hussman Network Router P N 374511B User Manual

P/N 374511B  
March, 1997  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 1  
KEY PAD INSTRUCTIONS  
Shift Upper – This key is used to key in the top  
(red) letters.  
Shift Lower – This key is used to key in the  
bottom (blue) letters.  
NOTE: If either of the above keys is pressed  
accidentally, simply press it again to deactivate  
it.  
INS & DEL – The screen will prompt you  
when you need to use these keys.  
CLR – Clears last entry  
Help – There are no help screens on the current  
software.  
ESC – Escape; returns you to the previous  
menu.  
ENT – Enter; you will be prompted as to when  
to use this key.  
Space – enters a space between letters.  
Arrows – These keys move the cursor in the  
direction shown. The Right Arrow key is also  
used to toggle between functions such as  
enable/disable and press/temp.  
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
P/N 374511B  
Page 2  
Hand Held Device  
PROTOCOL  
The Hussmann Interface Module may be operated  
from either battery power or from a 120V/12VDC  
transformer. When using the transformer, connect  
Module before plugging in the transformer. The  
startup screen will automatically appear.  
HUSSMANN  
INTERFACE MODULE  
(C) 1991 HUSSMANN  
CORPORATION  
VER 1.30  
When battery operated, the Module will shut down  
if the key pad has not been used for three minutes.  
When a transformer is used, the hand held module  
will beep and remain on.  
If the battery is too weak to function, the menu  
screen will become faint or not come up at all. If  
the battery is completely without power, the han
held module will beep and show an alar
message. There is also a Low Battery mess
that appears at the Main Menu for Protocol™
Regardless of the power source, if Protoc
not communicating with the hand held m
beep will sound and a COMM ERROR me
appear. If the Protocol™ system is with
the hand held module will beep a
ALARM message.  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
970307  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 3  
Following the startup screen, the  
SELECT EQUIPMENT screen will appear.  
SELECT EQUIPMENT  
SELECT EQUIPMENT  
1-PROTOCOL  
1-PROTOCOL  
2-CASE CONTROL  
3-PUMPING STATION  
4-FLUID COOLER  
2-CASE CONTROL  
3-PUMPING STATION  
4-FLUID COOLER  
Press 1 on the key pad.  
The PROTOCOL™ MAIN MENU will appear. This  
screen has 5 submenus each of which has its own  
submenu(s), see page 4.  
PROTOCOL MAIN MENU  
Any time a numbered list appears on the menu  
screen, pressing the key pad number will take you  
to that submenu or function.  
1-STATUS MENU  
2-CONFIG MENU  
3-DEFROST MENU  
4-MAINT MENU  
5-ALARM MENU  
Notes:  
1) If Case Control is accidentally selected, the  
only way to escape is to disconnect power to the  
Interface Module.  
LOW BATTERY  
2) Neither Pumping Station nor Fluid Cooler  
information is contained in this manual.  
3) LOW BATTERY appears only if battery voltage  
is below normal levels  
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
P/N 374511B  
Page 4  
Hand Held Device  
PROTOCOL  
PROTOCOL MAIN MENU  
(_ _) = PAGE NUMBERFORMORE INFORMATION  
1- STATUS MENU (07)  
2- CONFIG MENU (10)  
3- DEFROST MENU (23)  
4- MAINT MENU (28)  
5- ALARM MENU (30)  
MAIN STATUS MENU  
1-PRESSURES (07)  
2-DEFROST / TEMPCKT (08)  
3-TEMPERATURE MENU (09)  
4-COMP RUN METERS (09)  
CONFIG MENU  
DEFROST MENU  
MAINT MENU  
1-SET THE CLOCK (10)  
2-SENSOR SETUP (11)  
3-PROTOCOLSETUP(15)  
4-COMM SETUP (20)  
5-LIGHTCONTROL(21)  
6-TEMPCONTROL(22)  
1-VIEW/SET ITEMS (23)  
2-COPY SCHEDULE (25)  
3-ASSIGN OUTPUTS (26)  
*4-ASSIGN CIRCUITS  
FOR SPLIT SUCT(27)  
1-FORCE A COMP ON  
2-CLEAR FORCE FLAG  
3-FORCE A COMP OFF  
4-FORCE A DEFR ON  
5-FORCE A DEFR OFF  
PRESS ENT FOR MORE  
6-CLEAR RUN METER  
7-FORCE LIGHT ON  
ALARM MENU  
PRESSURE STATUS  
P1 P2  
A01- LO SUCTION PRESS  
TIME 01:56 01/21  
END OF ALARMS  
SUCTION  
SETPOINT  
42  
40  
0
0
#COMPS - 1 2 3 4 5 6  
ON (X) X X X X  
*This item only appears when unit is configured  
for split suction option.  
8-FORCE LIGHT OFF  
**9-CLEAR ALM TABLE  
**0-RESETCONTROL  
TEMPERATURE STATUS  
(F)  
