Bryant Electric Air Conditoner 597C User Manual

installation and  
597C  
start-up instructions  
12 SEER  
SPLIT-SYSTEM  
AIR CONDITIONER  
Cancels: II 597C-18-4  
II 597C-18-5  
11-00  
NOTE: Read the entire instruction manual before starting the  
installation.  
This symbol indicates a change since the last issue.  
SAFETY CONSIDERATIONS  
Improper installation, adjustment, alteration, service, maintenance,  
or use can cause explosion, fire, electrical shock, or other  
conditions which may cause death, personal injury, or property  
damage. Consult a qualified installer, service agency, or your  
distributor or branch for information or assistance. The qualified  
installer or agency must use factory-authorized kits or accessories  
when modifying this product. Refer to the individual instructions  
packaged with the kits or accessories when installing.  
Follow all safety codes. Wear safety glasses, protective clothing,  
and work gloves. Use quenching cloth for brazing operations.  
Have fire extinguisher available. Read these instructions thor-  
oughly and follow all warnings or cautions included in literature  
and attached to the unit. Consult local building codes and National  
Electrical Code (NEC) for special requirements.  
Recognize safety information. This is the safety-alert symbol  
.
When you see this symbol on the unit and in instructions or  
manuals, be alert to the potential for personal injury.  
A98515  
Fig. 1—Model 597C  
Understand the signal words DANGER, WARNING, and CAU-  
TION. These words are used with the safety-alert symbol. DAN-  
GER identifies the most serious hazards which will result in severe  
personal injury or death. WARNING signifies hazards which  
could result in personal injury or death. CAUTION is used to  
identify unsafe practices which would result in minor personal  
injury or product and property damage. NOTE is used to highlight  
suggestions which will result in enhanced installation, reliability,  
or operation.  
6. Avoid direct tubing contact with water pipes, duct work,  
floor joists, wall studs, floors, and walls.  
7. Do not suspend refrigerant tubing from joists and studs with  
a rigid wire or strap that comes in direct contact with tubing.  
(See Fig. 2.)  
8. Ensure that tubing insulation is pliable and completely  
surrounds vapor tube.  
9. When necessary, use hanger straps which are 1 in. wide and  
conform to shape of tubing insulation. (See Fig. 2.)  
WARNING: Before installing, modifying, or servicing  
system, main electrical disconnect switch must be in the  
OFF position. There may be more than 1 disconnect  
switch. Lock out and tag switch with a suitable warning  
label. Electrical shock can cause personal injury or death.  
10. Isolate hanger straps from insulation by using metal sleeves  
bent to conform to shape of insulation.  
When outdoor unit is connected to factory-approved indoor unit,  
outdoor unit contains system refrigerant charge for operation with  
indoor unit of the same size when connected by 15 ft of  
field-supplied or factory-accessory tubing. For proper unit opera-  
tion, check refrigerant charge using charging information located  
on control-box cover.  
INTRODUCTION AND RECOMMENDATIONS  
NOTE: In some cases noise in the living area has been traced to  
gas pulsations from improper installation of equipment.  
IMPORTANT: Maximum liquid-line size is 3/8-in. O.D. for all  
residential applications including long line.  
IMPORTANT: Always install a liquid-line filter drier on any  
system using an existing field service lineset and/or indoor  
evaporator coil or fan coil. Also, always use liquid line filter driers  
on burnout compressor replacements. Refer to Product Data Sheets  
for appropriate part number. Obtain filter driers from your local  
distributor or branch.  
1. Locate unit away from windows, patios, decks, etc. where  
unit operation sounds may disturb customer.  
2. Ensure that vapor- and liquid-tube diameters are appropriate  
to capacity of unit.  
3. Run refrigerant tubes as directly as possible by avoiding  
unnecessary turns and bends.  
INSTALLATION  
I. CHECK EQUIPMENT AND JOB SITE  
4. Leave some slack between structure and unit to absorb  
vibration.  
A. Unpack Unit  
5. When passing refrigerant tubes through the wall, seal  
opening with RTV or other pliable silicon-based caulk. (See  
Fig. 2.)  
Move to final location. Remove carton, taking care not to damage  
unit.  
