HP Hewlett Packard Power Supply 16A User Manual

hp Modular Power Distribution Units  
(Zero-U/1U Modular PDUs)  
QuickSpecs  
MODELS  
Low Voltage Modular PDU Model, 100 – 127 VAC  
24A Model – mPDU, 24A, Low  
252663-D71 (NA/LA/JPN)  
High Voltage Modular PDU Model(s), 200 – 240 VAC  
16A Model – mPDU, 16A, High  
252663-B24 (WW)  
24A Model – mPDU, 24A, High  
252663-D72 (NA/LA/JPN)  
32A Model – mPDU, 32A, High  
252663-B31 (INT’L)  
40A Model – mPDU, 40A, High  
252663-B21 (WW)  
Feature List  
Single input power distribution units with a unique modular design architecture  
Up to 32 outlet receptacles  
Zero-U/1U dense rack form factor  
Easily accessible outlet receptacles and improved cable management  
Models range from 16A-40A  
DA-11041  
World Wide — Version 3 — December 11, 2002  
 
1
hp Modular Power Distribution Units  
(Zero-U/1U Modular PDUs)  
QuickSpecs  
PRODUCT HIGHLIGHTS (continued)  
Consolidate and Maximize Cord Management  
When you have the power to choose where to mount the Extension Bars, you have the option of mounting the bars closer to where your specific servers  
are located; so you dont have to use long power cords running down the entire length of your rack – you can now get smaller cords plugging-in to a  
nearby Extension Bar.  
Shorter jumper cords (4.5ft) are offered as optional kits (PN 142257-006, quantity 1; PN 142257-007, quantity 15). Two short jumper cords ship with every  
high voltage model of the mPDU. Additional shorter cords, if needed, have to be ordered (typically most devices ship with a 12ft – 8ft long jumper cord).  
For more information on IEC320 -C14 to IEC 320 -C13 jumper cords, please refer the PDU cable section at the end of this document.  
For low voltage applications (100 – 127V), typically most devices ship with a NEMA 5-15 cable (which plugs-into the NEMA 5-15R outlets on the low volt  
Extension Bar). However, some devices with IEC320-C13 inlet may not ship with a NEMA cable. In such cases, a cable IEC320-C14 to NEMA 5-15P (PN  
e7743a) will have to be ordered.  
Easily Accessible Outlet Receptacles  
Because you have the flexibility to decide how you want to configure your Modular PDU, you can now choose to mount the Extension Bars such that the  
outlet receptacles are easily accessible, allowing you to easily plug-in and plug-out devices.  
Current Ratings from 16A to 40A  
Modular PDUs are available in a wide range, including four high volt models ranging from 16A to 40A current ratings; and one low voltage 24A model.  
Compatibility  
Ideal for use with the HP 9000 and 10000 Series Racks, the Modular PDUs are largely designed for the dense rack environment. These Modular PDUs  
connect directly to the facility input power.  
In addition, the low voltage model also connects to the low voltage UPS R3000 XR. The 40A model may be hardwired to a UPS as well. And the recently  
announced 16A high voltage model will also connect to the high voltage UPS models of the R3000 XR and R6000.  
Note: Control unit of the Modular PDUs may be mounted in a 1U configuration in most standard racks. To mount the Extension Bars in a rack other than  
the HP 9000 and 10000 series racks, an optional kit PN 310777-B21 is offered. This kit allows mounting the Extension Bars in most third party racks  
which use a standard EIA19vertical rail.  
SERVICE & SUPPORT, CAREPAQ AND WARRANTY INFORMATION  
Warranty Upgrade Options  
HP Modular PDUs are backed by a limited 3-year warranty.  
When used in the HP 9000 and 10000 Series Racks, HP PDUs assume the warranty of theHP Rack in which theyre installed. HP CarePaq services  
bought for the HP Rack also extend towards the HP Modular PDU if it is being used inside the HP rack.  
FM-CBXHW-36 – 9x5 Next-Business-Day On-Site Coverage, 3 Years  
FM-CB4HR-36 – 9x5 4-Hour Response On-Site Coverage, 3 Years  
FM-CB724-36 – 24x7, 4-Hour Response On-Site Coverage, 3 Years  
CarePaq Information  
For CarePaq (hardware & software) information, as well as orderable part numbers, please refer to the URL listed below:  
DA-11041  
World Wide — Version 3 — December 11, 2002  
 