SP  
0
0
T1  
T2  
T3  
-40  
-40  
-40  
0
**These options only available with Software Version 2.30 or greater.  
Protocol Control must also be V1.30 or greater  
PRESS ENT FOR MORE  
TEMPERATURE STATUS (CONT)  
(F)  
0
0
0
0
SP  
0
0
0
0
T4  
T5  
T6  
T7  
T8  
TEMP / CIRCUIT #1  
NAME – CIRCUIT #1 NAME  
0
0
STATUS  
REFR  
TEMPCTRL – ENABLED  
AUXILIARY STATUS (EXPANDED)  
(F)  
AUX #1 22  
REFRIG: ON  
SETPT  
20  
REF 18  
A7 -  
A8 -  
A9 -  
A10 -  
A11 -  
A12 -  
0
0
0
0
0
0
COMPRESSOR RUN METER  
COMP1  
COMP2  
COMP3  
COMP4  
COMP5  
COMP6  
56  
57  
56  
53  
0
HOURS  
HOURS  
HOURS  
HOURS  
HOURS  
HOURS  
0
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
970307  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 5  
CONFIG MENU  
(_ _) = PAGENUMBER FORMORE INFORMATION  
1- SET THE CLOCK (10)  
2- SENSOR SETUP (11)  
3- PROTOCOLSETUP(15)  
4- COMM SETUP (20)  
5- LIGHT CONTROL(21)  
6-TEMPCONTROL(22)  
CLOCK SETUP MENU  
SENSOR SETUP MENU  
PROTOCOLSETUPMENU  
TIME  
DATE  
YEAR  
-
-
-
22:23  
02:23  
96  
COMM SETUP MENU  
1-PRESSURE # 1 (11)  
2-PRESSURE #2 (12)  
3-TEMP # 1 (13)  
4-TEMP # 2 (13)  
5-TEMP # 3 (13)  
1-REFR SETUP (15)  
2-DEFR SETUP (18)  
3-DESCRIPTION (19)  
4-ALARM OUTPUT (19)  
STATION NUMBER - 99  
DAYLIGHT-  
SPRING -  
ENABLED  
02:00 04/27  
02:00 10/28  
BAUD RATE  
- 19200  
FALL  
-
TEMPERATURE CONTROL  
1-REFR CIRCUIT #1 (22)  
2-REFR CIRCUIT #2 (22)  
3-REFR CIRCUIT #3 (22)  
4-REFR CIRCUIT #4 (22)  
5-REFR CIRCUIT #5 (22)  
6-REFR CIRCUIT #6 (22)  
7-REFR CIRCUIT #7 (22)  
8-REFR CIRCUIT #8 (22)  
1-TEMP # 4 (13)  
2-TEMP # 5 (13)  
3-TEMP # 6 (13)  
4-TEMP # 7 (13)  
5-TEMP # 8 (13)  
6-AUX SENSORS (14)  
LIGHT MENU  
1-CIRCUIT #1 (21)  
2-CIRCUIT #2 (21)  
ALARM OUTPUT  
OUTPUT NUMBER - X  
LIGHT CIRCUIT #1  
STATUS  
STATUS  
NAME  
-
-
-
-
ENABLED  
ENABLED  
CASE LTS  
04:00  
DESCRIPTION  
NAME – PROTOCOLNAME  
CONFIG - REFRIGERATION  
COMPS (TOTAL)  
REFR CIRCUIT #1  
ON TIME  
-
4
TEMPCNTL - ENABLED  
OFF TIME - 22:00  
OUTPUT 08  
CYCLING - ROUND ROBIN  
SUCTION SP - 15 PSI  
SPLIT SUCTION - DISABLED  
SETPOINT  
RATE  
- 15 F  
3 F  
-
-
OUTPUTRELAY - 1  
CONFIG DEFROST  
# OF CIRCUITS - 3  
# COMPRS  
SPLITSP  
-
-
0
0 PSI  
INTERLOCK - DISABLED  
DRIP CYCLE - 0  
SAT CONTROL  
SAT SETPT  
SAT DIFF  
CONTROL  
SPR CONTROL  
SPR SP  
-
-
-
-
-
-
DISABLED  
0 F  
0 F  
TEMP  
DISABLED  
0 F  
MIXMATCH SETUP  
COMPRESSORS  
STEP  
1
2
0
X
X
X
3
0
0
X
X
4
0
0
0
X
1
2
3
4
-
-
-
-
01 =  
03 =  
06 =  
14 =  
X
X
0
0
:
:
16 -  
00 =  
0
0
0
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
P/N 374511B  
Page 6  
Hand Held Device  
PROTOCOL  
DEFROST MENU  
(_ _) = PAGENUMBER FORMOREINFORMATION  
1- VIEW/SET ITEMS (23)  
2- COPY SCHEDULE (25)  
3- ASSIGN OUTPUTS (26)  
*4-ASSIGN CIRCUITS  
DEFROST MENU  
DEFROST CIRCUIT #X  
DEFROST BOARD #1  
CIRCUIT  
NAME  
STATUS  
TYPE  
OFTIM  
03  
OUTPUT  
CIRCUIT  
1
2
3
4
5
6
7
8
CIRCUIT #1 NAME DEFR  
CIRCUIT #2 NAME REFR  
CIRCUIT #3 NAME DATV  
CIRCUIT #4 NAME N/A  
CIRCUIT #5 NAME N/A  
CIRCUIT #6 NAME N/A  
CIRCUIT #7 NAME N/A  
CIRCUIT #8 NAME N/A  
NUMBER  
LENGTH  
START  
FOR SPLIT SUCT(27)  
1
2
3
4
1
2
3
4
15  
00:00  
00  
SUCTION ASSIGNMENT (27)  
AMPERAGE  
CIRCUIT  
SUCTION  
1
2
3
4
5
6
7
8
01  
01  
01  
01  
01  
01  
01  
01  
DEFR TERM ENABLED  
DEFROST BOARD #2  
2ND DEFR  
3RD DEFR  
08:15  
16:00  
OUTPUT  
CIRCUIT  
5
6
7
8
5
6
7
8
COPY DEFROST SCHEDULE  
EXPANSION BOARD  
OUTPUT CIRCUIT  
COPY FROM CIRCUIT - 00  
COPY TO CIRCUIT - -  
9
00  
00  
00  
00  
10  
11  
12  
EXPANSION BOARD  
OUTPUT CIRCUIT  
13 00  
DEFROST BOARD #3  
DEFROST BOARD #4  
OUTPUT CIRCUIT  
21 00  
OUTPUT  
CIRCUIT  
17  
18  
19  
20  
00  
00  
00  
00  
14  
15  
16  
00  
00  
00  
22  
23  
24  
00  
00  
00  
*This item only appears when unit is configured for split suction option.  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
970307  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 7  
STATUS MENU  
1-STATUS MENU  
PROTOCOL MAIN MENU  
This is a read only menu. It gives you current  
operating conditions.  
1-STATUS MENU  
2-CONFIG MENU  
3-DEFROST MENU  
4-MAINT MENU  
P1 gives the present pressure for the suction man-  
ifold.  
5-ALARM MENU  
P2 gives the second suction pressure input.*  
Press ESC Key.  
STATUS MENU  
SETPOINT is the Suction Set Point for the control  
board. The board turns compressors ON and OFF  
to maintain this suction pressure.  
1-PRESSURES  
2-DEFROST / TEMP CKT  
3-TEMPERATURES  
# COMPS - 1  
ON(X)  
lists the compressor numbers, and indicates  
which are running.  
2
X
3
4
X
4-COMPR RUN METER  
Note: Compressors are configured as follows:  
Horizontal Protocols  
PRESSURE STATUS  
1
2
3
4
5
6
P1 P2  
SUCTION  
SETPOINT  
0
0
0
0
Vertical Protocols  
2
4
3
6
5
# COMPS - 1 2 3 4  
ON(X)  
X X  
PRESS ENT FOR MORE  
1
*When Split Suction is installed or when Satellite  
compressor is controlled by pressure, P2 can also  
be used to monitor high side discharge pressures.  
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
P/N 374511B  
Page 8  
Hand Held Device  
PROTOCOL  
STATUS MENU (Continued)  
2-DEFROST / TEMP CKT  
This is a read-only menu. This screen shows the  
current operational status of Defrost Circuits and  
associated temperatures as provided by Auxiliary  
inputs.  
STATUS MENU  
1-PRESSURES  
2-DEFROST / TEMP CKT  
3-TEMPERATURES  
4-COMPR RUN METER  
NAME gives a description of the case loads for this  
defrost circuit.  
STATUS indicates whether the defrost circuit is in  
defrost (DEFR), refrigeration (REFR), or a  
Manually Forced condition (F-DEFR, F-REFR).  
TEMP CIRCUIT #1  
NAME  
CIRCUIT #1 NAME  
TEMP-CTRL indicates whether temperature control  
is available for this circuit. This control feature  
allows the refrigeration solenoid to be operated ON  
and OFF to maintain a temperature setpoint.  