—1—  
TABLE 1REFRIGERANT CONNECTIONS AND RECOMMENDED LIQUID- AND VAPOR-TUBE DIAMETERS (IN.)  
LIQUID  
Connection Diameter  
VAPOR  
Connection Diameter  
VAPOR (LONG LINE)  
Connection Diameter Tube Diameter  
UNIT  
SIZE  
Tube Diameter  
Tube Diameter  
018, 024  
030, 036  
042, 048  
060  
3/8  
3/8  
3/8  
3/8  
3/8  
3/8  
3/8  
3/8  
5/8  
3/4  
7/8  
7/8  
5/8  
3/4  
5/8  
3/4  
7/8  
7/8  
3/4  
7/8  
7/8  
11/8  
11/8  
11/8  
NOTES:  
1. Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult Residential Long-Line Application Guideline.  
2. Do not apply capillary-tube indoor coils to these units.  
For buried-line applications greater than 36 in., consult your local  
distributor.  
WARNING: The unit cabinet must have an uninter-  
rupted or unbroken ground to minimize personal injury if  
an electrical fault should occur. The ground may consist  
of electrical wire or metal conduit when installed in  
accordance with existing electrical codes. Failure to  
follow this warning can result in an electric shock, fire, or  
death.  
If refrigerant tubes or indoor coil are exposed to atmosphere, they  
must be evacuated to 500 microns to eliminate contamination and  
moisture in the system.  
A. Outdoor Unit Connected to Factory-Approved In-  
door Unit  
Outdoor unit contains correct system-refrigerant charge for opera-  
tion with indoor unit of same size when connected by 15 ft of  
field-supplied or factory-accessory tubing. Check refrigerant  
charge for maximum efficiency.  
B. Connect Ground and Power Wires  
Connect ground wire to ground connection in control box for  
safety. Connect power wiring to contactor as shown in Fig. 4.  
B. Refrigerant Tubing  
DISCONNECT  
PER N. E. C. AND/OR  
LOCAL CODES  
Connect tubing to fittings on outdoor unit vapor- and liquid-  
service valves. (See Table 1.) Use refrigerant-grade tubing.  
CONTACTOR  
C. Sweat Connection  
FIELD POWER  
WIRING  
CAUTION: To avoid valve damage while brazing, ser-  
vice valves must be wrapped in a heat-sinking material,  
such as a wet cloth.  
FIELD GROUND  
Service valves are closed from factory and ready for brazing. After  
wrapping service valve with a wet cloth, tubing set can be brazed  
to service valve using either silver-bearing or non-silver-bearing  
brazing material. Consult local code requirements. Refrigerant  
tubing and indoor coil are now ready for leak testing. This check  
should include all field and factory joints.  
WIRING  
GROUND  
LUG  
A91056  
Fig. 4Line Power Connections  
C. Connect Control Wiring  
VII. MAKE ELECTRICAL CONNECTIONS  
Route 24v control wires through control-wiring grommet and  
connect leads to control wiring. (See Fig. 5.)  
Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If  
thermostat is located more than 100 ft from unit, as measured  
along the control-voltage wires, use No. 16 AWG color-coded  
wire to avoid excessive voltage drop.  
WARNING: To avoid personal injury or death, do not  
supply power to unit with compressor terminal-box cover  
removed.  
All wiring must be NEC Class 1 and must be separated from  
incoming power leads.  
Use furnace transformer, fan-coil transformer, or accessory trans-  
former for control power, 24v/40va minimum.  
NOTE: Use of available 24v accessories may exceed the mini-  
mum 40va power requirement. Determine total transformer load-  
ing and increase the transformer capacity or split the load with an  
accessory transformer as required.  
Be sure field wiring complies with local and national fire, safety,  
and electrical codes, and voltage to system is within limits shown  
on unit-rating plate. Contact local power company for correction of  
improper voltage. See unit-rating plate for recommended circuit-  
protection device.  
NOTE: Operation of unit on improper line voltage constitutes  
abuse and could affect unit reliability. See unit-rating plate. Do not  
install unit in system where voltage may fluctuate above or below  
permissible limits.  
IMPORTANT: Check factory wiring and wire connections to  
ensure terminations are secured properly. Check wire routing to  
ensure wires are not in contact with tubing, sheet metal, etc.  
