Wireless Communication Card for
TB7200/7300/7600 Series
Communicating Thermostats
INSTALLATION INSTRUCTIONS
APPLICATION
The Honeywell wireless communication card (TB-VWG-APP-1014)
and related WirelessStatNetwork.jar driver file are designed for use
with WEBs-AX controllers to integrate Honeywell TB7200, TB7300,
and TB7600 Series wireless thermostats into a WEBs-AX building
control system. This card allows the integrator to work in the familiar
Workbench tool set using any of the TB7200, TB7300, and TB7600
Series wireless thermostats.
The wireless communication card and TB7200, TB7300, and
®
TB7600 Series thermostats use ZigBee wireless mesh. The
wireless thermostats are ideal for retrofit applications where the
addition of communicating field bus wiring in the building space is
difficult or cost prohibitive.
This document covers the mounting of the wireless communication
card in a WEBs-AX controller.
BEFORE YOU BEGIN
Included in the wireless card package you should find the following items:
•
•
The wireless communication card
A local antenna
A #2 phillips screwdriver is required for installation.
To add the Honeywell wireless thermostat network to a WEBs system, you need two .jar files for the WEBStation-AX.
You can download these files from the Honeywell Buildings Forum at buildingsforum.honeywell.com.
.Jar Files Needed:
•
•
Wireless Thermostat Network Driver: WirelessTstat.jar, version 4.0.4.8 or greater.
Wireless Thermostat Device and Point Configuration: Wireless TstatDevices.jar, version 4.0.4.8 or greater.
More Information
We recommend downloading the Honeywell Wireless Installation and Integration Reference Guide for the TB7200,
installation.
62-2020-03
WIRELESS COMMUNICATION CARD FOR TB7200/7300/7600 SERIES COMMUNICATING THERMOSTATS
STATUS LED INDICATORS
See the table below for status indicators on the wireless communication card.
Table 1. Status LED Indicators
Indicator
Description
1 x 200ms short blink
2 x 200ms short blinks
3 x 200ms short blinks
Power on
Power on and card memory initialized properly
Power on, card memory initialized properly and serial communication with WEBs-AX
controller main board active
4 x 200ms short blinks
Power on, card memory initialized properly, serial communication with WEBs-AX
controller main board active and wireless networks started successfully
4 x 200ms short blinks and Power on, card memory initialized properly, serial communication with WEBs-AX
1 x 1500ms long blink
controller main board active, wireless networks started successfully and wireless
communication with wireless thermostats active
SPECIFICATIONS
Thermostat Compatibility: TB7200, TB7300, and TB7600 Series wireless thermostats
Network Protocol: ZigBee wireless mesh
WEBs-AX Controllers: Compatible with WEB-2xx, WEB-6xx, and WEB-7xx
Platform:
WEB-2xx and WEB-6xx - WEBStation-AX 3.0 or later
WEB-7xx - WEBStation-AX 3.5 or later
Number of Thermostats Supported:
WEB-2xx - up to 30 wireless thermostats
WEB-6xx & WEB-7xx - up to 50 wireless thermostats
NOTE: The maximum number of thermostats supported by a WEBs-AX controller is dependent on resources
available at the controller.
Connections: 2 x 15 gold plated header for serial connection to compatible WEBs-AX controller and SMA connector
for antenna.
Input: Reset button
Status LED: 1 green LED
Board Dimensions: 2.2 in. x 1.75 in. (excluding antenna)
Approximate Shipping Weight: .02 lb
Agency Approvals: Compliant with FFC Part 15, Subpart C; C-Tick: EN55022:2006, IEC 61326-1:2005
3
62-2020—03
WIRELESS COMMUNICATION CARD FOR TB7200/7300/7600 SERIES COMMUNICATING THERMOSTATS
DISCLAIMER
NO WARRANTY. Honeywell, Inc. (herein after referred to as “Honeywell”) makes no warranty as to the accuracy of or
use of this technical documentation. Any use of the technical documentation or the information contained therein is
solely at the risk of the user.
Documentation may include technical or other inaccuracies or typographical errors. Honeywell reserves the right to
make changes to this document without prior notice, and the reader should in all cases consult Honeywell to determine
whether any such changes have been made. The information in this publication does not represent a commitment on
the part of Honeywell.
Honeywell shall not be liable for incidental or consequential damages resulting from the furnishing, performance, or use
of this material.
Electronic controls are static sensitive devices. Discharge yourself properly before manipulation and installing the
Honeywell wireless gateway.
Honeywell, Inc. may not be held liable for continued reliable, or robust operation of any and all wireless based devices.
Although Honeywell has taken many precautions in assuring the robustness of the TB7200/7300/7600 Series wireless
thermostat product line and associated network access point. Please note; future application of additional wireless
devices utilizing the same or similar channels and / or frequencies may degrade performance of overall system and / or
reliability.
Non-approved modifications or changes made to the wireless communication card or wireless thermostats may void the
FCC compliance of the and wireless thermostats.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device
may not cause harmful interference, and (2) This device must accept any interference received, including interference
that may cause undesired operation.
NOTE: The manufacturer is not responsible for any radio or tv interference caused by unauthorized modifica-
tions to this equipment. Such modifications could void the user’s authority to operate the equipment.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
® U.S. Registered Trademark
© 2011 Honeywell International Inc.
62-2020—03 M.S. Rev. 09-11
Golden Valley, MN 55422
Printed in United States
customer.honeywell.com
|