STATUS  
REFR  
ENABLED  
SETPOINT  
20  
TEMP CTRL  
(F)  
22  
AUX #1  
AUX #X provides the actual temperature reading  
of the circuit. Note that X will be a number  
between 1 and 8 depending upon the Temp/Circuit  
number you are currently accessing.  
REFRG – ON  
REF 7  
REFRIG is the status of the defrost/refrigeration  
relay. ON indicates that power is being fed to the  
solenoid. OFF indicates that the solenoid is de-  
energized.  
REF is an internal setpoint used by the Temp  
Control algorithm. This number will increase up /  
decrease down dependent upon the relationship of  
the temperature reading (AUX #) and the circuit  
setpoint.  
Press ENT to view additional circuit information.  
Note: Temperature Control is available on Hand  
Held Devices V2.40 or greater.  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
970307  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 9  
STATUS MENU (Continued)  
3-TEMPERATURE MENU  
TEMPERATURE MENU  
T1 temperature reading for suction pressure reset  
or optional temperature input.  
F
- 40  
- 40  
- 40  
SP  
0
T1 -  
T2 -  
T3 -  
0
T2 temperature reading for satellite or optional  
temperature input.  
0
PRESS ENT FOR MORE  
T3 If split suction is installed, T3 may be factory  
set to read head pressure instead of temperature.  
Screen will show T3- ___PSI.  
TEMPERATURE MENU  
If split suction is not installed, T3 is a designated  
temperature input; but if you prefer, it can be con-  
figured as a pressure input (See page12).  
F
0
0
0
0
0
SP  
0
T4 -  
T5 -  
T6 -  
T7 -  
T8  
0
Press ESC Key.  
0
0
A7 thru A12 are additional temperature inputs.  
These readings may be established by the user as  
either ANALOG or DIGITAL under the CONFIGU-  
RATION MENU. When set on DIGITAL the read  
out will be either OPEN or CLOSED. The digital  
setting is applicable to thermostats or auxiliary  
contactors.  
0
PRESS ENT FOR MORE  
AUXILIARY MENU  
A7 -  
OPEN  
CLOSED  
OPEN  
- 40  
When the ANALOG setting is used a thermistor is  
used to retrieve temperature readings between – 40  
and + 120˚F.  
A8 -  
A9 -  
A10 -  
A11 -  
A12 -  
60  
When not used the menu will read OPEN if set on  
DIGITAL. Set on ANALOG, an unused input will  
produce a – 40.  
- 40  
Press ESC Key.  
COMPRESSOR RUN METER  
4-COMPRESSOR RUN METER  
COMP1  
COMP2  
COMP3  
COMP4  
COMP5  
COMP6  
56  
57  
56  
55  
0
HOURS  
HOURS  
HOURS  
HOURS  
HOURS  
HOURS  
COMPRESSOR RUN METER submenu appears.  
This menu shows the total number of hours that  
each compressor has been operating.  
Press ESC to return to STATUS MENU.  
0
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
P/N 374511B  
Page 10  
Hand Held Device  
PROTOCOL  
CONFIG MENU  
2-CONFIG MENU  
PROTOCOL MAIN MENU  
1-STATUS MENU  
2-CONFIG MENU  
3-DEFROST MENU  
4-MAINT MENU  
This set of menus is used to make changes in the  
Protocol’s configuration. Press 2 on the Keypad  
to enter the CONFIG submenu.  
5-ALARM MENU  
1- SET THE CLOCK  
Press 1 on the Keypad to enter the CLOCK SETUP  
submenu. This screen has 5 fields used to set the  
correct time/date.  
CONFIG MENU  
1-SET THE CLOCK  
2-SENSOR SETUP  
3-PROTOCOL SETUP  
4-COMM SETUP  
Hour  
(24-hr clock only)  
22  
Minute  
23  
01  
02  
96  
5-LIGHT CONTROL  
6-TEMP CONTROL  
Month date  
Day date  
Year date  
(Last two digits only)  
The screen appears with the cursor indicating the  
hour field.  
CLOCK SETUP MENU  
22  
TIME  
22: 23  
CURSOR  
DATE  
01/ 02  
YEAR  
96  
Press the CLR button. This will change the field  
to 00. Then input the correct hour and press ENT.  
The cursor will move to the next field. Repeat the  
process through each field.  
DAYLIGHT  
SPRING  
FALL  
ENABLED  
02:00 04/28  
02:00 10/27  
Press ESC to return to the CONFIG MENU.  
When enabled, the DAYLIGHT function will auto-  
matically adjust the time and year (in case of leap  
years) corresponding to changes in TIME and DATE.  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
970307  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 11  
CONFIG MENU (continued)  
CONFIG MENU  
2- SENSOR SETUP  
1-SET THE CLOCK  
2-SENSOR SETUP  
3-PROTOCOL SETUP  
4-COMM SETUP  
Press 2 on the Keypad to enter the Sensor Setup  
Submenu. This screen has 6 menus.  
1- PRESSURE #1  
5-LIGHT CONTROL  
6-TEMP CONTROL  
Press 1 on the Keypad to enter the Pressure #1  
Submenu.  
SENSOR SETUP MENU  
PRESSURE #1 controls the suction pressure for  
the Protocol Control. Press the CLR key. Key in  
the applicable suction pressure in psig for HI  
ALARM and press ENT. Repeat for LO ALARM.  
1-PRESSURE #1  
2-PRESSURE #2  
3-TEMP #1  
Pressure Transducers are supplied in one of three  
ranges:  
4-TEMP #2  
5-TEMP #3  
0 to 100  
0 to 200  
0 to 500  
PRESSURE #1  
Using the  
key, toggle to the range of the trans-  
ducer used. Press ENT.  
HI ALARM  
LO ALARM  
40 PSI  
20 PSI  
Offset allows manual calibration for the pressure  
transducer. Manual calibration is achieved by  
entering a number between -5 and +5. This number  
will then be used to offset the pressure reading by  
the entered amount.  
XDCR RANGE  
OFFSET  
- 100 PSI  
PSI  
0
WARNING: Improper calibration of the  
transducer could lead to unpredictable  
operation of the control. Verify the accu-  
racy of the transducer reading with a  
minimum of two gauges.  
Note: Manual calibration is available on Hand  
Held version V2.40 or greater.  
Press ESC to return to SENSOR SETUP MENU.  
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
P/N 374511B  
Page 12  
Hand Held Device  
PROTOCOL  
CONFIG MENU (continued)  
2- PRESSURE #2  
SENSOR SETUP MENU  
Press 2 on the Keypad to enter the Pressure #2  
Submenu.  
1-PRESSURE #1  
2-PRESSURE #2  
3-TEMP #1  
PRESSURE #2 controls the suction pressure or  
Split Suction on the Protocol Control. Press the  
CLR key. Key in the applicable suction pres-  
sure in psig for HI ALARM and press ENT.  
Repeat for LO ALARM.  
4-TEMP #2  
5-TEMP #3  
Pressure Transducers are supplied in one of three  
ranges:  
PRESSURE #2  
0 to 100  
0 to 200  
0 to 500  
HI ALARM  
LO ALARM  
XDCR RANGE  
ALARM  
0
0
PSI  
PSI  
- 100 PSI  
ENABLED  
Using the  
key, toggle to the range of the trans-  
ducer used. Press ENT.  