NOTE: Use copper wire only between disconnect switch and  
unit.  
VIII. COMPRESSOR CRANKCASE HEATER  
NOTE: Install branch-circuit disconnect of adequate size per  
NEC to handle unit-starting current. Locate disconnect within sight  
from and readily accessible from unit, per Section 440-14 of NEC.  
When equipped with a crankcase heater, furnish power to heater a  
minimum of 24 hr before starting unit. To furnish power to heater  
only, set thermostat to OFF and close electrical disconnect to  
outdoor unit.  
A. Route Ground and Power Wires  
Remove access panel to gain access to unit wiring. Extend wires  
from disconnect through power wiring hole provided and into  
unit-control box.  
A crankcase heater is required if refrigerant tubing is longer than  
50 ft. Refer to Residential Split-System Long-Line Application  
Guideline.  
3—  
TABLE 2ACCESSORY USAGE  
REQUIRED FOR  
LOW-AMBIENT  
APPLICATIONS  
(BELOW 55°F)  
REQUIRED FOR  
REQUIRED FOR  
SEA COAST  
APPLICATIONS  
(WITHIN 2 MILES)  
LONG-LINE  
APPLICATIONS*  
(OVER 50 FT)  
ACCESSORY  
Crankcase Heater  
Evaporator Freeze Thermostat  
Winter-Start Control  
Accumulator  
Yes  
Yes  
Yes†  
No  
Yes  
No  
No  
No  
No  
No  
No  
No  
Compressor Start-Assist  
Capacitor and Relay  
Yes  
Yes  
No  
No  
No  
Low-Ambient Controller,  
MotorMasterT Control,  
or  
Yes  
No  
Low-Ambient Pressure Switch  
See Low-Ambient  
Instructions  
Wind Baffle  
No  
Coastal Filter  
Support Feet  
No  
No  
No  
Yes  
Recommended  
Recommended  
Liquid-Line Solenoid Valve  
See Long-Line  
Application  
Guideline  
or  
No  
No  
No  
Hard-Shutoff TXV  
Ball-Bearing Fan Motor  
Yes‡  
No  
*For tubing-line sets between 50 and 175 ft, refer to Residential Split-System Long-Line Application Guideline.  
Only when low-pressure switch is used.  
Required for Low-Ambient Controller (full-modulation feature) and MotorMasterT Control only.  
IX. INSTALL ELECTRICAL ACCESSORIES  
4. Set room thermostat at desired temperature. Be sure set  
point is below indoor ambient temperature.  
Refer to the individual instructions packaged with kits or acces-  
sories when installing.  
5. Set room thermostat to COOL and fan control to ON or  
AUTO mode, as desired. Operate unit for 15 minutes.  
Check system-refrigerant charge.  
X. START-UP  
CAUTION: To prevent compressor damage or personal  
injury, observe the following:  
Do not overcharge system with refrigerant.  
Do not operate unit in a vacuum or at negative pressure.  
Do not disable low-pressure switch.  
In scroll-compressor applications:  
Dome temperatures may be hot.  
In 3-phase application, incorrect phasing will cause  
reverse rotation, resulting in elevated noise levels, equal-  
ized pressures, and reduced current draw. Correct by  
reversing power connection L1 and L2 on contactor.  
A. Sequence of Operation  
Turn on power to indoor and outdoor units. Transformer is  
energized.  
On a call for cooling, thermostat makes circuits R-Y and R-G.  
Circuit R-Y energizes contactor, starting outdoor-fan motor and  
compressor circuit. R-G energizes indoor unit-blower relay, start-  
ing indoor-blower motor on high speed.  
When thermostat is satisfied, its contacts open, de-energizing  
contactor and blower relay. Compressor and motors stop.  
If indoor unit is equipped with a time-delay relay circuit, the  
indoor blower will run an additional 90 sec to increase system  
efficiency.  
XI. CHECK CHARGE  
A. Unit Charge  
CAUTION: To prevent personal injury wear safety  
glasses, protective clothing, and gloves when handling  
refrigerant and observe the following:  
Factory charge is shown on unit-rating plate. Adjust charge by  
following procedure shown on charging tables located on unit.  
Back-seating service valves are not equipped with  
Schrader valves. Fully back seat (counterclockwise)  
valve stem before removing gage-port cap.  
