‐ Determine if R and Y terminals are wired in reverse. Verify module's R and C ter‐  
ule powers up only when com‐ minals have a constant source.  
pressor runs  
TRIP LED is on but system  
and compressor check OK  
Verify Y terminal is wired properly per OEM wiring diagram. Verify voltage at con‐  
tactor coil falls below 0.5VAC when off. Verify 24VAC is present across Y and C  
when thermostat demand signal is present. If not, R and C are reverse wired.  
TRIP LED and ALERT LED  
flashing together  
Verify R and C terminals are supplied with 19-28VAC.  
ALERT Flash Code 3  
(Compressor short cycling)  
displayed incorrectly  
Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at  
contactor coil falls below 0.5VAC when off.  
ALERT Flash Code 5 or 6 Check that compressor T1 and T3 wires are through module's current sensing  
(Open Circuit, Missing Phase) holes. Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at  
displayed incorrectly  
contactor coil falls below 0.5VAC when off.  
ALERT Flash Code 8  
Determine if module's Y terminal is connected. Verify Y terminal is connected to  
(Welded Contactor) displayed 24VAC at contactor coil. Verify 24VAC is present across Y and C when  
incorrectly mostat demand signal is present. If not, R and C are reversed wired. Verify  
voltage at contactor coil falls below 0.5VAC when off. Review.  
ther‐  
R-410A QUICK REFERENCE GUIDE  
R-410A refrigerant operates at 50% - 70% higher pressures than R-22. Be sure that servicing equipment and  
replacement components are designed to operate with R-410A.  
R-410A refrigerant cylinders are rose colored.  
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.  
R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.  
Manifold sets should be 750 psig high-side and 200 psig low-side with 520 psig low-side retard.  
Use hoses with 750 psig service pressure rating.  
Leak detectors should be designed to detect HFC refrigerant.  
R-410A, as with other HFC refrigerants, is only compatible with POE oils.  
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.  
POE oils may cause damage to certain plastics and roofing materials.  
Vacuum pumps will not remove moisture from oil.  
A liquid line filter-drier is required on every unit.  
Do not use liquid line filter-driers with rated working pressures less than 600 psig.  
Do not install a suction line filter-drier in liquid line.  
Wrap all filter-driers and service valves with wet cloth when brazing.  
Do not use with an R-22 TXV.  
If indoor unit is equipped with an R-22 TXV, it must be changed to an R-410A TXV.  
Do not use capillary tube indoor coils.  
Never open system to atmosphere while it is under a vacuum.  
When system must be opened for service, break vacuum with dry nitrogen and replace all filter-driers.  
Do not vent R-410A into the atmosphere.  
Observe all WARNINGS, CAUTIONS, NOTES, and bold text.  
International Comfort Products, LLC  
 
Lewisburg, TN 37091  
16  
506 01 5102 00  

Grandstream Networks Security Camera GXV3611 User Manual
Grizzly Saw H7724 User Manual
Haier Refrigerator ZHBCN05FVS User Manual
Harrington Hoists Chainsaw Sharpener 10 2 AH250 AH500 Main Body User Manual
Hotpoint Clothes Dryer VTD60 User Manual
Hotpoint Refrigerator RFA52 User Manual
HP Hewlett Packard Switch CZ155A#B1H User Manual
Huawei Wireless Office Headset ETS3023 User Manual
Husqvarna Trimmer H348SG User Manual
Hyundai IT Car Video System H CMD7082 User Manual