OFFSET  
0
PSI  
Using the  
key, move down to the Alarm status  
selection. Using the  
DISABLED. Press ENT.  
key, toggle ENABLED or  
Offset allows manual calibration for the pressure  
transducer. Manual calibration is achieved by  
entering a number between -5 and +5. This number  
will then be used to offset the pressure reading by  
the entered amount.  
WARNING: Improper calibration of the  
transducer could lead to unpredictable  
operation of the control. Verify the accu-  
racy of the transducer reading with a  
minimum of two gauges.  
Note: Manual calibration is available on Hand  
Held version V2.40 or greater.  
Press ESC to return to SENSOR SETUP MENU.  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
970307  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 13  
CONFIG MENU (continued)  
3- TEMP #1  
SENSOR SETUP MENU  
3-TEMP #1 allows you to establish set point  
and alarm levels for the first temperature  
input.  
1-PRESSURE #1  
2-PRESSURE #2  
3-TEMP #1  
Press 3 on the Keypad to enter the TEMP #1  
Submenu.  
4-TEMP #2  
5-TEMP #3  
The ALM DELAY is a programmable time delay.  
This sets the time it will take before the control  
log’s the alarm.  
TEMPERATURE # 1  
The CIRCUIT - X allows you to attach a defrost  
circuit to the temperature input (or vice versa).  
When the circuit is in defrost, the HI ALARM will be  
ignored.  
SET PT  
-
-
-
-
-
XX F  
XX F  
HI ALARM  
LO ALARM  
ALARM  
3
4
5
XX F  
ENABLE  
30 MIN  
X
Press CLR.  
press ENT.  
Key in your selection and  
ALM DELAY  
CIRCUIT  
-
Using the  
key, toggle ENABLED or DISABLED.  
Press ENT.  
TEMPERATURE # 2  
Press ESC to return to SENSOR SETUP MENU.  
SET PT  
-
-
-
-
-
XX F  
4- TEMP #2  
HI ALARM  
LO ALARM  
ALARM  
XX F  
XX F  
Press 4 on the Keypad to enter the TEMP #2  
Submenu. Follow instructions above.  
ENABLE  
30 MIN  
X
ALM DELAY  
CIRCUIT  
5- TEMP #3  
-
Press 5 on the Keypad to enter the TEMP #3  
Submenu.  
TEMPERATURE # 3  
INPUT MODE TEMP  
If split suction is installed, TEMP #3 may be  
factory set to read head pressure instead of  
temperature. This is accomplished by changing  
the input mode to Pressure.  
-
SET PT  
-
XX F  
XX F  
HI ALARM  
LO ALARM  
ALARM  
-
-
-
-
XX F  
If split suction is not installed, TEMP #3 is a  
designated temperature input; but if you prefer it  
can be factory set as a pressure input.  
ENABLE  
30 MIN  
X
ALM DELAY  
CIRCUIT  
-
Using the  
ENT.  
key, toggle TEMP or PRESS. Press  
Note: When using T3 for a pressure reading,  
remember to place the hardware switch on the  
main control board in the pressure position.  
Press ESC to return to SENSOR SETUP MENU.  
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
P/N 374511B  
Page 14  
Hand Held Device  
PROTOCOL  
CONFIG MENU (continued)  
SENSOR SETUP MENU  
1-TEMP #4  
6- AUX SENSORS  
2-TEMP #5  
3-TEMP #6  
Press 6 on the Keypad to enter the Auxiliary  
Sensors Submenu.  
4-TEMP #7  
5-TEMP #8  
6-AUX SENSORS  
AUXILIARY SENSORS provide six temperature  
inputs—analog or digital.  
AUXILIARY SENSORS  
Analog for thermistors  
Digital for thermostats.  
1-AUX SENSOR #1  
2-AUX SENSOR #2  
3-AUX SENSOR #3  
4-AUX SENSOR #4  
5-AUX SENSOR #5  
6-AUX SENSOR #6  
MORE ON NEXT PAGE  
ANALOG SETTING  
ANALOG accommodates temperature readings  
between – 40 and + 120˚F. Set on ANALOG, an  
unused input will produce a – 40.  
DIGITALSETTING  
When set on DIGITAL the read out will be either  
OPEN (not in use) or CLOSED.  
AUXILIARY SENSORS  
1-AUX SENSOR #7  
2-AUX SENSOR #8  
3-AUX SENSOR #9  
4-AUX SENSOR #10  
5-AUX SENSOR #11  
6-AUX SENSOR #12  
Use the  
DIGITAL.  
key to toggle between ANALOG and  
Using the ENT key, move down the selections.  
Press CLR. Key in your selection and press ENT.  
The cursor will move down to the next sensor.  
AUX SENSOR #1  
Press ESC to return to AUXILIARY SENSORS MENU.  
Press ESC again to return to SENSOR SETUP MENU.  
Press ESC again to return to CONFIG MENU.  
MODE  
DIGITAL  
NAME –  
TERM. SP  
HI ALARM  
LO ALARM  
ALARM  
CLOSED  
0
F
F
-40  
ENABLED  
Note: Aux Sensors 7 through 12 are available  
only on Expansion Module.  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
970307  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 15  
CONFIG MENU (continued)  
CONFIG MENU  
3- PROTOCOL SETUP  
Press 3 on the Keypad to enter the Protocol Setup  
Submenu.  
1-SET THE CLOCK  
2-SENSOR SETUP  
3-PROTOCOL SETUP  
4-COMM SETUP  
1- REFR SETUP  
Press 1 on the Keypad to enter the REFR SETUP  
submenu.  
5-LIGHT CONTROL  
6-TEMP CONTROL  
This screen programs the Control Board for the  
refrigeration parameters:  
PROTOCOL SETUP  
Number of compressors controlled  
Compressor Cycling Algorithm*  
Suction Pressure Set Point  
Split Suction Control—  
ENABLED/DISABLED  
Number of compressors controlled  
Split Suction Reset Set Point  
1-REFR SETUP  
2-DEFR SETUP  
3-DESCRIPTION  
4-ALARM OUTPUT  
To change numeric fields, press the CLR key.  
Key in the applicable number. Press ENT. Use  
the  
Press ENT.  
key, toggle between ENABLED/DISABLED.  
CONFIG-REFRIGERATION  
COMPS (TOTAL)  
CYCLING  
4
Use the down arrow to get to the next screen  
which programs the satellite and Suction Pressure  
Reset controls.  
ROUND ROBIN  
30 PSI  
– ENABLED  
SUCTION SP  
SPLIT SUCT  
# COMPRS  
SPLIT SP  
Satellite Control — ENABLED/DISABLED  
Satellite Set Point  
Satellite Differential  
0
0
PSI  
Sat. Control Status — TEMP/PRESS**  
**When configured for pressure, the P2 input  
serves as the connection point for the transducer.  