Front-seating service valves are equipped with Schrader  
valves.  
NOTE: If superheat- or subcooling-charging conditions are not  
favorable, charge must be weighed in accordance with unit-rating  
plate ± 0.6 oz/ft of 3/8-in. liquid line above or below 15 ft  
respectively.  
EXAMPLE:  
25 ft 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge  
CAUTION: Do not vent refrigerant to atmosphere. Re-  
cover during system repair or final unit disposal.  
B. Cooling Only Procedure  
The following procedure is valid when indoor airflow is within ±  
21 percent of its rated CFM.  
1. Fully back seat (open) liquid- and vapor-tube service  
valves.  
1. Operate unit a minimum of 10 minutes before checking  
charge.  
2. Unit is shipped with valve stem(s) front seated (closed) and  
caps installed. Replace stem caps after system is opened to  
refrigerant flow. Replace caps finger-tight and tighten with  
wrench an additional 1/12 turn.  
2. Measure suction pressure by attaching a gage to suction-  
valve service port.  
3. Measure suction temperature by attaching an accurate  
thermistor-type or electronic thermometer to suction line at  
service valve.  
3. Close electrical disconnects to energize system.  
4—  
BRYANT  
NON-PROGRAMMABLE  
THERMOSTAT  
BRYANT  
NON-PROGRAMMABLE  
THERMOSTAT  
FA, FB, FC,  
FD, FF  
FAN COIL  
AIR  
SINGLE-STAGE  
FURNACE  
AIR  
CONDITIONER  
MODEL AC  
CONDITIONER  
MODEL AC  
24 VAC HOT  
24 VAC COM  
24 VAC HOT  
24 VAC COM  
R
C
R
C
W
Y
R
C
R
C
SEE  
NOTE 2  
SEE  
NOTE 2  
C
HEAT STAGE 1 W/W1  
C
HEAT STAGE 1 W/W1  
W2  
COOL STAGE 1  
Y/Y2  
COOL STAGE 1  
INDOOR FAN  
Y/Y2  
G
INDOOR FAN  
G
G
G
A97359  
A97360  
BRYANT  
PROGRAMMABLE  
THERMOSTAT  
MODEL AC  
BRYANT  
PROGRAMMABLE  
THERMOSTAT  
MODEL AC  
FA, FB,  
FC, FD, FF  
FAN COIL  
AIR  
CONDITIONER  
SINGLE-STAGE  
FURNACE  
AIR  
CONDITIONER  
R
G
R
G
R
G
24 VAC HOT  
R
24 VAC HOT  
INDOOR FAN  
HEAT STAGE 1  
G
INDOOR FAN  
HEAT STAGE 1  
W2  
W/W1  
Y/Y2  
W
Y
W/W1  
Y/Y2  
COOL STAGE 1  
NOT USED  
COOL STAGE 1  
NOT USED  
O/W2  
Y1/ W2  
O/W2  
Y1/W2  
SEE  
NOTE 2  
SEE  
NOTE 2  
C
C
NOT USED  
NOT USED  
C
C
B
L
24 VAC COM  
NOT USED  
NOT USED  
C
B
L
C
24 VAC COM  
NOT USED  
NOT USED  
S1  
S2  
S1  
S2  
OPTIONAL  
OUTDOOR  
SENSOR  
OPTIONAL  
OUTDOOR  
SENSOR  
CONNECTION  
CONNECTION  
A97361  
A97362  
OTHER  
NON-PROGRAMMABLE  
AC THERMOSTAT  
OTHER  
NON-PROGRAMMABLE  
AC THERMOSTAT  
FA, FB, FC,  
FD, FF  
SINGLE-STAGE  
FURNACE  
AIR  
AIR  
CONDITIONER  
FAN COIL CONDITIONER  
R
R
C
24 VAC HOT  
24 VAC HOT  
R
R
SEE  
NOTE 2  
C
C
W
Y
HEAT STAGE 1  
W
Y
SEE  
NOTE 2  
C
HEAT STAGE 1  
COOL STAGE 1  
INDOOR FAN  
W
Y
W2  
COOL STAGE 1  
INDOOR FAN  