3
hp Modular Power Distribution Units  
(Zero-U/1U Modular PDUs)  
QuickSpecs  
HP MODULAR PDU SPECIFICATIONS  
Mechanical Dimensions (WxHxD) 17.5 x 1.62 x 5.6 in/44.45 x 4.11 x 14.22 cm  
Unit Weight  
18 lb/8.16 kg  
Shipping Dimensions (WxHxD)  
Shipping Weight  
21.5 x 12.25 x 13.0 in/54.61 x 31.12 x 33.02 cm  
20.2 lb/9.16 kg  
Operating Temperature  
Operating Relative Humidity (%)  
Operating Elevation  
50° to 122°F/10° to 50°C  
10% to 90%  
0 to 10,000 ft/0 to 3048 m  
–4° to 140°F/–20° to 60°C  
5% to 95%  
Storage Temperature  
Storage Relative Humidity (%)  
Storage Elevation  
0 to 30,000 ft/0 to 9144 m  
Conformance Standards  
UL, CUL, CE, NOM, D - 16A and 40A models  
UL, CUL, NOM – 24A High and Low voltage models  
CE, D - 32A model  
Kit Contents  
24-40A Modular PDUs ship with x1 Control Unit and x4 Extension Bars  
16A Modular PDU ship with x1 Control Unit and x2 Extension Bars  
All models ship with:  
0U/1U Mounting brackets/hardware for Control Unit  
Mounting brackets for Extension Bars  
Cord Retention bracket for the Control Unit  
Tie wraps  
Install Card  
High voltage models ship with two 10A, IEC320 -C14 to IEC 320 -C13 jumper cables, each 4.5ft/1.37m long. In  
addition, the 16A model ships with one 16A, IEC 320-C19 to IEC 320-C20 jumper cord, 8.2ft/2.5m long.  
DA-11041  
World Wide — Version 3 — December 11, 2002  
4
 
hp Modular Power Distribution Units  
(Zero-U/1U Modular PDUs)  
QuickSpecs  
ADDITIONAL SPECIFICATIONS  
Low Voltage 24A  
High Voltage 16A  
High Voltage 24A  
High Voltage 32A  
High Voltage 40A  
(NA/JPN/LA)  
(WW)  
252663-B24  
16A  
(NA/JPN/LA)  
(INTL)  
(WW)  
Part Number  
252663-D71  
24A  
252663-D72  
24A  
252663-B31  
32A  
252663-B21  
40A  
Current (max)  
AC Voltage Range  
Frequency (Hertz)  
Load Capacity (VA)  
100-127V  
50/60Hz  
200-240V  
50/60Hz  
200-240V  
50/60Hz  
200-240V  
50/60Hz  
200-240V  
50/60Hz  
2880 (@120V)  
4x15A  
3680 (@230V)  
2X10A  
4992 (@208V)  
4x15A  
7360 (@230V  
4x15A  
9200 (@230V)  
4x15A  
Output Circuit  
Breakers  
Overload Protection  
Indicator Lights  
Yes  
Yes  
Yes  
Yes  
Yes  
Indicator light on each of the Extension Bars; and a main AC pilot light on the Control Unit  
Plugs and Cables  
Control Unit (x1)  
Input: 3.6m attached  
cable with L5-30P  
Input: Detachable  
input power cord  
Input: 3.6m attached  
cable with L6-30P  
Input: 3.6m attached  
cable with IEC309-32A  
Input: Hardwire  
(country specific) with  
a IEC 320-C20 inlet  
Output: Four IEC320-  
C19 (12A ea)  
Output: Four IEC320-  
C19 (12A ea)  
Output: Four IEC320-  
C19 (12A ea)  
Output: Four IEC320-  
C19 (12A ea)  
Output: Two IEC320-  
C19 (8A ea)  
Note: Manual ON/Off control provided for each load group; switch guards provided to prevent inadvertent power Off. The Control unit for the 16A model  
has 2 outputs while the Control Unit for all other Modular PDUs has 4 outputs. The Extension Bars plug directly into the output-ends of the Control  
Unit.  
Extension Bars (x4)* Input: 2m attached  
Input: 2m attached  
Input: 2m attached  
Input: 2m attached  
Input: 2m attached  
cord with IEC320-C20  
cord with IEC320- C20 cord with IEC320- C20 cord with IEC320- C20 cord with IEC320- C20  
*Except for the 16A  
model, which has 2  
Extension Bars  
Output: Each Bar has  
8 NEMA 5-15 outlets  
Output: Each Bar has  
8 C13 outlets  
Output: Each Bar has  
8 C13 outlets  
Output: Each Bar has  
8 C13 outlets  
Output: 3 Bars each  
with 8 C13 (10A max  
per outlet, 12A max  
per Bar); 1 Bar with 4  
C19 (12A max per  
outlet, 12A max per  
Bar)  
(12A max per outlet,  
12A max per Bar)  
(10A max per outlet,  
12A max per Bar)  
(10A max per outlet,  
12A max per Bar)  
(10A max per outlet,  
12A max per Bar)  
DA-11041  
World Wide — Version 3 — December 11, 2002  
 