Suction Pressure Reset status —  
ENABLED/DISABLED  
NOTE:  
COMPS(TOTAL) is the total number of compressors on the  
Protocol units  
# COMPRS is the number of compressors (total) assigned to  
Suction Pressure Reset Set Point  
split suction  
To change numeric fields, press the CLR key.  
Key in the applicable number. Press ENT. Use  
CONFIG-REFRIGERATION  
SAT CONTROL – DISABLED  
the  
key, toggle between ENABLED/DISABLED  
SAT SETPT  
SAT DIFF  
0
F
F
and TEMP/PRESS. Press ENT.  
0
CONTROL  
TEMP  
Press ESC to return to enter the MixMatch Setup.  
SPR CONTROL  
SPR SP  
DISABLED  
Press ESC again to return to PROTOCOL SETUP  
MENU.  
0
F
*Algorithm options are Round Robin or MixMatch.  
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
P/N 374511B  
Page 16  
Hand Held Device  
PROTOCOL  
CONFIG MENU (continued)  
MixMatch compressor cycling is used when com-  
pressors of varying horsepowers have been  
installed. This algorithm allows the compressor  
horse power to be more closely matched with the  
evaporator load  
MIXMATCH SETUP  
COMPRSSORS  
SETUP  
1
X
0
0
0
2
0
X
0
0
3
0
0
X
0
4
0
0
0
X
1
2
3
4
01  
02  
03  
04  
There are 16 available steps for MixMatch  
cycling. The additional steps are accessible by  
pressing the  
arrow to view additional screens.  
Each step can be programmed by entering anum-  
ber between 1 and 63 of the step number. The  
Hand Held Device will use this number to display  
the compressors selected with an ‘X’and those not  
selected with a ‘0.’  
The number entered and used by the Hand Held  
Device is a binary number. The following example  
describes the relationship of the number to com-  
pressors. Causion: If you have concerns over this  
programming, consult Bridgeton Refrigeration  
Engineering.  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
970307  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 17  
CONFIG MENU (continued)  
MIXMATCH PROGRAMMING EXAMPLE  
1. Start by making a column for each compressor. A programming worksheet is available at the back  
2. The first row must be all 0’s.  
of this manual.  
3. Each row will be a step. Each step should  
increase rack capacity by the smallest increase in  
capacity possible.  
Any unused steps must have a zero inserted for the  
4. Use an X in the column for a compressor being numbers to prevent unwanted compressors from  
on, and a 0 in the column for a compressor being  
off. It may help to write the capacity in horsepower  
to the right of each row.  
running.  
5. For each row, add the value of each column  
with an X in it and put it on the right of each row.  
These are the numbers you enter in for each step.  
6. Adjust the X’s and the 0’x for equal runtime on  
each compressor.  
Mixmatch Programming Worksheet  
Compr #  
1
4
1
2
4
2
3
5
4
4
6
8
5
6
Total  
HP  
Total  
HP  
0
Column  
Column Value  
16  
32  
Value  
0
1
2
X
X
4
1
3
X
5
4
4
X
6
8
5
X
X
X
8
3
6
X
X
9
6
7
10  
11  
14  
15  
19  
10  
12  
11  
13  
14  
0
8
X
X
X
X
9
X
X
X
X
X
10  
11  
12  
13  
14  
15  
16  
X
X
0
0
0
0
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
P/N 374511B  
Page 18  
Hand Held Device  
PROTOCOL  
CONFIG MENU (continued)  
2- DEFR SETUP  
PROTOCOL SETUP  
Press 2 on the Keypad to enter the Defrost Setup  
Submenu.  
1-REFR SETUP  
2-DEFR SETUP  
3-DESCRIPTION  
4-ALARM OUTPUT  
This screen programs the Control Board for the  
defrost parameters:  
Number of defrost circuits controlled  
Interlock status—  
ENABLED/DISABLED  
To change numeric fields, press the CLR key.  
Key in the applicable number. Press ENT. Use  
CONFIG - DEFROST  
the  
Press ENT.  
key, toggle between ENABLED/DISABLED.  
# OF CIRCUITS  
INTERLOCK  
7
– DISABLED  
DRIP CYCLE  
0
Press ESC to return to PROTOCOL SETUP MENU.  
*
Interlock is used when there is only one defrost  
circuit programmed into the control. If that one  
defrost circuit is electric, all compressors will turn  
on during the duration of the defrost. If the single  
defrost circuit is gas, the reverse cycle algorithm  
will be activated.  
* This drip cycle is only used for reverse cycle gas  
defrost units.  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
970307  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 19  
CONFIG MENU (continued)  
PROTOCOL SETUP  
3- DESCRIPTION  
1-REFR SETUP  
2-DEFR SETUP  
3-DESCRIPTION  
4-ALARM OUTPUT  
Press 3 on the Keypad to enter the Description  
Submenu.  
This screen provides for a 16 character description  
of the Protocol unit for user identification on  
Hussnet™.  
Press the CLR key.  
Key in the description . Press Shift Upper to use  
the red (upper) letters and Shift Lower to use the  
blue (lower) letters.  
CONFIG - DESCRIPTION  
NAME -  
Press ENT.  
Press ESC to return to PROTOCOL SETUP MENU.  
Press ESC again to return to CONFIG MENU.  
4- ALARM OUTPUT  
PROTOCOL SETUP  
Press 4 on the Keypad to enter the Alarm Output  
Submenu.  
1-REFR SETUP  
2-DEFR SETUP  
3-DESCRIPTION  
4-ALARM OUTPUT  
The alarm output feature allows one of the 24  
available outputs to be energized during the  
occurance of any alarm (High/Low Pressure,  
High/Low Temp, etc.)  
The output number refers to a relay which is wired  
into the main Protocol Alarm Relay (AR).  
Key in the number (between 1 and 24). Make sure  
that the output is available and not being used by  
another function (defrost, lighting or temperature  
control).  
ALARM OUTPUT  
OUTPUT NUMBER – X  
Press ENT.  
Press ESC to return to PROTOCOL SETUP MENU.  
Press ESC again to return to CONFIG MENU.  
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
P/N 374511B  
Page 20  
Hand Held Device  
PROTOCOL  
CONFIG MENU (continued)  
CONFIG MENU  
1-SET THE CLOCK  
2-SENSOR SETUP  
3-PROTOCOL SETUP  
4-COMM SETUP  
4- COMM SETUP  
Press 4 on the Keypad to enter the Communication  
Setup Submenu.  
5-LIGHT CONTROL  
6-TEMP CONTROL  
This screen provides for assigning each Protocol a  
station number for computer identification on  
Hussnet™. It also provides baud rate assignment.  
The baud rate is the rate at which a computer can  
receive data from Protocol. All Protocols must  
have the same baud rate in order to communicate.  
A baud rate of 19200 is suggested.  
COMM SETUP MENU  
STATION NUMBER – 00  
BAUD RATE 19200  
Press the CLR key. Key in the number. Press  
ENT.  
Press ESC to return to CONFIG MENU.  