G
G
G
G
A97367  
A97366  
Fig. 5Typical 24v Circuit Connections  
5—  
BRYANT  
NON-PROGRAMMABLE  
THERMOSTAT  
AIR  
FK4C  
FAN COIL  
CONDITIONER  
MODEL AC  
J1 JUMPER  
DH  
R
R
C
24 VAC HOT  
24 VAC COM  
HEAT STAGE 1  
C
J2 JUMPER  
W/W1  
Y/Y2  
G
W1  
W2  
Y/Y2  
G
SEE  
NOTE 2  
C
COOL STAGE 1  
INDOOR FAN  
O
Y1  
A97363  
OTHER  
NON-PROGRAMMABLE  
AC THERMOSTAT  
AIR  
FK4C  
FAN COIL  
CONDITIONER  
J1 JUMPER  
DH  
R
LEGEND  
24 VAC HOT  
R
C
24-V FACTORY WIRING  
24-V FIELD WIRING  
FIELD SPLICE CONNECTION  
CONTACTOR  
J2  
JUMPER  
W
Y
HEAT STAGE 1  
W1  
W2  
Y/Y2  
G
SEE  
NOTE 2  
C
COOL STAGE 1  
INDOOR FAN  
C
G
O
A97368  
Y1  
A97365  
BRYANT  
PROGRAMMABLE  
THERMOSTAT  
MODEL AC  
AIR  
FK4C  
FAN COIL  
CONDITIONER  
DH  
R
R
24 VAC HOT  
NOTES:  
G
INDOOR FAN  
HEAT STAGE 1  
J1 JUMPER  
J2 JUMPER  
1. BRYANT THERMOSTAT-WIRING DIAGRAMS ARE ONLY  
ACCURATE FOR MODEL NUMBERS BEGINNING WITH  
TSTAT_ _ _ _ _ _ _.  
2. WIRING MUST CONFORM TO NEC OR LOCAL CODES.  
3. SOME UNITS ARE EQUIPPED WITH PRESSURE  
SWITCH(ES), TEMPERATURE SWITCH, OR 5MINUTE  
COMPRESSOR-CYCLE PROTECTION. CONNECT 24V FIELD  
WIRING TO FACTORY-PROVIDED STRIPPED LEADS.  
4. A LIQUID-LINE SOLENOID VALVE IS REQUIRED ON SOME  
UNITS.  
G
W/W1  
Y/Y2  
W1  
W2  
COOL STAGE 1  
NOT USED  
O/W2  
Y1/W2  
Y/Y2  
NOT USED  
SEE  
NOTE 2  
C
5. THERMOSTATS ARE FACTORY CONFIGURED WITH  
C
Y1  
O
C
B
L
24 VAC COM  
NOT USED  
NOT USED  
5MINUTE  
4CYCLESPERHOUR  
COMPRESSOR-CYCLE  
LIMIT.  
PROTECTION  
SEE THERMOSTAT-  
AND  
INSTALLATION INSTRUCTIONS FOR DETAILS.  
6. TO STAGE ELECTRIC-RESISTANCE HEAT, CONSULT  
OUTDOOR-THERMOSTAT INSTALLATION INSTRUCTIONS.  
S1  
S2  
OPTIONAL  
OUTDOOR  
SENSOR  
CONNECTION  
A97364  
Fig. 5Typical 24v Circuit Connections (Continued)  
6—  
TABLE 3SUPERHEAT CHARGING  
OUTDOOR  
TEMP  
EVAPORATOR ENTERING AIR TEMPERATURE (°F WB)  
50  
52  
54  
56  
58  
60  
62  
64  
66  
68  
70  
72  
74  
76  
(°F)  
55  
60  
9
12  
10  
6
14  
12  
10  
7
17  
15  
13  
10  
6
20  
18  
16  
13  
9
23  
21  
19  
16  
12  
8
26  
24  
21  
19  
15  
12  
8
29  
27  
24  
21  
18  
15  
11  
9
32  
30  
27  
24  
21  
18  
15  
13  
10  
8
35  
33  
30  
27  
24  
21  
19  
16  
14  
12  
9
37  
35  
33  
30  
28  
25  
22  
20  
18  
15  
13  
11  
8
40  
38  
36  
33  
31  
28  
26  
24  
22  
20  
17  
15  
14  
42  
40  
38  
36  
34  
31  
30  
27  
25  
23  
22  
20  
18  
45  
43  
41  
39  
37  
35  
33  
31  
29  
27  
26  
25  
23  
7
65  
70  
75  
80  
5
85  
90  
5
95  
6
100  
105  
110  
115  
5
6
Where a dash () appears, do not attempt to charge system under these conditions, or refrigerant slugging may occur. Charge must be weighed in.  