5
hp Modular Power Distribution Units  
(Zero-U/1U Modular PDUs)  
QuickSpecs  
MODULAR PDU FAMILY INFORMATION  
MODEL SELECTION MATRIX  
Low Voltage 24A  
252663-D71  
High Voltage 16A  
High Voltage 24A  
252663-D72  
High Voltage 32A  
252663-B31  
High Voltage 40A  
252663-B21  
Part Number  
252663-B24  
Input Connection  
(Single Input)  
NEMA L5-30P  
Detachable input power  
cord with a IEC 320-C20  
inlet  
NEMA L6-30P  
IEC 309-32A  
Field Wired Terminal  
Note: The 16A model with  
the detachable cord can be  
used only in applications  
where the total leakage  
current is less than 3.5 mA.  
Output Connections (32) NEMA 5-15R  
Note: The low volt Extension  
(16) IEC 320 C-13  
(32) IEC 320 C-13  
(32) IEC 320 C-13  
(24) IEC 320 C-13  
(4) IEC 320 C-19  
Note: The 16A model ships  
with 2 Extension Bars, while  
all other 24-40A models ship  
with 4 Extension Bars.  
Bars w/5-15 outlets should  
be used ONLY with the low  
volt Control Unit that is  
shipped with the low volt  
Modular PDU unit.  
Applications  
Connects to low voltage Connects to the high  
models of the UPS R3000voltage models of the  
XR (and may also be UPS R3000 XR and  
connected directly into R6000  
Designed to connect  
directly into the facility directly into the facility  
Designed to connect May be hardwired (Note:  
Hardwiring needs to be done  
by a certified on-site  
electrician in accordance with  
the local electrical installation  
codes.) into the facility  
input or to a high voltage  
input  
input  
the facility input)  
Note: Except for the UPS  
R3000 XR, North America  
high volt model, where an  
additional cable option kit,  
PN 340653-001 (IEC320-  
C19 to L6-20P), is needed to  
connect a 16A mPDU to the  
NA high voltage model of the  
UPS R3000 XR  
UPS (R12000 XR)  
Also connects directly into  
the facility input  
Note: You need to purchase  
a cable PN 340653-001  
(IEC320-C19 to L6-20P) for  
North America. Other country  
specific cables are managed  
at the country level.  
DA-11041  
World Wide — Version 3 — December 11, 2002  
 
6
hp Modular Power Distribution Units  
(Zero-U/1U Modular PDUs)  
QuickSpecs  
ADDITIONAL PDU CABLES AVAILABLE  
Product Part Number  
Description  
142257-002  
8 ft/2.5 m, x1  
10A, IEC320 -C14 to IEC 320 -C13 cables for connecting devices to the  
power distribution unit.  
142257-003  
142257-006  
10 ft/3.0 m, x1  
4.5 ft/1.37 m, x1  
142257-007  
201493-001  
4.5 ft/1.37 m, x15  
High Volt, Y-cable for NA/LA, x1  
Remote Insight Lights-Out Edition (RILOE) power Y-cable has been  
designed for plugging into HP PDUs. One single Y-cable supports two  
RILOE cards, which reduces the number of plugs required on the PDU for  
connecting the RILOE cards.  
201493-002  
201493-B21  
201493-B22  
High Volt, Y-cables for NA/LA, x20  
High Volt, Y-cable for INTL, x1  
High Volt, Y-cables for INTL, x20  
Please refer to the Power Cord Matrix for more information on power cords/cable part numbers, input/output descriptions.  
© 2002 Hewlett-Packard Company  
Hewlett-Packard, the Hewlett-Packard logo, CarePaq, ProLiant, and StorageWorks are trademarks of Hewlett-Packard Company in the U.S. and/or other  
countries. All other product names mentioned herein may be trademarks of their respective companies.  
Hewlett-Packard shall not be liable for technical or editorial errors or omissions contained herein. The information is provided "as is" without warranty of any  
kind and is subject to change without notice. The warranties for Hewlett-Packard products are set forth in the express limited warranty statements  
accompanying such products. Nothing herein should be construed as constituting an additional warranty.  
DA-11041  
World Wide — Version 3 — December 11, 2002  
 
7

Grizzly Grinder H8218 User Manual
Haier Ice Maker HPIMD25B User Manual
Harbor Freight Tools Marine Safety Devices 96291 User Manual
Harbor Freight Tools Scale 94569 User Manual
Healthrider Treadmill HRTL19990 User Manual
Hotpoint Double Oven 6180 User Manual
Hotpoint Washer Dryer BWD 129 User Manual
Humax TV Receiver COMBO 9000 User Manual
Ikelite Digital Camera F50fd User Manual
Impex Home Gym WM 348 User Manual