Note: All baud rates will be the same for all  
Protocols in a given store. However, the station  
numbers must be different.  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
970307  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 21  
CONFIG MENU (continued)  
CONFIG MENU  
5- LIGHT CONTROL  
1-SET THE CLOCK  
2-SENSOR SETUP  
3-PROTOCOL SETUP  
4-COMM SETUP  
Press 5 on the Keypad to enter the Light Control  
Submenu.  
1-CIRCUIT #1  
5-LIGHT CONTROL  
6-TEMP CONTROL  
Press 1 or 2 on the Keypad to enter the Circuit #  
Submenu.  
This screen programs lighting controls on one cir-  
cuit.  
LIGHT MENU  
1-CIRCUIT #1  
2-CIRCUIT #2  
Use the  
key to toggle between ENABLED /  
DISABLED to activate the lighting function. Press  
ENT.  
Using the ENT key, move down the selections.  
Press CLR. Key in your selection and press ENT.  
The cursor will move down to the next sensor.  
LIGHT CIRCUIT #1  
NAME identifies the lights on this circuit.  
ONTIME controls when the lights turn on.  
OFFTIME controls when the lights turn off.  
STATUS  
ENABLED  
CASE LTS  
04:00  
NAME  
ONTIME  
OFFTIME –- 22:00  
OUTPUT –- 08  
OUTPUT controls the relay used by these  
PowerLinks™ (lighting circuit breakers).  
Press ESC to return to LIGHT MENU.  
Press ESC again to return to CONFIG MENU.  
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
P/N 374511B  
Page 22  
Hand Held Device  
PROTOCOL  
CONFIG MENU (continued)  
CONFIG MENU  
6- TEMPERATURE CONTROL  
1-SET THE CLOCK  
2-SENSOR SETUP  
3-PROTOCOL SETUP  
4-COMM SETUP  
Press 6 on the Keypad to enter the Temperature  
Control Submenu.  
Note: Temperature Control is available on HAND  
HELD DEVICE V2.40 or greater.  
5-LIGHT CONTROL  
6-TEMP CONTROL  
Press the number of the Temp Refr Circuit you  
wish to view or use the  
and  
to move to the  
appropriate entry and press ENT.  
TEMPERATURE CONTROL  
1-REFR CIRCUIT #1  
1-REFR CIRCUIT #1  
2-REFR CIRCUIT #2  
3-REFR CIRCUIT #3  
4-REFR CIRCUIT #4  
This screen allows configuration for temperature  
control of a given circuit.  
Use the  
key to toggle between ENABLED /  
DISABLED to activate the control function. Press  
ENT.  
MORE ON NEXT PAGE  
SETPOINT will be the setting the control will try to  
achieve for this circuit.  
TEMPERATURE CONTROL  
RATE is a number from 1 to 3 which allows the  
algorithm to be adjusted for different evaporators.  
Arate of 1 establishes a 30 second cycle rate for the  
output; 2 establishes a 60 second cycle rate; and  
3 establishes a 90 second cycle rate. You may need  
to experiment with the rate adjustment in order to  
achieve the optimum level of performance.  
1-REFR CIRCUIT #5  
2-REFR CIRCUIT #6  
3-REFR CIRCUIT #7  
4-REFR CIRCUIT #8  
MORE ON NEXT PAGE  
OUTPUT controls the relay used by the correspond-  
ing Defrost Circuit.  
REFR CIRCUIT #1  
Important – Verify the output number between  
this temperature circuit and the connected  
defrost circuit to ensure proper energizing and  
de-energizing of solenoids. Make sure that in  
the case of electric defrosts, you haven’t select-  
ed the output that operates defrost heaters.  
TEMP CONTROL  
SETPOINT  
RATE  
ENABLED  
15 F  
3 F  
OUTPUT –- 1  
Press ESC to return to TEMP CONTROL MENU.  
Press ESC again to return to CONFIG MENU.  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
970307  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 23  
DEFROST MENU  
PROTOCOL MAIN MENU  
3-DEFROST MENU  
1-STATUS MENU  
2-CONFIG MENU  
3-DEFROST MENU  
4-MAINT MENU  
Press 3 on the Keypad to enter the Defrost sub-  
menu.  
5-ALARM MENU  
1- VIEW/SET ITEMS  
Press 1 on the Keypad to enter the VIEW/SET ITEMS  
Submenu.  
DEFROST MENU  
This screen shows three columns:  
CIRCUIT lists the defrost circuit within the  
Protocol. The numbers 1 through 8 are fixed.  
1-VIEW/SET ITEMS  
2-COPY SCHEDULE  
3-ASSIGN OUTPUTS  
4-ASSIGN CIRCUITS  
FOR SPLIT SUCT  
NAME refers to the description used to identify  
the defrost circuit.  
STATUS lists the status of each defrost circuit.  
REFR = In refrigeration  
DEFR = In defrost  
DATV = DE-activated, will not defrost.  
TERM = Defrost terminated by temp.  
N/A = Not Available or Not Installed  
DEFROST MENU  
NAME  
CIRCUIT  
STATUS  
REFR  
DEFR  
DATV  
1
2
3
4
CIRCUIT #1 NAME  
CIRCUIT #2 NAME  
CIRCUIT #3 NAME  
The horizontal arrows are used to activate or deac-  
tivate a circuit for defrost control, to force a circuit  
in or out of refrigeration or defrost go to the  
MAINTENANCE MENU. Note that the DATV status  
permanently disables the defrost function.  
CIRCUIT #4 NAME REFR  
PRESS ENT TO SET  
Use the vertical arrows to move up and down the  
circuit list.  
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
P/N 374511B  
Page 24  
Hand Held Device  
PROTOCOL  
DEFROST MENU (continued)  
DEFROST MENU  
WITH THE CURSOR ON A CIRCUIT NUMBER, press the  
CIRCUIT  
SYSTEM  
STATUS  
N/A  
ENT key to open that circuit submenu.  
5
6
7
8
00  
00  
00  
00  
CIRCUIT #6 - REFR  
N/A  
N/A  
Press the CLR key. Key in the applicable Lineup  
name. Press ENT. Repeat for NAME, NUMBER/DAY,  
DEFR LENGTH and 1ST DEFR HOUR:MINUTES.  
N/A  
PRESS ENT TO SET  
Note: To key in name, press Shift Upper to use  
the red (upper) letters and Shift Lower to use the  
blue (lower) letters.  
CIRCUIT #6 - REFR  
Three different types of defrost may be used:  
NAME  
-
-
-
-
-
-
Offtime  
Gas  
Electric  
DEFR TYPE  
NUMBER/DAY  
DEFR LENGTH  
1ST DEFR  
OFTIM  
03  
15  
Using the  
key, toggle to the desired defrost  
00:00  
00  
type. Press ENT.  
AMPERAGE  
The amperage number is used for electric  
defrosts to turn off compressors and reduce over-  
all amp draw.  
Using the  
key, toggle between ENABLED /  
CIRCUIT #6 - REFR  
DISABLED for defrost termination. Press ENT.  