NOTE: Superheat °F is at low-side service port.  
4. Measure outdoor air dry-bulb temperature with thermom-  
eter.  
XII. FINAL CHECKS  
IMPORTANT: Before leaving job, be sure to do the following:  
5. Measure indoor air (entering indoor coil) wet-bulb tempera-  
ture with a sling psychrometer.  
1. Securely fasten all panels and covers.  
2. Tighten service valve stem caps to 1/12-turn past finger  
tight.  
6. Refer to Table 3. Find outdoor temperature and evaporator  
entering air wet-bulb temperature. At this intersection, note  
superheat.  
3. Leave Users Manual with owner. Explain system operation  
and periodic maintenance requirements outlined in manual.  
7. Refer to Table 4. Find superheat temperature located in item  
6 and suction pressure. At this intersection, note suction-  
line temperature.  
4. Fill out Dealer Installation Checklist and place in customer  
file.  
8. If unit has a higher suction-line temperature than charted  
temperature, add refrigerant until charted temperature is  
reached.  
CARE AND MAINTENANCE  
For continuing high performance and to minimize possible equip-  
ment failure, periodic maintenance must be performed on this  
equipment.  
9. If unit has a lower suction-line temperature than charted  
temperature, reclaim refrigerant until charted temperature is  
reached.  
Frequency of maintenance may vary depending upon geographic  
areas, such as coastal applications.  
10. If outdoor air temperature or pressure at suction valve  
changes, charge to new suction-line temperature indicated  
on chart.  
See the Users Information Manual for this equipment for fre-  
quency and type of maintenance required.  
7—  
TABLE 4REQUIRED SUCTION-LINE TEMPERATURE (°F)  
SUPERHEAT  
TEMP  
SUCTION PRESSURE AT SERVICE PORT (PSIG)  
61.5  
64.2  
67.1  
70.0  
73.0  
76.0  
79.2  
82.4  
85.7  
(°F)  
0
35  
37  
39  
41  
43  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
37  
39  
41  
43  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
39  
41  
43  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
41  
43  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
43  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
83  
45  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
83  
85  
47  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
83  
85  
87  
49  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
83  
85  
87  
89  
51  
53  
55  
57  
59  
61  
63  
65  
67  
69  
71  
73  
75  
77  
79  
81  
83  
85  
87  
89  
91  
2
4
6
8
10  
12  
14  
16  
18  
20  
22  
24  
26  
28  
30  
32  
34  
36  
38  
40  
SERVICE TRAINING  
Packaged Service Training programs are an excellent way to increase your  
knowledge of the equipment discussed in this manual, including:  
Unit Familiarization  
Installation Overview  
Maintenance  
Operating Sequence  
A large selection of product, theory, and skills programs is available, using popular  
video-based formats and materials. All include video and/or slides, plus companion  
book.  
Classroom Service Training plus "hands-on" the products in our labs can mean  
increased confidence that really pays dividends in faster troubleshooting, fewer  
callbacks. Course descriptions and schedules are in our catalog.  
CALL FOR FREE CATALOG 1-800-962-9212  
[ ] Packaged Service Training  
[ ] Classroom Service Training  
A94328  
© 2000 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231  
Printed in U.S.A.  
597c185  
Catalog No. 5359-704  
8—  

Blizzard Entertainment Blizzard Power Plow 810SS User Manual
Brother MFC 8840D User Manual
Brother Model MFC 5200C User Manual
Brother VERSION 0 MFC 290C User Manual
Epson Stylus CX6600 User Manual
Faria Instruments Commander User Manual
Friedrich 230 VoltsUE12 User Manual
Genie Air Conditioner AG_06 User Manual
Haier Air Conditioner HW 18EMA13T3 User Manual
Haier Commercial Cool CPN10XHJ User Manual