DEFR TERM  
-
-
-
ENABLED  
Note: the termination signal is provided by the  
appropriate Auxiliary input (i.e., AUX1 for CKT1,  
AUX2 for CKT2, …).  
2ND DEFR  
3ND DEFR  
08:15  
16:00  
END OF DEFROSTS  
The remaining defrosts are listed. The control  
panel spaces the number of defrosts evenly  
across a 24 hour day. To customize the defrost  
schedule, press the CLR key. Key in the applic-  
able hour for defrost start. (Defrost times can be  
entered on the quarter hour – :00, :15, :30 or  
:45.) Press ENT. Press the CLR key. Key in  
the applicable minute for defrost start. Press  
ENT.  
Press ESC to return to previous screen and to  
return to VIEW / SET ITEMS MENU.  
Press ESC again to return to DEFROST MENU.  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
970307  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 25  
DEFROST MENU (continued)  
DEFROST MENU  
1-VIEW/SET ITEMS  
2-COPY SCHEDULE  
3-ASSIGN OUTPUTS  
4-ASSIGN CIRCUITS  
FOR SPLIT SUCT  
2- COPY SCHEDULE  
Press 2 on the Keypad to enter the Copy Schedule  
Submenu.  
Press the CLR key. Key in the applicable Circuit  
# for Copy From. Press ENT.  
COPY DEFROST SCHEDULE  
Press the CLR key. Key in the applicable Circuit  
# for Copy to. Press ENT.  
COPY FROM CIRCUIT  
COPY TO CIRCUIT  
-
-
00  
Press ESC to return to DEFROST MENU.  
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
P/N 374511B  
Page 26  
Hand Held Device  
PROTOCOL  
DEFROST MENU (continued)  
DEFROST MENU  
3- ASSIGN OUTPUTS  
1-VIEW/SET ITEMS  
2-COPY SCHEDULE  
3-ASSIGN OUTPUTS  
4-ASSIGN CIRCUITS  
FOR SPLIT SUCT  
Press 3 on the Keypad to enter the Assign Outputs  
Submenu.  
Press ENT to move the cursor to the value to be  
changed. Press the CLR key.  
DEFROST BOARD #1  
Key in the applicable Circuit #. Press ENT.  
OUTPUT  
CIRCUIT  
Electric defrost circuits will typically require two  
outputs (one for solenoid and one for heater con-  
trol); while offtime and gas defrost circuits require  
only one.  
1
2
3
4
00  
00  
00  
00  
Press ESC to return to DEFROST MENU.  
DEFROST BOARD #2  
OUTPUT  
CIRCUIT  
5
6
7
8
00  
00  
00  
00  
DEFROST BOARD #4  
DEFROST BOARD #3  
EXPANSION BOARD  
EXPANSION BOARD  
OUTPUT  
CIRCUIT  
OUTPUT  
CIRCUIT  
OUTPUT  
CIRCUIT  
OUTPUT  
CIRCUIT  
21  
22  
23  
24  
00  
00  
00  
00  
17  
18  
19  
20  
00  
00  
00  
00  
13  
14  
15  
16  
00  
00  
00  
00  
9
00  
00  
00  
00  
10  
11  
12  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
970307  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 27  
DEFROST MENU (continued)  
DEFROST MENU  
4- ASSIGN CIRCUITS  
FOR SPLIT SUCTION  
1-VIEW/SET ITEMS  
2-COPY SCHEDULE  
3-ASSIGN OUTPUTS  
4-ASSIGN CIRCUITS  
FOR SPLIT SUCT  
NOTE: This item only appears when the unit is  
configured for the split suction option.  
Press 4 on the Keypad to enter the Assign Circuits  
For Split Suction Submenu.  
SUCTION ASSIGNMENT  
Press ENT to move the cursor to the value to be  
changed. Press the CLR key.  
CIRCUIT  
SUCTION  
1
2
3
4
00  
00  
00  
00  
Press the left and right arrow keys to toggle  
between suctions #1 and #2.  
Press ESC to return to DEFROST MENU.  
Press ESC again to return to PROTOCOL MAIN  
MENU.  
SUCTION ASSIGNMENT  
CIRCUIT  
SUCTION  
5
6
7
8
00  
00  
00  
00  
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
P/N 374511B  
Page 28  
Hand Held Device  
PROTOCOL  
MAINT MENU  
PROTOCOL MAIN MENU  
1-STATUS MENU  
2-CONFIG MENU  
3-DEFROST MENU  
4-MAINT MENU  
4- MAINT MENU  
Press 4 on the Keypad to enter the Maintenance  
Menu Submenu. This screen has one function,  
four menus, and a second page.  
5-ALARM MENU  
The functions is: 2-CLEAR FORCE FLAG  
MAINT MENU  
1-FORCE A COMP ON  
2-CLEAR FORCE FLAG  
3-FORCE A COMP OFF  
4-FORCE A DEFR ON  
5-FORCE A DEFR OFF  
PRESS ENT FOR MORE  
Simply press 2 to activate clear function.  
Press Numbers 1, 3, 4, 5 on the Keypad to enter  
the Submenu. Key in compressor or defrost  
circuit #. Press ENT.  
The time limit on COMPRESSORS forced on/off is  
20 minutes. After time limit expires, compressors  
return to normal operation.  
FORCE A COMP ON  
The time limit for DEFROST CIRCUITS forced on is  
a function of the defrost length programmed for  
that circuit. For circuits forced out of defrost, oper-  
ation is suspended for the current defrost only.  
Normal operation resumes at the next scheduled  
defrost.  
ENTER NUMBER  
-
0
0
0
0
1
3
FORCE A COMP OFF  
ENTER NUMBER  
-
Press ESC to return to MAIN MENU.  
FORCE A DEFR ON  
ENTER NUMBER  
-
4
5
FORCE A DEFR OFF  
ENTER NUMBER  
-
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
970307  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 29  
4- MAINT MENU  
MAINT MENU  
6-CLEAR RUN METER  
7-FORCE LIGHT ON  
8-FORCE LIGHT OFF  
9-CLEAR ALM TABLE  
0-RESET CONTROL  
Press 4 on the Keypad to enter the Maintenance  
Menu Submenu.  
Press ENT to move to the second page.  
This screen has two functions and three menus.  
The two functions are:  
6-CLEAR RUN METER  
9-CLEAR ALARM TABLE  
FORCE A LIGHT ON  
ENTER NUMBER  
-
0
0
0
7
8
Simply press 6 or 9 to activate clear function.  
Press Numbers 7, 8, 0 on the Keypad to enter the  
Submenu. Key in compressor or defrost circuit #.  
Press ENT.  
FORCE A LIGHT OFF  
ENTER NUMBER  
-
Press ESC to return to MAIN MENU.  
RESET CONTROL  
Options 9 and 0 are available with Software Version 2.30 or greater. Protocol™ Control  
must be V1.30 or greater  
ENTER NUMBER  
-
0
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
P/N 374511B  
Page 30  
Hand Held Device  
PROTOCOL  
ALARM MENU  
PROTOCOL MAIN MENU  
5-ALARM MENU  
1-STATUS MENU  
2-CONFIG MENU  
3-DEFROST MENU  
4-MAINT MENU  
5-ALARM MENU  
Press 5 on the Keypad to enter the Alarm  
Submenu.  
This screen lists the last 16 alarms giving the type,  
time (24 hour clock) and date of each. Alarms  
may be continued on the next screen. To read con-  
tinued alarms, Press ENT.  
The screen will read END OF ALARMS after last  
alarm reading.  
ALARM MENU  
Press ESC to return to MAIN MENU. When exiting  
the menu, you will be prompted whether to clear  
the alarms. Press the CLR Key to remove the cur-  
rent alarm.  
A01 - LO SUCTION PRES  
TIME 01:56 01/21  
END OF ALARMS  
Types of Alarms  
•POWER DOWN  
•POWER RESET  
•HI TEMPALARM – AUXILIARY INPUT  
•MODULES IN BACKUP MODE  
•HIGH SUCTION PRESSURE*  
•LOW SUCTION PRESSURE*  
•HIGH HEAD PRESSURE  
•LOW HEAD PRESSURE  
•ALL COMPRESSORS OFF ALARM*  
•LO TEMPALARM – AUXILIARY INPUT  
•HI ALARM T1  
•LO ALARM T1  
•HI ALARM T2  
•LO ALARM T2  
•HI ALARM T3  
•LO ALARM T3  
•MEMORY CHECK ERROR  
•DEFROST MEMORY CHECK ERROR  
•HI ALARM T4  
•LO ALARM T4  
•HI ALARM T5  
•LO ALARM T5  
•HI ALARM T6  
•LO ALARM T6  
•HI ALARM T7  
•LO ALARM T7  
•HI ALARM T8  
•LO ALARM T8  
*Denotes switchback. Control operated by mechan-  
ical low pressure switch. No defrosts occur during  
switchback.  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
970307  
 
P/N 374511B  
Hand Held Device  
PROTOCOL  
Page 31  
Mixmatch Programming Worksheet  
Compr #  
1
2
3
4
5
6
Total  
Column  
Value  
HP  
Total  
HP  
Column Value  
1
2
4
8
16  
32  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
Mixmatch Programming Worksheet  
Compr #  
1
2
3
4
5
6
Total  
Column  
Value  
HP  
Total  
HP  
Column Value  
1
2
4
8
16  
32  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
970307  
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)  
 
®
CORPORATION  
CONDENSING UNITS AND REFRIGERATION SYSTEMS  
This warranty is made to the original purchaser user and is NOT TRANSFERABLE.  
ONE YEAR LIMITED WARRANTY  
1. Hussmann Corporation warrants the new Hussmann Equipment, and all parts thereof, to be free of defects in mate-  
rial and workmanship at time of purchase.  
2. Hussmann's obligation under this warranty shall be limited to repairing or exchanging free of charge any part or  
parts of the system or unit, supplied by Hussmann Corporation, Bridgeton, Missouri, F.O.B. factory or the nearest  
authorized parts depot, which may prove to be defective within one year from date of original installation (not to  
exceed fifteen months from date of shipment from factory) and which is proven to the satisfaction of Hussmann to  
be thus defective.  
3. THIS WARRANTY TO REPAIR OR REPLACE ABOVE RECITED, IS THE ONLY WARRANTY EXPRESSED, IMPLIED,  
OR STATUTORY MADE BY HUSSMANN WITH RESPECT TO THE EQUIPMENT ABOVE LISTED, AND IT NEITHER  
ASSUMES NOR AUTHORIZES ANY PERSON TO ASSUME FOR IT, ANY OTHER OBLIGATION OR LIABILITY IN  
CONNECTION WITH THE SALE OF SAID EQUIPMENT OR ANY PART THEREOF.  
EXCLUSIONS  
1. THIS WARRANTY SHALL NOT APPLY TO LOSS OF FOOD DUE TO FAILURE FOR ANY REASON.  
2. HUSSMANN SHALL NOT BE LIABLE:  
a. For any repairs or replacements made by buyer without written consent of Hussmann, or when equipment is  
installed or operated in a manner contrary to printed instructions covering installation and service which accom-  
panied or was supplied for such equipment.  
b. For any damages, delays, losses, direct or consequential, caused by defects, nor for damages caused by short  
or reduced supply of material, fire, flood, strikes, acts of God or circumstances beyond its control.  
c. When the failure or defect of any part or parts is incident to ordinary wear, accident, abuse or misuse, or when  
the serial number of the equipment has been removed, defaced, altered or tampered with.  
d. When equipment is operated on low or improper voltages, or put to use other than normally recommended by  
Hussmann.  
e. For payment of any removal or installation charges of warranted parts.  
f. For payment of refrigerant losses for any reasons.  
g. When equipment is moved to an address other than the original installation.  
ADDITIONAL FOUR YEAR PROTECTION PLAN FOR MOTOR/COMPRESSOR ASSEMBLY ONLY  
(OPTIONAL – MUST BE PURCHASED PRIOR TO SHIPMENT  
OF CONDENSING UNIT OR REFRIGERATION SYSTEM)  
In addition to the above One Year Warranty on said Condensing Unit or Refrigeration System, Hussmann Corporation,  
agrees to repair or replace the motor compressor only, with a motor compressor of like or authorized similar capacity  
(F.O.B. Factory or nearest Vendor author ized parts depot), at any time during this four year period immedi-  
ately f ollowing the e xpiration of the above one year w arranty, if proven to the satisfaction of Hussmann,  
that the compressor is inoper ative due to defects in factory workmanship or material under normal use and  
service. Hussmann reserves the right to inspect the job site, installation and reason for f ailure.  
The Four Year Protection Plan does not include controls, relay, capacitor, ov erload protector, v alve plates, oil  
pumps, gaskets or any e xternal part on the motor compressor replaceable in the field, or any other part of the  
refrigeration system.  
GENERAL CONDITIONS  
No service or labor charges incidental to the replacement of parts during the First Year Warranty and the succeeding  
four years under the protection plan will be allowed under the terms thereof.  
All claims must be presented and completed within six months from date of failure. Claims must be accompanied by  
the vendor invoice and credit showing model and serial number of compressor that failed and the new replacement  
compressor. Records should be maintained with copies of above documents to show any inwarranty replacements with-  
in the One Year Warranty and should be submitted along with claim to show original compressor model and serial num-  
ber.  
HUSSMANN CORPORATION  
Bridgeton, Missouri 63044 – U.S.A.  
8/92  
 

Haier Dehumidifier DM32M User Manual
Harman Stove Company Stove P68 User Manual
Hasbro Board Games Hunchback of Notre Dame User Manual
Honeywell Scanner 800 Series User Manual
Honeywell Thermostat CT8602 User Manual
HP Hewlett Packard Copier 4100N User Manual
HP Hewlett Packard Saw 438A User Manual
Husky Pressure Washer 1750 US User Manual
Husqvarna Automobile 4210 E User Manual
Husqvarna Washer DWF 7589 User Manual